Equipment Specifications

Truck body with Thermo King T-1000R Spectrum or T-1200R Spectrum unit

  • A 2 zones multi-temperatures truck body ATP IR standards with internal dimensions (L x W x H) of 9.12m x 2.47m x 2.54m resulting with an internal surface of 103.73 m2. Owing to the many configurations the bodies' sizes are to be calculated in cubic metres therefore it results with a body with maximum total internal volume of 57 m3. An internal volume that is smaller is permissible as long as the internal surface is not smaller by more than 20%.

  • A K factor of 0.40 W/m2.K. A better K factor is also permissible.

  • Body white in colour. A maximum 20% of the external surface decal coverage is recommended.

  • Body with double rear doors with door switches. A door arrangement that is better than this is also permissible. Unit is to be configured to force ZONE NULL when opening the doors. Thermal curtains are recommended.

  • A transversal movable dividing wall with a K factor as required and laid out in ATP (see table 1 in section “Detail specifications”). A K factor that is better than those from table 1 is also permissible.

  • Thermo King S3 remote evaporators installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode. ZONE PRIORITY function must be DISABLED.

  • A specific configuration file for pharmaceutical applications used for tighter temperature management.

  • A temperature datalogger which complies with EN12830 standard with at least one sensor in each zone. Thermo King DAS or TouchPrint Datalogger are recommended.

Truck with T-1000R/1200R Spectrum S3+S3

Truck body with Thermo King UT-1200 Spectrum unit

  • A 2 zones multi-temperatures truck body ATP IN standards with internal dimensions (L x W x H) of 8.93m x 2.47m x 2.44m resulting with an internal surface of 99.71 m2. Owing to the many configurations the bodies' sizes are to be calculated in cubic meters therefore it results with a body with maximum total internal volume of 54 m3. An internal volume that is smaller is permissible if the internal surface is not smaller by more than 20%.

  • A K factor of 0.70 W/m2.K. A better K factor is also permissible.

  • Body white in colour. A maximum 20% of the external surface decal coverage is recommended.

  • Body with double rear doors and single side door with door switches. A door arrangement that is better than this is also permissible. Unit is to be configured to force ZONE NULL when opening the doors. Thermal curtains are recommended.

  • A transversal movable dividing wall with a K factor as required and laid out in ATP (see table 1 in section “Detail specifications”). A K factor that is better than those from table 1 is also permissible.

  • Thermo King S3 remote evaporators installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode. ZONE PRIORITY function must be DISABLED.

  • A specific configuration file for pharmaceutical applications used for tighter temperature management.

  • A temperature datalogger which complies with EN12830 standard with at least one sensor in each zone. Thermo King DAS or TouchPrint Datalogger are recommended.

Truck with UT-1200 Spectrum S3+S3

Truck body with Thermo King UT-R Spectrum S3+S3 unit

  • 2 zone multi-temperatures truck body ATP IR standards with internal dimensions (L x W x H) of 7.50m x 2.59m x 2.81m resulting with an internal surface of 95.56 m2. Owing to the many configurations the bodies’ sizes are to be calculated in cubic meters therefore it results with a body with maximum total internal volume of 46.96 m3. An internal volume that is smaller is permissible if the internal surface is not smaller by more than 20%.

  • A K factor of 0.40 W/m².K. A better K factor is also permissible.

  • Body white in colour. A maximum 20% of the external surface decal coverage is recommended.

  • Body with double rear doors with door switches. A door arrangement that is better than this is also permissible. Unit is to be configured to force ZONE NULL when opening the doors. Thermal curtains are recommended.

  • A transversal movable dividing wall with a K factor as required and laid out in ATP (see table in section “Detail specifications”). A K factor that is better than those from table 1 is also permissible.

  • Thermo King S3 remote evaporators installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode. ZONE PRIORITY function must be DISABLED.

  • A specific configuration file for pharmaceutical applications used for tighter temperature management.

  • A temperature datalogger which complies with EN12830 standard with at least one sensor in each zone. Thermo King DAS, TouchPrint Datalogger or TouchLog are recommended.

Truck with UT-R Spectrum S3+S3

Temperature Range Table

Truck body with Thermo King T-1200R Spectrum unit

Temperature Range Extreme Ambient Temperature Recommended Setpoint Max Average Deviation from Setpoint
Temperature below ‐20°C +40°C / -30°C -25°C +5/-6°C of setpoint
Temperature between 2°C and 8°C +40°C / -30°C +6°C +2/-4°C of setpoint
Temperature between 15°C and 25°C +40°C / -30°C +20°C +3/-5 °C of setpoint

Truck body with Thermo King T-1000R Spectrum unit

Temperature Range Extreme Ambient Temperature Recommended Setpoint Max Average Deviation from Setpoint
Temperature between 2°C and 8°C +40°C / -30°C +6°C +2/-3°C of setpoint
Temperature between 15°C and 25°C +40°C / -30°C +20°C +2/-4°C of setpoint

Truck body with Thermo King UT-1200 Spectrum unit

Temperature Range Extreme Ambient Temperature Recommended Setpoint Max Average Deviation from Setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+5°C

+/-3°C of setpoint

Temperature between 15°C and 25°C

+40°C / -30°C

+20°C

+2/-3°C of setpoint

Truck body with Thermo King UT-R Spectrum unit

Temperature Range Extreme Ambient Temperature Recommended Setpoint Max Average Deviation from Setpoint

Temperature above -27°C

+30°C / -30°C

-29 °C

+/-3°C of setpoint

Temperature below -20°C

+40°C / -30°C

-24 °C

+4/-6°C of setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+5°C

+/- 3°C of setpoint

Temperature between 15°C and 25 °C

+40°C / -30°C

+20 °C

+/- 5°C of setpoint

Note To ensure total flexibility the qualification is to be performed at all stated ranges from above.