Normal R-404A/R-452A System Operating Pressures (Scroll Compressor)

Container Temperature Operating Mode Ambient Temperature Suction Pressure Discharge Pressure
21 C (70 F) Cool 27 to 38 C, 80 to 100 F 410 to 670 kPa, 4.10 to 6.70 bar, 59 to 97 psig 2140 to 2650 kPa, 21.40 to 26.50 bar, 310 to 385 psig
16 to 27 C, 60 to 80 F 400 to 600 kPa, 4.00 to 6.00 bar, 58 to 87 psig 1725 to 2140 kPa, 17.25 to 21.40 bar, 250 to 310 psig
2 C (35 F) Cool 27 to 38 C, 80 to 100 F 385 to 425 kPa, 3.85 to 4.25 bar, 56 to 62 psig 1860 to 2380 kPa, 18.60 to 23.80 bar, 270 to 345 psig
16 to 27 C, 60 to 80 F 345 to 385 kPa, 3.45 to 3.85 bar, 50 to 56 psig 1450 to 1860 kPa, 14.50 to 18.60 bar, 210 to 270 psig**
-18 C (0 F) Cool 27 to 38 C, 80 to 100 F 214 to 228 kPa, 2.14 to 2.28 bar, 31 to 33 psig 1515 to 2035 kPa, 15.15 to 20.35 bar, 220 to 295 psig**
16 to 27 C, 60 to 80 F 200 to 215 kPa, 2.00 to 2.15 bar, 29 to 31 psig 1100 to 1515 kPa, 11.00 to 15.15 bar, 160 to 220 psig**
-29 C (-20 F) Cool 27 to 38 C, 80 to 100 F 145 to 160 kPa, 1.45 to 1.60 bar, 21 to 23 psig 1450 to 1965 kPa, 14.50 to 19.65 bar, 210 to 285 psig**
16 to 27 C, 60 to 80 F 130 to 145 kPa, 1.30 to 1.45 bar, 19 to 21 psig 1035 to 1450 kPa, 10.35 to 14.50 bar, 150 to 210 psig**

Suction and discharge pressures vary too greatly during Modulation Cool to use for evaluating or diagnosing refrigeration system performance. During the Modulation Cool mode, the suction pressure will vary between 100 and 450 kPa, 1.0 and 4.5 bar, 15 and 65 psig depending upon the percent (percent) cooling capacity.

**Discharge pressure is determined by condenser fan cycling.