Additional Validations and Variations
Addition of T-1200R
The T-1200R on a body type truck with a 0.4W/m2 K insulation or better is approved in parallel because it is of the same refrigeration specification as the T-1200R Intermodal. The T-1200R should not be used on a body volume that is less than 52m3 and not more than 58 m3; this would require a different specification unit.
Additional Body Sizes
Smaller body sizes appropriate to the unit design are also included because the performance will be improved as body size reduces.
-
The T-1000R should not be used on a body volume that is less than 43 m3; this would require a different specification unit.
-
The UT-1200 (with 2 S3 evaporators ) should not be used on a body volume that is less than 41 m3, this would require a different specification unit.
-
The T-800R should not be used on a body volume that is less than 32 m3; this would require a different specification unit.
Addition of a Side Door
Based on the document: PharmaSolutions- Variation GDP-DQ-SP-ST with additional side door_Rev01ep05052020, approved by Baggerman Farma Consult on 11/06/2020 the addition of the side door for SP-ST configurations was approved.