ClimaAIRE I D Controller

         
1.

On/ OFF button.

The Red Alarm (ALARM) symbol will shine in the following two conditions:

  • high or low pressure switches are OFF longer than 10 minutes

  • high or low pressure switches are OFF 5 times per 10 minutes

In both cases, the unit will switch to the Ventilation Mode. If the Red Alarm appears, alarm code is shown on the display.

The Yellow Alarm (WARNING) symbol will shine in case of temperature sensor failure.

If the Yellow Alarm appears, alarm code flashes 5 times on the display. To restart the unit, press the ON/OFF button (1) twice to switch the unit OFF and ON. If the alarm comes up again, don’t restart and see your nearest dealer for service.

2.

Mode select button

(MODE)

(ESCAPE)

Reheat/Auto mode.

The unit will cool or heat the bus automatically (according to thermostat requirements).

A/C mode.

The unit will operate in cool mode.

Heating mode.

The unit will operate in heating mode.

Ventilation mode

Only the blowers are operating.

3.

Temperature button

(UP)

Use to increase/ decrease temperature setpoint.

Temperature button

(DOWN)

4.

Blower speed button

(SPEED)

(ENTER)

Automatic blower speed

The blowers are controlled automatically depending on the thermostat setpoint and passenger compartment conditions.

High blower speed
Medium blower speed
Low blower speed
5.

Fresh air select button

(AIR MODE)

(SMOG)

Automatic mode – the fresh air damper is controlled automatically
Fresh air damper open (100% FA)
Half open – fresh air damper at 50% position (50% FA)
Recirculated air – fresh air damper closed (0% FA)
6. Display Return air temperature icon
Setpoint icon
Red – Boost pump icon
Blue – Compressor clutch icon

Operating Instructions

Turn the system ON by pressing button ON/OFF (1).

Use the buttons MODE, SPEED, AIR MODE and DOWN and UP to adjust the system. By pressing the selection button you select one of the options in the same group.

Use the DOWN button to set lower setpoint temperature (down to Lo = full cooling independent on real temperature). Use the UP button to set higher setpoint temperature (up to Hi = full heating independent on real temperature).

In Auto Mode all functions are controlled by the ClimaAIRE I D controller automatically according to the required setpoint.

Turn the system OFF by pressing button ON/OFF (1).

Specifications

APPLICATION

Control of HVAC unit

SETUP TEMPERATURE RANGE

17 °C (63 °F) to 27 °C (80 °F)

Display in °C and °F as firmware option

OPERATING VOLTAGE RANGE

10 - 32 VDC

CURRENT CONSUMPTION

Max. 100 mA

OPERATING TEMPERATURE RANGE

-30 °C (-22 °F) to 80 °C (176 °F)

CONNECTION

RS232 serial connection

CAN bus - CAN0, CAN1

DIMENSION (WxHxD)

187 mm x 57 mm x 60 mm

POWER SUPPLY

Ready for 12 VDC and 24 VDC

DIAGNOSTIC / PROGRAMMING

RS-232, CANDiag software