Standard Display
The Standard Display is a ¼ VGA graphical type display. The temperature can be displayed in Celsius or Fahrenheit.
The Standard Display will display the controlling sensor and Setpoint. The Setpoint will be the low reading with the C or F.
Once a key is pressed, the Standard Display will change to the Unit Status Display. After two minutes of no key activity, the display will return to the Standard Display.
Idle Screen and Check Symbol
After approximately 30 seconds of inactivity, the display will go into hibernation and one of the following symbols will be displayed. Display alternates between the idle screen and the standard display during this time.
Happy face = everything is OK | |
Disgruntled face = there is a message | |
Unhappy face = there is an alarm |
The check symbol indicates that a Smart PTI has recently been running and no problems were found. The checkmark will only be shown in the normal operation state. This symbol will appear at the left hand corner of the idle screen display.
Unit Status Display
The Unit Status Display will show the following (looking from top to bottom):
Display Icons
Mode Descriptions
Chilled/Cooling (Magnum+ and CFF only)
Chilled cooling is a mode where the unit setpoint is set to above -10C. The function here is to maintain setpoint temperature by controlling the temperature on the supply air.
The supply air is not allowed to be lower than the setpoint. Chilled/cooling mode can operate the unit in different modes where the compressor can run loaded, unloaded/loaded and vapor injection depending on the need for cooling capacity. The condenser fan will operate in an on/off algoritim depending on the temperature on the condenser. The evaporator fans will operate in either high or low speed mode depending on the need for capacity.
Chilled/Heating (Magnum+ and CFF only)
Chilled heating is a mode the unit setpoint is set to above -10C. The function here is to maintain setpoint temperature by controlling the temperature on the supply air.
The supply air is not allowed to be lower than the setpoint. Chilled heating mode can operate the unit where only the evaporator fan low speed is running, evaporator high speed is running or evaporator high speed and heat is on.
Frozen/Cooling Down
Frozen/cooling down mode where the unit setpoint is set to below -10C. The function here is to maintain setpoint temperature by controlling the temperature on the return air.
Frozen/cooling down mode can operate the unit in different modes where the compressor is loaded and vapor injection is on/off. The condenser fan will operate in an on/off algorithm depending on the temperature on the condenser. The evaporator fans will operate in low speed mode or off.
Defrost
Defrost is a situation where the unit either on demand or timing is defrosting the evaporator coil. The unit is heating with the heating elements awaiting 18C on the evaporator sensor.
When the set Defrost termination temperature is reached, the unit will return to the operation mode depending on the setpoint.
PTI
PTI is a pretrip inspection and is used to diagnose the condition of the unit. There are a possibility to chose between several type of PTI´s depending on the test needed to secure the functionality of the unit.
Silent mode
Silent mode is a way to make the reefer unit silent without manual switching it OFF and ON.