Temperature Sensors
Thermistor type temperature sensors are used. Each sensor is connected to a cable and placed in a sealed stainless steel tube. The temperature signal from the sensor is transmitted through the cable. Temperature sensors include the following:
-
Supply Air
-
Return Air
-
Evaporator Coil
-
Condenser Coil
-
Compressor Discharge Temperature Sensor
-
Ambient Air
Sensor Installation
All sensors should be properly installed as follows:
-
Supply air sensors must be inserted to the bottom of the sensor tube and completely sealed by the grommet connection.
-
Return air sensor installs in a grommet between the evaporator fans.
-
Evaporator coil (defrost) sensor must be placed in the middle of the coil and 75 mm deep between the fins.
-
Condenser sensor must be placed on the upper left side of the condenser coil and 70 mm deep between the fins.
-
Ambient sensor must be placed on the bottom plate of the right forklift pocket.
-
Compressor discharge temperature sensor is attached to compressor head by adhesive. Refer to (Compressor Discharge Temperature Sensor).
Sensor Testing
The controller constantly monitors the left hand and right hand supply sensors, return sensor and defrost (evaporator coil) sensor to determine when to initiate a demand defrost. If a demand defrost is requested and defrost has occurred within the last 90 minutes, the controller initiates a probe test to check for a defective sensor.
During a Probe test, the VGA display shows [PROBE TEST PLEASE WAIT]. The controller operates the unit on high speed evaporator fans only for five minutes. All sensor temperatures are then compared.
-
Sensors with large temperature differences are discarded from the control algorithm. The controller then activates the appropriate Alarm codes to identify the defective sensor(s).
Sensor errors recorded during a probe test are cleared when the next Defrost is initiated or Unit On/Off switch is turned Off.
Resistance Values for Temperature Sensors
Sensors are permanently calibrated and can be checked using an ohmmeter. Ohm readings should agree with the data shown in the following sensor resistance tables.
Supply, Return, Evaporator Coil, Condenser Coil, and Ambient Air Sensors
°F | °C | Ohms | °F | °C | Ohms |
---|---|---|---|---|---|
-40 | -40 | 842,9 | 53.6 | 12 | 1046,8 |
-31 | -35 | 862,5 | 57.2 | 14 | 1054,6 |
-22 | -30 | 822,2 | 60.8 | 16 | 1062,4 |
-13 | -25 | 901,9 | 64.4 | 18 | 1070,2 |
-4 | -20 | 921,6 | 68 | 20 | 1077,9 |
5 | -15 | 941,2 | 71.6 | 22 | 1085,7 |
10.4 | -12 | 956,9 | 75.2 | 24 | 1093,5 |
14 | -10 | 960,9 | 78.8 | 26 | 1101,2 |
17.6 | -8 | 968,7 | 82.4 | 28 | 1109,2 |
21.2 | -6 | 976,5 | 86 | 30 | 1116,7 |
24.8 | -4 | 984,4 | 89.6 | 32 | 1124,5 |
28.4 | -2 | 992,2 | 93.2 | 34 | 1132,2 |
32 | 0 | 1000,0 | 96.8 | 36 | 1139,9 |
35.6 | 2 | 1007,8 | 100.4 | 38 | 1147,7 |
39.2 | 4 | 1015,6 | 104 | 40 | 1155,4 |
42.8 | 6 | 1023,4 | 107.6 | 42 | 1163,1 |
46.4 | 8 | 1031,2 | 111.2 | 44 | 1170,8 |
50 | 10 | 1039,0 | 113 | 45 | 1174,7 |
Compressor Discharge Sensors
°F | °C | Ohms | °F | °C | Ohms |
---|---|---|---|---|---|
-13 | -25 | 1,121,457 | 185 | 85 | 9,202 |
-4 | -20 | 834,716 | 194 | 90 | 7,869 |
5 | -15 | 627,284 | 203 | 95 | 6,768 |
14 | -10 | 475,743 | 212 | 100 | 5,848 |
23 | -5 | 363,986 | 221 | 105 | 5,091 |
32 | 0 | 280,824 | 230 | 110 | 4,446 |
41 | 5 | 218,406 | 239 | 115 | 3,870 |
50 | 10 | 171,166 | 248 | 120 | 3,354 |
59 | 15 | 135,140 | 257 | 125 | 2,924 |
68 | 20 | 107,440 | 266 | 130 | 2,580 |
77 | 25 | 86,000 | 275 | 135 | 2,279 |
86 | 30 | 69,282 | 284 | 140 | 2,021 |
95 | 35 | 56,158 | 293 | 145 | 1,797 |
104 | 40 | 45,812 | 302 | 150 | 1,591 |
113 | 45 | 37,582 | 311 | 155 | 1,393 |
122 | 50 | 30,986 | 320 | 160 | 1,247 |
131 | 55 | 25,680 | 329 | 165 | 1,118 |
140 | 60 | 21,397 | 338 | 170 | 1,015 |
149 | 65 | 17,914 | 347 | 175 | 920 |
158 | 70 | 15,067 | 356 | 180 | 834 |
167 | 75 | 12,728 | 365 | 185 | 748 |
176 | 80 | 10,793 | 374 | 190 | 679 |