Modify OptiSet Product Settings

  1. Press the F4 key to enter the main menu. Press the F2 or F3 key to scroll to Controls menu and Press F4 to expand the menu.

  2. Press F3 key and scroll to the setting to be modified. Settings that can be modified:

    • Temperature Setpoint

      Note Setpoint changes > 5° C (9° F) will force the CO2 setting to 1%, O2 setting to 20%, cancel the AFAM DELAY, Optimized Mode, Humidity Control, and Humidity Setpoint.

    • Evaporator Fan Speed

    • Defrost Termination Temperature

    • Humidity Control

    • Humidity Setpoint

    • AFAM DELAY

    • O2 Minimum (if applicable)

    • CO2 Maximum

      Notice
    • Cargo Loss
    • Do not modify any of the above settings without direct instructions from the shipper. Serious cargo damage could occur.
  3. For example, to modify the O2 and CO2 settings, press F3 key to scroll to O2 MIN.

  4. Press the F2 OR F3 key to increase or decrease the O2 Min supplied by the shipper.

  5. Press and hold the F4 key until returned to the main menu. The new rate is recorded in the datalogger and appears on the display.

  6. Press F2 or F3 key to scroll to CO2 MAX.

  7. Press F4 key to enter the setting mode.

  8. Enter the CO2 setting supplied by the shipper.

  9. Press and hold the F4 key until returned to the main menu. The new rate is recorded in the datalogger and appears on the display.