Alarms List
Warning Alarms
Warnings are non-critical alarm conditions and do not affect the operation of the engine system, they serve to draw the operators attention to an undesirable condition.
Example:
1/2 |
Alarms |
|
Coolant Temp High |
||
Warning |
In the event of an alarm the LCD jumps to the alarms page, and scroll through all active alarms.
By default, warning alarms are self-resetting when the fault condition is removed.
Shutdown Alarms
Shutdown Alarms are latching and immediately stop the Generator. Once this has occurred, the module shuts the generator set down immediately to prevent further damage. To restart the generator the fault must be cleared and the alarm reset.
Alarm Codes
Level | Alarm Code | Alarms | DTC code | ECU current DTCs | Description |
---|---|---|---|---|---|
Shut Down | 101 | Crank Attempts Expired | Alarm if Engine did NOT achieve 800 rpm within 12 seconds. Becomes a Shutdown Alarm when number of restart attempts is greater than number of “Crank Restarts” set in Configuration Menu. | ||
Warning | 102 | Failed to Start | The generator had failed to start as it did not meet the required Crank Disconnect criteria during the configured number of Crank Attempts. | ||
Warning | 103 | Failed to Stop | Module detected that the generator is running when the DSE module has instructed it to stop. | ||
Shut Down | 105 | Low Oil Level | If low oil level for 60 seconds. | ||
Warning | 108 | Coolant Level Low | Low Coolant Level detected. - Initiates 20 min restart delay | ||
Shut Down | 109 | Water in Fuel | Water in the fuel had been detected. | ||
Warning | 302 | ECU amber | P1192 S=100 F=4 | Oil Press Switch | The circuit to the engine oil pressure sensor had become open |
The low oil pressure switch had activated after the Safety On Delay timer had expired. | |||||
Engine oil pressure had fallen below the Low Oil Pressure Shutdown Trip level after the Safety On Delay timer had expired. | |||||
Warning | 302 | ECU amber | P0219 S=190 F=0 | Engine Speed High - most severe | The engine speed had risen above the Run Away Trip level. |
The engine speed had risen above the Over Speed Alarm Trip level for the configured delay timer. | |||||
The engine speed had risen above the Over Speed Overshoot Trip level | |||||
Warning | 302 | ECU amber | P0118 S=110 F=3 | Coolant Temperature High voltage, or short | The coolant temperature sensor has become open circuit. |
The high engine coolant temperature switch had activated after the Safety On Delay timer had expired. | |||||
The engine coolant temperature had risen above the High Coolant Temperature Shutdown Trip level after the Safety On Delay timer had expired. | |||||
Shut Down | 116 | Calibration Fault | Calibration Fault | Controller internal calibration has failed. The unit must be sent back to DSE to be investigated and repaired. | |
Warning | 117 | PTI passed | |||
Warning | 118 | PTI activated | |||
Warning | 119 | 20 Minute Crank Lockout | |||
Shut Down | 120 | Pre Trip Test Fail | |||
Warning | 121 | Speed Override Mode Enabled | If Manual Speed Switching is Enabled and toggle button is inactive for 5 minutes, go back to Auto Mode | ||
Warning | 122 | Shift to High Speed | When the genset shifts from low to high speed (HS set at 1800rpm) | ||
Warning | 123 | Shift to Low Speed | When the genset shifts from high to low speed (LS set at 1500rpm) | ||
Shut Down | 301a | ECU Protect | The module received a protect fault condition from the engine ECU. Connect ECU Test Tool to read codes. | ||
Shut Down | 301b | ECU Red | The module received a red fault condition from the engine ECU. Connect ECU Test Tool to read codes. | ||
Warning | 302 | ECU Amber | The module received an amber fault condition from the engine ECU. Connect ECU Test Tool to read codes. | ||
Shut Down | 410 | Gen Over Voltage | The generator output voltage had risen above the Over Voltage Alarm Trip level for the configured delay timer. See “Alternator Diagnosis” | ||
Shut Down | 411 | Gen Below Voltage | The generator output voltage had fallen below the Under Voltage Alarm Trip level for the configured delay timer after the Safety On Delay timer had expired. See “Alternator Diagnosis” | ||
Shut Down | 422a | Gen Under Frequency | The generator output frequency had fallen below the Under Frequency Alarm Trip level for the configured delay timer after the Safety On Delay timer had expired. See “Alternator Diagnosis” | ||
Shut Down | 423a | Gen Over Frequency | The generator output frequency had risen above the Run Away Trip level. See “Alternator Diagnosis” | ||
Shut Down | 423b | Gen Over Frequency Overshoot | The generator output frequency had risen above the specified trip. See “Alternator Diagnosis” | ||
Shut Down | 423c | Gen Over Frequency | The generator output frequency had risen above the Over Frequency Alarm Trip level for the configured delay timer. See “Alternator Diagnosis” | ||
Shut Down | 800 | ECU Malfunction | The module received a malfunction fault condition from the engine ECU. Connect ECU Test Tool to read codes. | ||
Shut Down | 801 | ECU Data Fail | The module is configured for CAN operation but has not detected data being sent from the engine’s ECU. | ||
Shut Down | — | Generator Locked Out | The generator has cranked 3 times without success. Check the fuel level and the battery voltage. |