Vapor Injection Valve Replacement
Removal
-
Recover the refrigerant charge from the unit.
-
Turn the Unit On/Off switch Off. Disconnect electrical connections to valve coil.
-
Unsolder liquid line connections to the valve.
-
Remove the valve from the unit.
Installation
-
Clean the tubes for soldering.
-
Place the new valve in position and solder the liquid line connections.
-
Pressurize the refrigeration system and check for leaks (Refer to 制冷系统泄漏测试). Repair leak if required.
-
Recover the refrigerant used for the leak test if no leaks were found.
-
Evacuate the system (Refer to 制冷系统的排放和清洁).
-
Recharge the unit with R-404A/R-452A (Refer to 为设备注入制冷剂).
-
Recharge the unit with R-134a/R-513A (Refer to 为设备注入制冷剂).
-
Perform a controller pretrip test to verify system operation.