Manual Pretrip Inspection (Before Starting the Unit)
Pretrip inspections are an important part of a preventative maintenance program designed to minimize operating problems and breakdowns. Perform this pretrip inspection before every trip involving refrigerated cargo.
- Note
-
Refer to (Pre-Loading Inspection) also before commencing your journey.
-
Pretrip inspections are not intended to take the place of regular maintenance inspections.
- Note
-
Refer to (Loading and Enroute Inspections) also before commencing your journey.
-
Pretrip inspections are not intended to take the place of regular maintenance inspections.
Fuel: Verify the diesel fuel supply is adequate to guarantee engine operation to the next check point. Allow for maximum fuel consumption of 3.8 Litres (one gallon)one gallon per hour of engine operation.
Engine Oil: Check the engine oil level. It should be at the Full mark when the dipstick is threaded all the way into the oil pan. Do not overfill.
Engine Coolant: The engine coolant must have antifreeze protection to -34 C (-30 F)-30 F (-34 C). Add coolant if Alarm Code 37 is active. Check and add coolant to the expansion tank.
Engine Coolant: The engine coolant must have antifreeze protection to -34 C (-30 F). Add coolant if Alarm Code 37 is active. Check and add coolant to the overflow tank.
Battery: Verify the battery terminals are tight and free of corrosion.
This will cause the battery to become discharged over time.
Apart from the obvious inconvenience of having to charge the battery, it is also liable to damage battery cell material and cause the life of the battery to be shorter than acceptable.
Therefore, to ensure the battery remains in optimum condition during periods when the unit is not being used, Thermo King strongly recommends to switch on the unit at least once each week and run for 30 minutes or longer to keep the battery safe.
If the EnergyONE battery is drained after a long idle period, it will need to be recharged using an automatic programmable battery charger (Thermo King does not recommend the use of manual battery chargers on dry cell batteries).
Failure to do so may result in warranty for the battery being rejected.
Alternatively, Thermo King offer a solar panel option from aftermarket which would negate the requirement to switch off the microprocessor switch during long unit idle periods. For more information, please contact your local Thermo King dealership.
Compressor:
Belts: Verify belts are in good condition and adjusted to the proper tension. For more information about belt tension, see the Specifications chapter.
Electrical: Check the electrical connections to verify they are securely fastened. Wires and terminals should be free of corrosion, cracks, and moisture.
Structural: Visually inspect the unit for leaks, loose or broken parts, and other damage.
Coils: Verify condenser and evaporator coils are clean and free of debris.
-
Washing with clean water should be sufficient.
-
The use of cleaning agents or detergents is strongly discouraged due to the possibility of degradation of the construction.
-
If using a power washer, the nozzle pressure should not exceed 600 psi (41 bar). For the best results, spray the coil perpendicular to the face of the coil. The spray nozzle should be kept between 1 inch and 3 inches (25 to 75 millimeters) from the coil surface.
-
If necessary to use a chemical cleaner or detergent, use a cleaner that does not contain any hydrofluoric acids and is between 7 and 8 on the pH scale. Verify dilution instructions provided by the detergent supplier are followed. In case of doubt about the compatibility of the detergent with the type of materials listed above, always ask the supplier a written confirmation of the compatibility.
-
Should a chemical cleaner be required, it is MANDATORY that all components are thoroughly rinsed with water even if the instructions of the cleaner specify that it is a “no rinse” cleaner.
Cargo Box: Check the interior and exterior of the cargo box for damage. Any damage to the walls or insulation must be repaired.
Cargo Doors: Verify the cargo doors and weather seals are in good condition. The doors should latch securely and the weather seals should fit tightly.
Damper Door: The damper door in the evaporator air outlet must move freely with no sticking or binding.
Defrost Drains: Check the defrost drain hoses to verify they are open.
Remote Evaporators: (SLXi SPECTRUM and SLXi SPECTRUM Whisper™ Pro)(T-800 SPECTRUM, T-1000 SPECTRUM and T-1200 SPECTRUM)(UT-1200 SPECTRUM)(UT-R SPECTRUM)
-
Visually inspect Evaporator(s) for damaged, loose, or broken parts.
-
Check also for refrigerant leaks.
-
Check Defrost initiation and termination (including defrost timer) by activating/initiating a manual defrost.
TracKing Module:
-
Check that the module is turned on and communicating.
-
For Whisper™ Pro Enabled TracKing, it is recommended to check at some stage throughout your journey if the SR-3 unit automatically switches to “High Speed Lock Out” in an area designated for this - i.e., PIEK assigned Zone.
Note For further best practices, please visit www.europe.thermoking.com/best-practices. -
For Whisper™ Pro Enabled TracKing, it is recommended to check at some stage throughout your journey if the TSR-3 unit automatically switches to “High Speed Lock Out” in an area designated for this - i.e., PIEK assigned Zone.
Note For further best practices, please visit www.europe.thermoking.com/best-practices.