Liquid Line Solenoid Valve Replacement (R-134a System Only)
Removal
-
Close the liquid line service valve and pump down the low side to -35 kPa, -0.35 bar, 10 in. vacuum. Break the vacuum with nitrogen between 10 and 20 kPa, 0.10 and 0.20 bar, 1 and 3 psig.
-
Turn the unit On-Off switch OFF. Disconnect electrical connections to liquid line solenoid.
Note In most cases, only the coil requires replacement. No other repair is possible on the liquid line solenoid. -
Unsolder the liquid line connections from the valve.
-
Remove the valve from the unit.
Installation
-
Clean the tubes for soldering.
-
Place the new valve in position and solder the connections.
-
Release a small amount of refrigerant from the receiver tank to pressurize the liquid line. Check for leaks (see “Refrigerant Leak Test Procedure” in the Refrigeration Maintenance chapter of this manual).
-
If no leaks are found, recover the leak test gas (see “Refrigerant Recovery” in the Refrigeration Maintenance chapter of this manual).
-
Evacuate the low side (see “Evacuation and Cleanup of the Refrigeration System” in the Refrigeration Maintenance chapter of this manual).
-
Reconnect the electrical wires to the valve.
-
Open the liquid line service valve and place the unit in operation. Check the refrigerant charge and add refrigerant as required.