Gauge Manifold Connections
Before You Proceed
Note This procedure is only for units that contains
R134a refrigerant.
Note To minimize refrigerant loss, use sealing-type
quick connectors. These fittings restrict flow during evacuation.
Read the following before you proceed with a gauge manifold connection.
-
If a procedure requires the compressor to operate at a suction pressure below 5 inch vacuum (-17 kPa), place a jumper across the low pressure cutout switch to prevent compressor shutdown.
-
Use of the quick disconnect access valve during evacuation increases the time required to reach the correct micron level.