Configuration Menu

The Configuration Menu is used to configure the following controller functions (also see the flowcharts on the following pages):

    Warning
  • Equipment Damage and Risk of Injury
  • The unit will begin a start sequence and attempt to start when Configuration Mode is exited on the controller.

  • Controls - Set engine RPM control mode to AUTO / HIGH / LOW for service procedures.

  • Unit Configuration - Set unit Engine type, Generator type, Genset type, Serial Number, and Output Voltage settings.

  • Option Configuration - Set controller selectable options such as Tank Size, Fuel Sensor, Low Fuel Limit, Restarts, Speed Solenoid, HRG Gizmo, Water in Fuel, Composite, HM1 Threshold, HM2 Threshold.

  • System Configuration - Set the unit ID number. The ID number is not the unit serial #; it is a number created by the unit user, operator, or owner.

  • MISCH Configuration - The default setting is OFF. When this is set to ON, the controller will reset all run timers to 0 when the unit is turned Off and then back On.

To enter the Configuration Menu, complete the following steps:

  1. Place the On/Off switch in the “ON” position.

  2. Press the ENTER key or the ESCAPE key to enter the Main Menu, if necessary.

  3. Press the UP or DOWN key to scroll up or down through the Main Menu to the Configuration Menu.

  4. Press the ENTER key to enter the Configuration Menu.