Compressor does not operate - no amperage draw. |
Controller on; unit start sequence still timing. |
Wait up to two minutes for compressor start-up. |
No power to unit (condenser and evaporator fans do not operate). |
Locate fault
and repair: power source, power plug, CB1 main circuit breaker, motor
contactors, motor terminals, motor. |
Open in 29 Vac control circuit. |
Check fuses and On/Off switch. Replace or repair as required. |
Container temperature does not demand compressor operation. |
Adjust controller setpoint. |
Compressor contactor inoperative. |
Replace compressor contactor. |
No output signal from controller. |
Diagnose and replace the controller. |
Unit on defrost. |
Turn Unit On/Off switch Off and then On again. |
Detective high pressure or low pressure cutout switch. |
Replace defective switch. |
High condenser head pressure causing high pressure cutout. |
Check refrigeration system and correct fault. |
Defective compressor. |
Replace compressor. |
Controller shut unit down on Compressor Over Temperature. |
Let compressor cool and controller will reset automatically.
Check vapor injection valve and compressor temperature sensor. |
Compressor motor internal thermal overload protection open. |
If compressor contactor is energized, wait 60 minutes for protector
to cool and reset. |
Compressor does not operate - excessive amperage
draw or intermittent cycling on overload. |
Rotating scroll stuck. |
Replace compressor. |
Seized or frozen compressor bearings. |
Replace compressor. |
Improperly wired. |
Check/correct wiring against wiring diagram. |
Low line voltage. |
Check line voltage - determine location of voltage drop. |
Contacts in compressor contactor not closing completely. |
Check by operating manually. Repair or replace. |
Open circuit in compressor motor winding. |
Check motor stator connections. Check stator winding for continuity.
If open, replace compressor. |
Defective compressor motor internal thermal overload protector. |
Replace thermal overload protector or compressor. |
Refrigerant overcharge or high side restriction causing cycling
on high pressure cutout. |
Check for restricted filter drier, in-line filter or high side;
or refrigerant overcharge. |
Inefficient condenser operation causing cycling on high pressure
cutout. |
Check condenser airflow, condenser fan motor, fan blade, condenser
grille, condenser coil temperature sensor, water pressure switch (option),
water flow rate (option) and water-cooled condenser-receiver tank
(option). |
Compressor contactor burned out. |
Low line voltage. |
Increase line voltage to at least 90 percent of compressor
motor rating. |
Excessive line voltage. |
Reduce line voltage to at least 110 percent of compressor motor
rating. |
Short cycling. |
Eliminate cause of short cycling. |
Unit short cycles. |
Refrigerant overcharge causing cycling on high pressure cutout. |
Purge system. |
Inefficient condenser operation causing cycling on high pressure
cutout. |
Check condenser airflow, condenser fan motor, condenser fan
grille, condenser fan pressure switch, water pressure switch (option),
water flow rate (option) and water-cooled condenser-receiver tank
(option). |
Noisy compressor |
Loose mounting bolts. |
Tighten mounting bolts. |
Oil slugging or refrigerant flooding back. |
Perform controller pretrip test to check refrigerant charge.
Check expansion valve adjustment. Check compressor for compressor
oil. |
Scroll rotating backwards. |
Check phase correction system and check unit wiring. |
Defective compressor. |
Repair or replace compressor. |
Condenser fan motor does not operate. |
Unit in Heat or Defrost. |
Check indicator. If unit is in Heat or Defrost, unit operation
is normal (no remedy required). |
Unit in Cool with low condenser temperature. |
Check indicator condenser temperature and discharge pressure.
Condenser temperature may not require condenser fan operation (no
remedy required; condenser fan also pulses on and off on a 30 second
cycle to control condenser temperature). |
Water pressure switch closed (Water-cooled position) (Option). |
If unit is on water cooled condenser operation, unit operation
is normal. Otherwise water pressure switch must be Open for air-cooled
condenser operation. |
Defective water pressure switch (option). |
Replace defective switch. |
Loose line connection. |
Tighten connections. |
Open motor internal thermal overload protector. |
Check for seized bearings or defective thermal overload protector.
Repair or replace as necessary. |
Defective motor. |
Replace motor. |
Detective condenser fan contactor. |
Replace defective contactor |
No condenser fan output signal from controller. |
Diagnose and
replace condenser fan contactor or controller. |
Evaporator fan motor(s) does not operate. |
Unit on defrost. |
Check operating mode indicator LEDs. |
Loose line connection. |
Tighten connections. |
Open motor internal thermal overload protector. |
Check for seized bearings or defective thermal overload protector.
Repair or replace as necessary. |
Defective motor. |
Replace motor. |
No low or high speed evaporator fan output signal from controller
output module. |
Diagnose and replace output module or controller. |