R-134a Final Charging Procedure for Partially Charged Units
-
Connect the gauge manifold to the suction line and discharge line service ports. Be sure to purge the air from the lines (see “Gauge Manifold Set Attachment and Purging” in the Refrigeration Maintenance chapter of this manual).
-
Back seat and crack the discharge service valve.
-
Connect a refrigerant tank to the gauge manifold service line.
-
Set the R-134a refrigerant tank for liquid charging. Open the refrigerant tank hand valve.
-
Start and operate the unit in the COOL mode.
-
Read the suction pressure and slowly open the gauge manifold low pressure hand valve to permit suction pressure to increase approximately 170 kPa, 1.7 bar, 25 psig. This will meter liquid refrigerant slowly into the low side.
-
Add R-134a refrigerant until the receiver tank balls float at the top of the sight glass.
-
Close the hand valve on the refrigerant tank.
-
Operate the unit on COOL for 10 minutes and recheck refrigerant charge.
-
Remove the gauge manifold set.
-
Cap all service ports and valve stems.