Configuration Menu
The Configuration Menu is used to configure the following controller functions (also see the flowcharts on the following pages):
-
ENGINE TYPE - Yanmar or PCM
-
HM1 (Hour Meter 1) Threshold – The default setting is 0. When this is set to anything other than 0, it sets the threshold that generates the message “113. HOUR METER 1 HAS EXCEEDED THRESHOLD”.
-
HM2 (Hour Meter 2) Threshold – The default setting is 0. When this is set to anything other than 0, it sets the threshold that generates the message “114. HOUR METER 2 HAS EXCEEDED THRESHOLD”.
-
ENG (Engine) Off Hours – The default setting is 0. When this is set to anything other than 0, it sets the threshold that generates the alarm “110. ENGINE STOPPED DUE TO USER SETUP”.
-
Factory Reset – The default setting is OFF. When this is set to ON, the controller will reset all run timers to 0 when the unit is turned Off and then back On.
-
GENERATOR - generator type (M.ALTE or STAMFRD)
-
GENSET - Clip-ON, Side or centre
-
OUTPUT VOLTAGE - The default setting is 460. The other selection is 230, which is used is the alternator is configured for an output voltage of 230 Vac.
-
FUEL LEVEL - The default setting is 0. Possible settings are 1 to 400 gallons. This sets the threshold that generates the alarm “115. FUEL LEVEL LOW”.
-
CRANK RESTARTS - The default setting is 3. Possible settings are 0 to 15, and 0 equals infinite. This sets the number of restart attempts that are allowed.
-
COMPOSIT - Yes or No (Telematics)
-
RMM MASTER - Yes or No
-
FUEL PUMP TIME - Fuel pump enabled delay (0 = disabled / always on).
-
Place the On/Off switch in the “ON” position.
-
Press the ENTER key or the ESCAPE key to enter the Main Menu, if necessary.
-
Press the UP or DOWN key to scroll up or down through the Main Menu to the Configuration Menu.
-
Press the ENTER key to enter the Configuration Menu.
-
See “Setting Hour Meter Thresholds and Resetting Hour Meters” for an example of how change a setting.