Clearing Alarm Codes

Most alarm codes can be cleared conventionally from the Alarm Menu using the CLEAR soft key. See the Operating Instructions chapter for procedures. The operator should contact a supervisor or a Thermo King dealer about clearing alarms using the Guarded Access Menu. Refer to ( Table of Alarm Codes) for alarm corrective action.

Note Document all alarm faults and report them to the service technician.

There are three levels of corrective action that can be taken when an alarm condition occurs.

OK to Run: An alarm condition exists but does not affect unit operation. Corrective action can occur at a later date.

Check As Specified: An alarm condition exists that could affect unit operation. Follow diections in the Corrective Action column on the following chart.

Take Immediate Action: An alarm condition exists that will damage the unit or load. Take immediate action to correct the problem.

Note The corrective actions listed in the Operating Instructions chapter and in Table of Alarm Codes are suggestions only. Always consult your company for final decisions.
Note Table of Alarm Codes shows all possible alarm codes for all possible applications. Not all codes will be applicable to each individual unit. Not all alarm codes are available with all microprocessor controllers or all revisions of software.

Table of Alarm Codes

COLOR CODE DEFINITIONS: OK TO RUN CHECK AS SPECIFIED TAKE IMMEDIATE ACTION
Num   Description Operator Action
00   No Alarms Exist No action required.
02   Check Evaporator Coil Sensor Manually monitor load temperature. Report alarm at end of day.
03   Check (Control) Return Air Sensor Manually monitor load temperature. Report alarm at end of day.
04   Check (Control) Discharge Air Sensor Manually monitor load temperature. Report alarm at end of day.
05   Check Ambient Temp Sensor Report alarm at end of day.
06   Check Coolant Temp Sensor Report alarm at end of day.
07   Check Engine RPM Sensor Report alarm at end of day.
(09)   High Evaporator Temperature Manually monitor load temperature. Report alarm at end of day.
(10)   High Discharge Pressure If unit is shut down repair immediately. Otherwise, report alarm at end of day.
11   Unit Controlling on Alternate Sensor Manually monitor load temperature. Report alarm at end of day.
12   Sensor or Digital Input Shutdown The unit is no longer able to operate and has been shut down. Repair immediately.
13   Sensor Calibration Check Manually monitor load temperature. Report alarm at end of day.
(17)   Engine Failed to Crank If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(18)   High Engine Coolant Temperature If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(19)   Low Engine Oil Pressure If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(20)   Engine Failed to Start If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(21)   Cooling Cycle Check Manually monitor load temperature. Report alarm at end of day.
(22)   Heating Cycle Check Manually monitor load temperature. Report alarm at end of day.
(23)   Cooling Cycle Fault The unit is no longer able to operate and has been shut down. Repair immediately.
(24)   Heating Cycle Fault The unit is no longer able to operate and has been shut down. Repair immediately.
25   Alternator/Battery Charger Check If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(26)   Check Refrigeration Capacity Manually monitor load temperature. Report alarm at end of day.
28   Pretrip Abort Report alarm at end of day.
31   Check Oil Pressure Switch If unit is shut down repair immediately. Otherwise, report alarm at end of day.
32   Refrigeration Capacity Low The unit is no longer able to operate and has been shut down. Repair immediately.
33   Check Engine RPM Report alarm at end of day.
35   Check Run Relay Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(36)   Electric Motor Failed to Run If unit is shut down repair immediately. Otherwise, report alarm at end of day.
37   Check Engine Coolant Level Check engine coolant level. Do not remove the cap if the engine is hot. Report alarm at end of day.
38   Electric Phase Reversed If unit is shut down repair immediately. Otherwise, report alarm at end of day.
39   Check Water Valve Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
40   Check High Speed Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
41   Check Engine Coolant Temperature If unit is shut down repair immediately. Otherwise, report alarm at end of day.
42   Unit Forced to Low Speed Report alarm at end of day.
43   Unit Forced to Low Speed Modulation Report alarm at end of day.
44   Check Fuel System Add fuel as necessary, otherwise report alarm at end of day.
45   Check Hot Gas or Hot Gas Bypass Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
46   Check Air Flow If unit is shut down repair immediately. Otherwise, report alarm at end of day.
48   Check Belts or Clutch If unit is shut down repair immediately. Otherwise, report alarm at end of day.
50   Reset Clock Report alarm at end of day.
52   Check Heat Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
54   Test Mode Timeout Service Test or Output Test timed out after 15 minutes. Report alarm at end of day.
56   Check Host Evap Fan Low Speed If unit is shut down repair immediately. Otherwise, report alarm at end of day.
57   Check Host Evap Fan High Speed If unit is shut down repair immediately. Otherwise, report alarm at end of day.
61   Low Battery Voltage If unit is shut down repair immediately. Otherwise, report alarm at end of day.
62   Ammeter Out of Calibration If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(63)   Engine Stopped If unit is shut down repair immediately. Otherwise, report alarm at end of day.
64   Pretrip Reminder Report alarm at end of day.
65   Abnormal Temperature Differential Report alarm at end of day.
66   Low Engine Oil Level Check engine oil level. If unit is shut down repair immediately. Otherwise, report alarm at end of day.
67   Check Liquid Line Solenoid Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
68   Internal Controller Fault Code Report alarm at end of day.
70   Hourmeter Failure Report alarm at end of day.
74   Controller Reset to Defaults Report alarm at end of day.
79   Internal Data Logger Overflow Report alarm at end of day.
84   Restart Null Report alarm at end of day.
85   Forced Unit Operation Report alarm at end of day.
86   Check Discharge Pressure Sensor Report alarm at end of day.
87   Check Suction Pressure Sensor Report alarm at end of day.
89   Check Electronic Throttling Valve Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
90   Electric Overload If unit is shut down repair immediately. Otherwise, report alarm at end of day.
91   Check Electric Ready Input If unit is shut down repair immediately. Otherwise, report alarm at end of day.
92   Sensor Grades Not Set Report alarm at end of day.
96   Low Fuel Level Check engine fuel level and add fuel as required.
98   Check Fuel Level Sensor Report alarm at end of day.
108   Door Open Time-out Close doors. Report alarm at end of day.
111   Unit Not Configured Correctly Report alarm at end of day.
113   Check Electric Heat Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
114   Multiple Alarms - Can Not Run If unit is shut down repair immediately. Otherwise, report alarm at end of day.
117   Auto Switch from Diesel to Electric Report alarm at end of day.
118   Auto Switch from Electric to Diesel Report alarm at end of day.
120   Check Alternator Excite Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
121   Check PWM/Liquid Injection Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
122   Check Diesel/Electric Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
127   Setpoint Not Entered Be sure setpoint is adjusted to required temperature.
128   Engine Run Time Maintenance Reminder #1 Report alarm at end of day.
129   Engine Run Time Maintenance Reminder #2 Report alarm at end of day.
130   Electric Run Time Maintenance Reminder #1 Report alarm at end of day.
131   Electric Run Time Maintenance Reminder #2 Report alarm at end of day.
132   Total Unit Run Time Maintenance Reminder #1 Report alarm at end of day.
133   Total Unit Run Time Maintenance Reminder #2 Report alarm at end of day.
134   Controller Power On Hours Report alarm at end of day.
141   Auto-Switch Diesel to Electric Disabled Report alarm at end of day.
143   Check Remote Zone Drain Hose Heater Output If unit is shut down repair immediately. Otherwise, report alarm at end of day.
144   Lost Expansion Module CAN Communication If unit is shut down repair immediately. Otherwise, report alarm at end of day.
145   Loss of Controller “On” 8XP Feedback Signal If unit is shut down repair immediately. Otherwise, report alarm at end of day.
146   Software Version Mismatch If unit is shut down repair immediately. Otherwise, report alarm at end of day.
148   Auto-Switch Electric to Diesel Disabled Report alarm at end of day.
150   Out of Range Low (HMI) Manually monitor load temperature. Report alarm at end of day.
151   Out of Range High (HMI) Manually monitor load temperature. Report alarm at end of day.
157   OptiSet File Mismatch Report alarm at end of day.
158   Primary Software Failed to Load Report alarm at end of day.
159   Check Battery Condition If unit is shut down repair immediately. Otherwise, report alarm at end of day.
160   Lost Radio Expansion Board (REB) CAN Communication If unit is shut down repair immediately. Otherwise, report alarm at end of day.
203   Check Display Return Air Sensor Manually monitor load temperature. Report alarm at end of day.
204   Check Display Discharge Air Sensor Manually monitor load temperature. Report alarm at end of day.
233   REB Transitioning From Conservative to Full Null Report alarm at end of day.
234   Check Relative Humidity Sensor Report alarm at end of day.
251   REB Mis-configured Report alarm at end of day.
252   Check Auto Fresh Air Exchange Report alarm at end of day.
508   Speed Request Communications Error Report alarm at end of day.
509   Engine Control Unit (ECU) Failed to Enable If unit is shut down repair immediately. Otherwise, report alarm at end of day.
510   Engine Control Unit (ECU) Run Signal Failed If unit is shut down repair immediately. Otherwise, report alarm at end of day.
511   Engine Wait to Start Time Delay Expired Report alarm at end of day.
517   Water in Fuel Report alarm at end of day.
518   Generator Ground Fault If unit is shut down repair immediately. Otherwise, report alarm at end of day.
519   Check Battery Charger Input Power If unit is shut down repair immediately. Otherwise, report alarm at end of day.
520   Check Battery Charger Output Power If unit is shut down repair immediately. Otherwise, report alarm at end of day.
521   Battery Charger External / Environmental Faults If unit is shut down repair immediately. Otherwise, report alarm at end of day.
522   Battery Temperature Sensor Alarm If unit is shut down repair immediately. Otherwise, report alarm at end of day.
523   Battery Charger Indicated Conditions If unit is shut down repair immediately. Otherwise, report alarm at end of day.
524   Generator Operational Limit, V out to Frequency Ratio If unit is shut down repair immediately. Otherwise, report alarm at end of day.
525   Generator Frequency Range Fault If unit is shut down repair immediately. Otherwise, report alarm at end of day.
526   Generator Operational Limit Output Current If unit is shut down repair immediately. Otherwise, report alarm at end of day.
528   Controller Not Receiving Messages From Battery Charger If unit is shut down repair immediately. Otherwise, report alarm at end of day.
529   Check Fuel Pump Circuit If unit is shut down repair immediately. Otherwise, report alarm at end of day.
538   Engine J1939 CAN Datalink Degraded (Electronic Engine Only) If unit is shut down repair immediately. Otherwise, report alarm at end of day.
539   Engine J1939 CAN Datalink Failed (Electronic Engine Only) If unit is shut down repair immediately. Otherwise, report alarm at end of day.
599   Engine Service Tool Connected Maintenance information only. Report alarm at end of the day.
600   Check Crankshaft Speed Sensor Report alarm at end of day.
601   Check Camshaft Speed Sensor Report alarm at end of day.
602   Check Intake Throttle Position Sensor Report alarm at end of day.
603   Check Exhaust Pressure Sensor Report alarm at end of day.
604   Check Coolant Temperature Sensor Report alarm at end of day.
605   Check Fresh Air Temperature Sensor Report alarm at end of day.
607   Check Fuel Temperature Sensor Report alarm at end of day.
608   Check Rail Pressure Sensor Report alarm at end of day.
609   Check Intake Pressure Sensor Report alarm at end of day.
610   Check Atmospheric Pressure Sensor Report alarm at end of day.
611   Check Glow Plug Circuit Report alarm at end of day.
612   Check Intake Throttle Circuit Report alarm at end of day.
613   Check Injector(s) Report alarm at end of day.
614   Check High Pressure Fuel Pump Report alarm at end of day.
615   Rail Pressure Fault If unit is shut down repair immediately. Otherwise, report alarm at end of day.
616   Engine Overspeed If unit is shut down repair immediately. Otherwise, report alarm at end of day.
617   Internal ECU Fault If unit is shut down repair immediately. Otherwise, report alarm at end of day.
618   Check EGR Report alarm at end of day.
619   ECU Main Relay Fault Report alarm at end of day.
623   TRU CAN Message Timeout Report alarm at end of day.
624   Check EGR Temperature Sensor Report alarm at end of day.
625   Check Intake Air Temperature Sensor Report alarm at end of day.
626   Check Exhaust Temperature Sensor Report alarm at end of day.
699   Unknown ECU Fault If unit is shut down repair immediately. Otherwise, report alarm at end of day.