Evaluation of the Qualification Test

T-1200R Spectrum S3+S3 - Multi-temperatures Tests

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C     +20°C +17/+22 °C +19 °C -2 /+1°C of setpoint
+20°C +17/+22 °C +20 °C -2 /+1°C of setpoint
+6°C +2/+8 °C +6 °C -2 /+1°C of setpoint
 
-30°C     +20°C +15/+21 °C +18 °C -2 /+1°C of setpoint
+20°C +15/+23 °C +17 °C -5 /+0°C of setpoint
+6°C +2/+8 °C +5 °C -3 /+2°C of setpoint

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C      

+6°C

+3/+8 °C

+6°C

- /+1°C of setpoint

-25°C

-27/-21 °C

-25°C

-1 /+2°C of setpoint

-25°C

-27/-20 °C

-24°C

0 /+3°C of setpoint

 
-30°C    

+6°C

+4/+7 °C

+6°C

-1/+2°C of setpoint

-25°C

-28/-24 °C

-26°C

-2 /+0°C of setpoint

-25°C

-29/-21 °C

-26°C

-2 /+1°C of setpoint

Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient   Setpoint   5 minutes rear door opening   10 minutes rear doors opening  
Zone 1 Zone 2 Air temperature peak (Z2) Recovery time after closing doors Air temperature peak (Z2) Recovery time after closing doors
+40°C           +20°C +6°C +33.9 °C 11 minutes +37.3 °C 22 minutes
+20°C -25°C +29.7 °C 87 minutes  -  -
+6°C +20°C +36 °C 5 minutes +37.7 °C 6 minutes
-25°C +6°C +32.9 °C 17 minutes +35.8 °C 18 minutes
-25°C +20°C +35.3 °C 4 minutes +38.4 °C 4 minutes
             
-30°C       +20°C +6°C -24.4 °C 16 minutes -27.3 °C 23 minutes
+20°C +20°C -20.9 °C 25 minutes -25.8 °C 39 minutes
+6°C +20°C -21.1 °C 19 minutes -26.9 °C 27 minutes
+6°C +6°C -23.6 °C 9 minutes -26.8 °C 14 minutes

Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient     Zone 1     Zone 2  
Setpoint Time to move out of the range Rules to apply Setpoint Time to move out of the range Rules to apply
+40°C       +6°C 10minutes Above +8°C or max 2hrs. +20°C 2 hours Above +25°C or max 2hrs.
+6°C 8 minutes Above +8°C or max 2hrs. -25°C 15 minutes Above -20°C or max 2hrs.
-25°C 11 minutes Above -20°C or max 2hrs. +20°C 2 hours Above +25°C or max 2hrs.
             
-30°C     -25°C N.A. Non Applicable +6°C 7 minutes Below +2°C or max 2hrs.
-25°C N.A. Non Applicable +20°C 4 minutes Below +15°C or max 2hrs.
+20°C 20 minutes Below +15°C or max 2hrs. +6°C 35 minutes Below +2°C or max 2hrs.

T-1200R Spectrum S3+S3 - Single-temperature Tests

Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+20°C

+16/+21 °C

+19 °C

-2 / 0°C of setpoint

+6°C

+2/+8 °C

+5 °C

-2 / 0°C of setpoint

-25°C

-27/-20°C

-24 °C

0 /+2°C of setpoint

 
-30°C    

+20°C

+16/+22 °C

+19 °C

-3 / 0°C of setpoint

+6°C

+2/+8 °C

+5 °C

-2 / 0°C of setpoint

-25°C

-31/-25 °C

-28 °C

-4 /-1°C of setpoint

Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint 5 minutes rear door opening 10 minutes rear doors opening
Air temperature peak (Z2) Recovery time after closing doors Air temperature peak (Z2) Recovery time after closing doors
+40°C  +20°C +36.5 °C 6 minutes +38 °C 8 minutes
+6°C +34.2 °C 30 minutes +36.5 °C 41 minutes
-25°C +31.7 °C 117 minutes  -  -
           
-30°C   +20°C -24.5 °C 34 minutes -26 °C 55 minutes
+6°C -26 °C 24 minutes -28.2 °C 34 minutes

Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient

Setpoint

Time to move out of the range

Rules to apply

+40°C 

+6°C

20 minutes

Above +8°C or max 2hrs.

-25°C

15 minutes

Above -20°C or max 2hrs.

 

-30°C

+20°C

11 minutes

Below +15°C or max 2hrs.

+6°C

20 minutes

Below +2°C or max 2hrs.

T-1000R Spectrum S3+S3 - Multi-temperatures tests

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+20°C

+17/+22 °C

+20 °C

-2 / 0°C of setpoint

 
-30°C

+20°C

+16/+21 °C

+18 °C

-3 / 0°C of setpoint

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+6°C

+3/+8 °C

+6 °C

- / +1°C of setpoint

 
-30°C

+6°C

+4/+7 °C

+5 °C

-2 / 0°C of setpoint

Door Opening - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient   Setpoint   5 minutes rear door opening   10 minutes rear doors opening  
Zone 1 Zone 2 Air temperature peak (Z2) Recovery time after closing doors Air temperature peak (Z2) Recovery time after closing doors
+40°C          

+20°C

+6°C

+34.2 °C

19 minutes

+36.7 °C

24 minutes

+6°C

+20°C

+36.7 °C

4 minutes

+37.9 °C

5 minutes

             
-30°C      

+6°C

+20°C

-20.7 °C

34 minutes

-25.5 °C

59 minutes

+20°C

+6°C

-24.4 °C

15 minutes

-27.9 °C

24 minutes

Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient     Zone 1     Zone 2  
Setpoint Time to move out of the range Rules to apply Setpoint Time to move out of the range Rules to apply
+40°C      

+6°C

8 minutes

Above +8°C or max 2hrs.

+20°C

2 hours

Above +25°C or max 2hrs.

+20°C

2 hours

Above +25°C or max 2hrs.

+6°C

10 minutes

Above +8°C or max 2hrs.

             
-30°C    

+6°C

86 minutes

Below +2°C or max 2hrs.

+20°C

36 minutes

Below +15°C or max 2hrs.

+20°C

35 minutes

Below +15°C or max 2hrs.

+6°C

65 minutes

Below +2°C or max 2hrs.

T-1000R Spectrum S3+S3 - Single-temperature Tests

Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+20°C

+16/+21 °C

+19 °C

-2 / 0°C of setpoint

+6°C

+2/+8 °C

+5 °C

-2 / 0°C of setpoint

 
-30°C

+20°C

+16/+22 °C

+19 °C

-3 / 0°C of setpoint

+6°C

+2/+8 °C

+5°C

-2 / 0°C of setpoint

Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient   Setpoint   5 minutes rear door opening   10 minutes rear doors opening  
Air temperature peak (Z2) Recovery time after closing doors Air temperature peak (Z2) Recovery time after closing doors
+40°C          

+20°C

+36.5 °C

6 minutes

+38 °C

8 minutes

+6°C

+34.2 °C

30 minutes

+36.5 °C

41 minutes

             
-30°C      

+20°C

-24.5 °C

34 minutes

-26 °C

55 minutes

+6°C

-26 °C

24 minutes

-28.2 °C

34 minutes

Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint Time to move out of the range Rules to apply
+40°C +6°C 20 minutes Above +8°C or max 2hrs.
       
-30°C   +20°C 11 minutes Below +15°C or max 2hrs.
+6°C 20 minutes Below +2°C or max 2hrs.

UT-1200 Spectrum S3+S3 - Multi-Temperatures Tests

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+20°C

+17/+22 °C

+20 °C

- / +1°C of setpoint

 
-30°C

+20°C

+15/+22 °C

+18°C

-3 / 0°C of setpoint

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+5°C

+2/+8 °C

+6 °C

-1 / +2°C of setpoint

 
-30°C

+5°C

+3/+7 °C

+4°C

-4 / 0°C of setpoint

Door opening 5 minutes - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient     Zone 1 (side door)  Zone 2 (rear doors)
Setpoint Air temperature peak Recovery time after closing doors Setpoint Air temperature peak Recovery time after closing doors
+40°C      

+5°C

+31.8°C

9 minutes

+20°C

+30.9°C

4 minutes

+20°C

+35.6°C

4 minutes

+5°C

+25.7°C

20 minutes

             
-30°C    

+5°C

-27.5°C

18 minutes

+20°C

-13.8°C

29 minutes

+20°C

-25.3°C

25 minutes

+5°C

-17.3°C

37 minutes

Door opening 10 minutes - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient    Zone 1 (side door)  Zone 2 (rear doors)
Setpoint Air temperature peak Recovery time after closing doors Setpoint Air temperature peak Recovery time after closing doors
+40°C      

+5°C

+37.8°C

13 minutes

+20°C

+35.3°C

8 minutes

+20°C

+38.5°C

6 minutes

+5°C

+34°C

25 minutes

             
-30°C    

+5°C

-29.6°C

35 minutes

+20°C

-20.1°C

55 minutes

+20°C

-29.8°C

45 minutes

+5°C

-25°C

55 minutes

Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient     Zone 1     Zone 2  
Setpoint Time to move out of the range Rules to apply Setpoint Time to move out of the range Rules to apply
+40°C      

+5°C

18 minutes

Above +8°C or max 2hrs.

+20°C

2 hours

Above +25°C or max 2hrs.

+20°C

102 minutes

Above +25°C or max 2hrs.

+5°C

15 minutes

Above +8°C or max 2hrs.

             
-30°C    

+5°C

13 minutes

Below +2°C or max 2hrs.

+20°C

15 minutes

Below +15°C or max 2hrs.

+20°C

15 minutes

Below +15°C or max 2hrs.

+5°C

7 minutes

Below +2°C or max 2hrs.

UT-1200 Spectrum S3+S3 - Single-temperature Tests

Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+20°C

+17/+23 °C

+20 °C

-1 / 0°C of setpoint

+5°C

+2/+7 °C

+5°C

- / +1°C of setpoint

 
-30°C

+20°C

+15/+21 °C

+19 °C

-1°C of setpoint

+5°C

+2/+6 °C

+4°C

-3 / 0°C of setpoint

Door open - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint 5 minutes rear door opening 10 minutes rear doors opening
Air temperature peak Recovery time after closing doors Air temperature peak Recovery time after closing doors
+40°C 

+20°C

+30.4 °C

3 minutes

+35.7 °C

7 minutes

+5°C

+25.9 °C

17 minutes

+33.2 °C

25 minutes

           
-30°C  

+20°C

-9.4 °C

16 minutes

-21.9 °C

46 minutes

+5°C

-15.3 °C

16 minutes

-25.6 °C

28 minutes

Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and wall stowed

Ambient Setpoint Time to move out of the range Rules to apply
+40°C

+5°C

19 minutes

Above +8°C or max 2hrs.

 

+20°C

8 minutes

Above -20°C or max 2hrs.

       
-30°C  

+20°C

16 minutes

Below +15°C or max 2hrs.

+5°C

8 minutes

Below +2°C or max 2hrs.

UT-R Spectrum S3+S3 - Multi-Temperatures Tests

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+5 °C

+2.6 °C / +6.9 °C

+ 4.9 °C

-1.2 / +1 °C of setpoint

+20 °C

+17.5 °C / +20.9 °C

+ 20 °C

-1.5 / +0.3 °C of setpoint

 
-30°C

+5 °C

+3.6 °C / +6 °C

+5 °C

-0.8 / +0.6 °C of setpoint

+21 °C

+17.1 °C / +21.6 °C

+19.3 °C

-3.2 / +0.2 °C of setpoint

Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40°C    

+20 °C

+17.6 °C / +22.9 °C

+20.6 °C

-0.6 / +1.7 °C of setpoint

+5 °C

+2.7 °C / +6.2 °C

+5.2 °C

-0.6 / +1 °C of setpoint

 
-30°C

+21 °C

+16.9 °C / +22.7 °C

+19.4 °C

-3 / +0.5 °C of setpoint

+5 °C

+4.2 °C / +6 °C

+5 °C

-0.2 / +0.3 °C of setpoint

Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length.

Ambient   Setpoint   7minutes rear door opening  
Zone 1 Zone 2 Air temperature peak (Z2) Recovery time after closing doors
+40°C          

+20 °C

+6 °C

+25.5 °C

23 minutes

             
-30°C      

+5 °C

+21 °C

-13.9 °C

28 minutes

+21 °C

+5 °C

-18.6 °C

16 minutes

Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length

Ambient     Zone 1     Zone 2  
Setpoint Time to move out of the range Rules to apply Setpoint Time to move out of the range Rules to apply
+40°C      

+20 °C

> 2 hours

Above +25 °C or max 2hrs.

+6 °C

8.5 minutes

Above +8°C or max 2 hrs.

             
-30°C    

+21 °C

> 2 hours

Above +25°C or max 2hrs.

+5 °C

16 minutes

Below +2°C or max 2 hrs.

UT-R Spectrum S3+S3 – Single Temperature tests

Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint  Min/Max sensor temperature Average temperature Average temperature deviation
+40 °C    

+20 °C

+16.8 °C / +20.3 °C

+19.1 °C

-1.3 / +0 °C of setpoint

+5 °C

+2.4 °C / +6.8 °C

+5.1 °C

-0.5 / +0.5 °C of setpoint

-23 °C

-27.2 °C / -23.5 °C

-25.5 °C

-2.5 °C of setpoint

 
+30 °C

-29 °C

-31.8 °C / +27.7 °C

-29.8 °C

-1.2 / -0.3 °C of setpoint

 
-30 °C

+20 °C

+17.1 °C / +21.8 °C

+19.7 °C

-1.3/ +0.4 °C of setpoint

+5 °C

+3.4 °C / +6.6 °C

+4.7 °C

-1.0/ +0.4 °C of setpoint

-24 °C

-26.4 °C / -22.6 °C

-24.7 °C

-1.6/ +0.2 °C of setpoint

-27°C

-30.3 °C / -28.7 °C

-29.6 °C

-3.3 / -1.7 °C of setpoint

Door openings - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed

Ambient Setpoint 7 minutes rear door opening
Air temperature peak Recovery time after closing doors
+40 °C 

+5 °C

+24.2 °C

14 minutes

–23 °C

+12.9 °C

> 60 minutes

           
-30 °C  

+20 °C

-14.2 °C

18 minutes

+6 °C

-18.2 °C

15.5 minutes

Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and wall stowed

Ambient Setpoint Time to move out of the range Rules to apply
+40 °C

+5 °C

8.5 minutes

Above +8 °C or max 2hrs.

 

–23 °C

8.5 minutes

Above -20 °C or max 2hrs.

       
-30 °C  

+20 °C

33.5 minutes

Below +15 °C or max 2hrs.

+5 °C

7 minutes

Below +2 °C or max 2hrs.