Recommendations
To maintain the best temperature management within the load-space it is recommended to operate with the following set-point temperatures in the following ranges.
Recommended setpoint temperatures.
| Temperature Range | Extreme Ambient Temperature | ZONE 1 setpoint | ZONE 2 setpoint | 
|---|---|---|---|
| Temperature below -20°C | +43°C | ‐23°C | off | 
| -30°C | -23°C | off | |
| Temperature between +2°C and +8°C | +45°C | +5°C | off | 
| -30°C | +5°C | off | |
| Temperature between +15°C and +25 °C | +45°C | +20°C | off | 
| -30°C | +20°C | off | 
| Temperature below -20°C | -30°C | -23 °C | +5°C | 
| +20°C | |||
| +45°C | -23 °C | +5°C | |
| +20°C | |||
| Temperature between +2°C and +8°C | +45°C | +5°C | +20°C | 
| +40°C | +5°C | -25°C | |
| -30°C | +5°C | +20°C | |
| Temperature between +15°C and +25 °C | +45°C | +20°C | +5°C | 
| -30°C | +20°C | +5°C | 
- 
               The splitting of the zones for multi-temperature operation must be as stated in the qualification test: 2/3 and 1/3. 
- 
               For the configuration trailer with S3A, Zone 2 maximum split must be 1/3. If a larger Zone 2 compartment is required, please consult with your Thermo King Dealer. 
When operating in multi-temperatures mode:
- 
               For A-500 Spectrum with S3A remote evaporator software version must be equal to or higher than v.3.0.2. 
- 
               CONTROLLING SENSOR for both FRESH and FROZEN range is set RETURN AIR for Zone 1. 
- 
               Blower speed for DIESEL operation pull down and steady state is set HIGH. 
- 
               Blower speed for ELECTRIC operation pull down and steady state is MAXIMUM. 
- 
               Customers who will use the mentioned equipment as a single-temperature unit, the dividing door must be stowed in such a way that it does not interrupt the airflow from the main host unit evaporator and, Zone 2 must be switched off. 
 
     
        
  