Load Space Consideration
-
The load space should be kept always clean at all times and only cleaning agents that will not affect the products should be used.
-
A compartment moveable dividing wall is used in multi-temperatures applications to separate the compartments to allow them to operate at different temperatures. This dividing wall must not be positioned any less than 1300mm from the air outlet of the remote zone evaporator.
-
A minimum of 100 mm clearance must be provided between the top of the load and the air intake of the zone remote evaporator.
-
An air gap between the load and the walls should be always maintained :
-
If the dividing wall is positioned tightly against the load, satisfactory air circulation and temperature management will not be achieved.
-
If the load is positioned tightly against the body internal walls, satisfactory air circulation and temperature management will not be achieved.
-
-
If the unit is to be used as a single-temperature mode, the dividing wall should be stowed in such a way that it does not interrupt the airflow from each remote evaporator.