Pharma
Single and Multi-temperatures temperature Units qualified for pharmaceutical applications under Thermo King protocol are configured with specific Pharma configuration file and parameters loaded during commissioning by your local dealer. Evaporators fans have to run during the Null Cycle.
Temperature Range Table
Thermo King recommends to run the unit with the recommended Setpoints below:
V-300 MAX Spectrum 30/50 ES150+ES150:
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Deviation Setpoint |
---|---|---|---|
Temperature between +2°C and +8°C | +40°C / ‐30°C | +6°C | +/- 2°C of setpoint |
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +/- 2°C of setpoint |
V-500 MAX Spectrum 30/50 ES300+ES300:
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Deviation Setpoint |
---|---|---|---|
Temperature between +2°C and +8°C | +40°C / ‐30°C | +6°C | +/- 2°C of setpoint |
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +2/- 3°C of setpoint |
V-800 MAX Spectrum 30/50 ES400+ES400:
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Deviation Setpoint |
---|---|---|---|
Temperature between +2°C and +8°C | +40°C / ‐30°C | +6°C | +3/- 2°C of setpoint |
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +/- 2°C of setpoint |
V-300 MAX Spectrum 30/50 ES200+ES100:
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Deviation Setpoint |
---|---|---|---|
Temperature between +2°C and +8°C | -35°C | +4°C | +3/- 1°C of setpoint |
-20°C | +5°C | - 2°C of setpoint | |
Temperature between +15°C and +25°C | +35°C | +20°C | +/- 2°C of setpoint |
-20°C | +21°C | - 3°C of setpoint |
Efficient loading practices and operating procedures have to be followed to ensure optimum air circulation and temperature management.