Low Side Pump Down (R-134a Compressor Only)
Note Do NOT pump down a scroll compressor. Reclaim the
refrigerant when servicing the low side or high side of the R-23 refrigeration
system.
-
Install the gauge manifold on the compressor.
-
Set the controller setpoint temperature well below the return air temperature and operate the unit in the Cool mode until the temperature stabilizes (at least 5 minutes).
-
Close the receiver tank outlet valve. Allow the unit to operate until it reaches -15 to -40 kPa, -0.15 to -0.40 bar, 5 to 11 in. vacuum on the suction pressure gauge (3-5 minutes). Then shut the unit down manually with the On/Off switch.
-
To place the unit back in service, open the receiver tank outlet valve and turn the On/Off switch ON.