Alarm List Menu SG+ 1.5

The Alarm List Menu displays alarms. Alarms are recorded in the controller memory to simplify unit diagnostic procedures. The alarms are listed in the reverse order of their occurrence. The Alarm LED flashes if a shutdown alarm is present. Enter the Alarm List Menu to view the and acknowledge the alarms.

Alarm Types

There are two types of alarms:

  • Delayed Restart Alarm: Delayed restart alarms indicate the unit has stopped temporarily because of a problem or to prevent damage to the unit. The unit will attempt to restart in 20 minutes. The display will show information about the unit in the message screen and the time left to the restart attempt. A delayed restart alarm becomes a shutdown alarm after the third failed restart attempt in an hour.

  • Shutdown Alarm: The Alarm LED flashes and unit stops. Shutdown alarms indicate the unit has been stopped to prevent damage to the unit. The condition must be corrected before restarting the unit.

Displaying and Acknowledging Alarms

Enter the Alarm List Menu to view and acknowledge the alarms as follows:

  1. Place the On/Off switch in the “ON” position.

  2. Press the ALARM key to enter the Alarm List Menu directly. Or Enter the Alarm List Menu through the Main Menu as follows:

    • Press the ENTER key or the ESCAPE key to enter the Main Menu, if necessary.

    • Press the UP or DOWN key to scroll up or down through the Main Menu to the Alarm List Menu.

    • Press the ENTER key to enter the Alarm List Menu.

  3. The Alarm List Menu will appear on the display. It shows the most recent alarm and the following information:

    • The alarm code (100 through 604).

    • The position of the alarm in the list of recorded alarms. For example, 1/2 means alarm one of two.

    • The alarm text.

    • The alarm status (Active or Acknowledged).

    • Write down the alarm code and the alarm text.

  4. Write down the alarm code and the alarm text.

  5. Press the ENTER key to acknowledge the alarm. The Alarm LED will continue flashing until the active alarms (and messages) have been acknowledged.

  6. Press the DOWN key to scroll down to the next alarm, if necessary.

  7. Write down the alarm code and the alarm text.

  8. Press the ENTER key to acknowledge the alarm.

  9. Repeat steps 6 through 8 until all active alarms have been written down and acknowledged.

  10. Press the ESCAPE key to return to the Main Menu.