Option Configuration

The Option Configuration submenu allows setting values for the following unit options:

  • Fuel Tank Size – Select the correct fuel tank size for the unit (50, 75, 80, 125 gallon).

  • Fuel Level Sensor – Select if the unit is equipped with a fuel level sensor (YES / NO).

    Note Only applies to gensets with the standard ultrasonic fuel sensor connected directly to the SG+1.5 controller, for gensets equipped with telematics fuel level sensor option needs to be set to NO.
  • Fuel Low Limit - Set fuel level at which a fuel level warning is set.

  • Restarts - Set number of times the unit will attempt to restart after a failed start (default 1).

  • Speed Solenoid - Select if the unit is equipped with a speed solenoid (YES / NO) (SG 3000e Only).

  • HRG Gizmo - Select if the unit is equipped with a HRG Gizmo (YES / NO).

  • Water in Fuel - Select if the unit is equipped with a water level sensor in the fuel filter (SG5000 Only)

  • Composit - Telematics installed, will auto select (Yes / No).

  • HM1 Thredshold - Set the number of hours for the HM1 hour meter.

  • HM2 Thredshold - Set the number of hours for the HM2 hour meter.

To enter the Option Configuration submenu complete the following steps:

  1. Place the On/Off switch in the “ON” position.

  2. Press the ENTER key or the ESCAPE key to enter the Main Menu, if necessary.

  3. Press the UP or DOWN key to scroll up or down through the Main Menu to the Configuration option.

  4. Press the ENTER key to enter the Configuration menu.

  5. Press the UP or DOWN key to scroll up or down through the Configuration Menu to the Option Configuration submenu.

  6. Press the ENTER key to enter the Option Configuration submenu.

    • Press the UP or DOWN key to scroll up or down through the options.

    • Press the ESCAPE key to return to the Option Configuration Menu.