Thermocouple Locations
There is no information in the GDP guideline as to the location of or how many thermo couplings for temperature measurement should be inserted into the load space during the qualification test. Therefore, the locations of the thermocouples are referred to as in standard NFX 15-140. This means 20- 25 thermocouples locations are utilised in the box during the qualification test. These thermocouples are calibrated, and the calibration documents are available under request.
- 
               EAIT_1 Return air sensor Zone 1 
- 
               EAOT_1 Supply air sensor Zone 1 
- 
               EAIT_2 Return air sensor Zone 2 
- 
               EAOT_2 Supply air sensor Zone 2 
Thermocouples Ti1_01, Ti1_06, Ti1_11, Ti2_01, Ti2_06 and Ti2_11 are located at Top right corner 150 mm away from any wall/door.
Thermocouples Ti1_02, Ti1_07, Ti1_12, Ti2_02, Ti2_07 and Ti2_12 are located at Right bottom corner between boxes and wall.
Thermocouples Ti1_03, Ti1_08, Ti1_13, Ti2_03, Ti2_08 and Ti2_13 are located at Left bottom corner between boxes and wall.
Thermocouples Ti1_04, Ti1_09, Ti1_14, Ti2_04, Ti2_09 and Ti2_14 are located at Top left corner 150 mm away from any wall/door.
Thermocouples Ti1_05, Ti1_10, Ti1_15, Ti2_05, Ti2_10 and Ti2_15 are located in the centre.
- 
               EAIT_1 Return air sensor 
- 
               EAOT_1 Supply air sensor 
Thermocouples Ti1_01, Ti1_06, Ti1_11, and Ti1_16 are located at Top right corner 150 mm away from any wall/door.
Thermocouples Ti1_02, Ti1_07, Ti1_12, and Ti1_17 are located at Right bottom corner 150 mm away from any wall/door.
Thermocouples Ti1_03, Ti1_08, Ti1_13 and Ti1_18 are located at Left bottom corner 150 mm away from any wall/door.
Thermocouples Ti1_04, Ti1_09, Ti1_14 and Ti1_19 are located at Top left corner 150 mm away from any wall/door.
Thermocouples Ti1_05, Ti1_10, Ti1_15 and Ti1_20 are located in the centre.
Ambient Sensors Te01 and Te09 are located at Top right corner 150 mm away from any wall/door.
Ambient Sensors Te02 and Te10 are located at Right bottom corner 150 mm away from any wall/door.
Ambient Sensors Te03 and Te11 are located at Left bottom corner 150 mm away from any wall/door.
Ambient Sensors Te04 and Te12 are located at Left bottom corner 150 mm away from any wall/door.
Ambient Sensors Te05 is located at Center of the left wall 150 mm away from any wall/door.
Ambient Sensors Te06 is located at Center of the floor 150 mm away from any wall/door.
Ambient Sensors Te07 is located at Center of the right wall 150 mm away from any wall/door.
Ambient Sensors Te08 is located at Center of the ceiling 150 mm away from any wall/door.
 
     
        
  