Option Configuration
The Option Configuration submenu allows setting values for the following unit options:
-
Fuel Tank Size – Select the correct fuel tank size for the unit (50, 75, 80, 125 gallon).
-
Fuel Level Sensor – Select if the unit is equipped with a fuel level sensor (YES / NO).
Note Only applies to gensets with the standard ultrasonic fuel sensor connected directly to the SG+1.5 controller, for gensets equipped with telematics fuel level sensor option needs to be set to NO. -
Fuel Low Limit - Set fuel level at which a fuel level warning is set.
-
Restarts - Set number of times the unit will attempt to restart after a failed start (default 1).
-
Speed Solenoid - Select if the unit is equipped with a speed solenoid (YES / NO) (SG 3000e Only).
-
HRG Gizmo - Select if the unit is equipped with a HRG Gizmo (YES / NO).
-
Water in Fuel - Select if the unit is equipped with a water level sensor in the fuel filter (SG5000 Only)
-
Composit - Telematics installed, will auto select (Yes / No).
-
HM1 Thredshold - Set the number of hours for the HM1 hour meter.
-
HM2 Thredshold - Set the number of hours for the HM2 hour meter.
To enter the Option Configuration submenu complete the following steps:
-
Place the On/Off switch in the “ON” position.
-
Press the ENTER key or the ESCAPE key to enter the Main Menu, if necessary.
-
Press the UP or DOWN key to scroll up or down through the Main Menu to the Configuration option.
-
Press the ENTER key to enter the Configuration menu.
-
Press the UP or DOWN key to scroll up or down through the Configuration Menu to the Option Configuration submenu.
-
Press the ENTER key to enter the Option Configuration submenu.
-
Press the UP or DOWN key to scroll up or down through the options.
-
Press the ESCAPE key to return to the Option Configuration Menu.
-