Detailed Specifications
Dividing Wall ATP Specifications
Dividing wall ATP specifications
| K factor coefficient | Minimum thickness of dividing wall | ||
| Removable | Fixed | ||
| GRP floor Longitudinal | 2.0 W/m². K | 1.5 W/m². K | 25 mm | 
| GRP floor Transversal | 2.6 W/m². K | 1.5 W/m². K | 40 mm | 
| Aluminium floor Longitudinal | 3.0 W/m². K | 2.0 W/m². K | 25 mm | 
| Aluminium floor Transversal | 3.2 W/m². K | 2.0 W/m². K | 40 mm | 
Dividing wall coefficients include a safety margin to allow for degradation and thermal leakages.
Return air Bulkhead
 Important Return air bulkhead panel to be of solid fixed
               type allowing a minimum return air gap of 52 mm from the evaporator
               panels and the top should be closed to conform to Thermo King recommended
               minimum standards.
            
               | A | Minimum 52 mm | B | Minimum 82 mm | 
| C | Minimum 200 mm | D | Minimum 1927 mm | 
 Note Dimension B MUST be maintained, no
                  matter what the thickness of the trailer wall. With thicker trailer
                  wall where the refrigerated unit is not protruding into the box; maintaining
                  dimension A could reduce dimension B to less than 82 mm. If this is
                  the case, dimension B must be maintained to 82 mm and as a result
                  of this, dimension A may be more than 52 mm.
            
         A-500 Spectrum Software
The A-500 Spectrum unit must be loaded with software revision equal to or later than the following:
- 
                        Rev.3.0.2 
 
     
        
  