Alarm Codes, Descriptions and Corrective Actions
-
Shutdown Alarm (Level 1 Alarm): Alarm light on display flashes and unit stops. Correct alarm condition and acknowledge alarm before restarting.
-
Check Alarm (Level 2 Alarm): Alarm light on display flashes until alarm is acknowledged.
-
Event Log (Level 3 Alarm): Alarm is recorded in datalogger only (inspect event log).
Model CRR DF - Alarm Codes, Descriptions and Corrective Actions
Code | Description | Corrective Action |
00 | Supply Air
Sensor Open Circuit (Check Alarm)
|
|
01 | Supply Air Sensor Short Circuit
(Check Alarm)
|
|
02 | Return Air Sensor Open Circuit (Check Alarm)
|
|
03 | Return Air Sensor Short Circuit (Check Alarm)
|
|
04 | Evaporator Coil Sensor Open Circuit (Check Alarm)
|
|
05 | Evaporator Coil Sensor Short Circuit (Check Alarm)
|
|
06* | R-134 Compressor Current Too High (Check Alarm)
|
|
07* | R-134 Compressor Current Too Low (Check Alarm)
|
|
*If both alarms 06 and 07 are activated, the alarms are caused by a large difference in measured amps. Start “Manual Function Test” and start the R-134a compressor and condenser fan. Check the compressor amps measurement. If necessary, check the resistance of the compressor motor windings. | ||
10* | Heater Current Too High (Check Alarm)
|
|
11* | Heater Current Too Low (Check Alarm)
|
|
*If both alarms 10 and 11 are activated, the alarms are caused by a large difference in measured amps. Start “Manual Function Test” and energize the heaters. Check the heater amps measurement. If necessary, isolate and check the resistance of each individual heater element. | ||
14* | Evaporator Fan Low Speed Current Too High (Check Alarm)
|
|
15* | Evaporator Fan Low Speed Current Too Low (Check Alarm)
|
|
*If both alarms 14 and 15 are activated, the alarms are caused by a large difference in measured amps. Start “Manual Function Test” and start the evaporator fans. Check the evaporator fan amps measurement. If necessary, check the resistance in the motors between L1, L2 and L3, and L1 and L3. Resistance readings should be equal (approximately 30 Ohms, total of 3 motors). | ||
16* | Condenser Fan Current Too High (Check Alarm)
|
|
17* | Condenser Fan Current Too Low (Check Alarm)
|
|
18 |
|
|
*If both alarms 16 and 17 are activated, the alarms are caused by a large difference in measured amps. Start “Manual Function Test” and start the condenser fan. Check the condenser fan amps measurement. If necessary, check the resistance in the motor between L1 and L2, L2 and L3, and L1 and L3. Resistance readings should be equal (approximately 10 Ohms). | ||
19 | Temperature Too Far from Setpoint (Check Alarm)
|
Note This alarm can be activated if the supply or
temperature does approach setpoint.
|
20 | Defrost Time Too Long (Check Alarm)
|
Note This alarm can be activated at low voltage
and very low box temperature conditions, even under normal operating
conditions.
|
22 | Capacity Test 1 Error (Check Alarm)
|
|
23 | Capacity Test 2 Error (Check Alarm)
|
|
34 | Ambient Air Sensor Open Circuit (Check Alarm)
|
|
35 | Ambient Air Sensor Short Circuit (Check Alarm)
|
|
43 | Return Air Temperature Too High (Check Alarm)
|
|
52 | Probe Error (Check Alarm)
|
|
56 | Compressor Temperature Too High (Shutdown Alarm)
|
|
58 | Phase Sensor Error (Check Alarm)
|
|
59 | Delta Current Error (Log Alarm)
|
|
97 | Compressor Sensor Open Circuit (Log Alarm)
|
Note Unit will operate normally without compressor
sensor. However, controller compressor high temperature protection
is not active.
|
98 | Compressor Sensor Short Circuit (Log Alarm)
|
|
112 | Zero Current
Too High (Check Alarm)
|
|