Initiating the Evaporator Manual Defrost Cycle
-
Press and release the Select key once, and the letters dEF will appear (flashing) on screen along with the present defrost condition OFF.
-
To activate manual defrost, press the Enter key and then the Up or Down key and the defrost condition will change to On.
-
Press the Select key twice to return to the Standard Display where the Defrost (dEF) symbol along with the DEFROST icons will appear when the defrost cycle begins.
Note In 380.xx software, the compartment temperature appears instead of the Defrost (dEF) symbol.Note The defrost termination switch must be closed.Note Press the Select key three times for multi-temperature or reverse cycle units. -
Press the Select key twice to return to the Standard Display (three times in bi-temperature units and in reverse cycle units), where the letters dEF and the DEFROST symbol will appear when the defrost cycle starts (the load compartment temperature must be lower than 0ºC).
Note The letters dEF will remain on screen for a while after returning to cool mode. -
A defrost cycle terminates automatically, in accordance with the [dtt] time set at the Parameters screen. See Section 3 for a description of the [dtt] parameter.
Note The letters dEF will remain on screen for a while after returning to cool mode.