Low Pressure Cutout Switch Replacement
Removal
-
Recover the refrigerant charge from the unit (see “Refrigerant Recovery” in this chapter).
-
Disconnect the leads from the wire harness.
-
Unsolder the low pressure cutout switch from the unit.
Installation
-
Clean the tube for soldering.
-
Place the new switch in position and solder the suction line connection.
-
Pressurize the refrigeration system and check for leaks (see “Refrigerant Leak Test Procedure” in this chapter).
-
Evacuate the system (see “Evacuation and Cleanup of the Refrigeration System” in this chapter).
-
Recharge the unit (see “Refrigerant Charge” in this chapter).
-
Reconnect the electrical wires to the switch.