Pressure Transducer (Sensor)
The sensors are located on the discharge or suction tubes near the compressor. The controller will display the actual discharge or suction system pressure. The display will show a reading and a bar graph.
To configure a sensor in the unit, refer to (Configuration Menu).
Removal
-
Disconnect the sensor from the control box.
-
Remove the sensor from the discharge or suction tube. The fitting on the line has a Schrader valve which will prevent refrigerant leakage.
Installation
-
Apply Locktite to fitting threads (Red 277).
-
Install sensor on fitting.
-
Route wire harness to control box and connect in accordance with wiring diagram.