Pharma
Single temperature units qualified for pharmaceutical applications under Thermo King protocol are configured with specific Optiset profiles visible on the HMI display as follow:
-
PHARMA AMBIENT: for temperature ranges +15°C to 25°C
-
PHARMA CHILLED: for temperature ranges +2°C to 8°C
-
PHARMA FROZEN: for temperature below -20°C
In case the operator is not using the Optiset profiles, ThermoKing recommends to run the unit with the recommended Setpoints below:
Single Temperature Units
Temperature Range | Recommended Setpoint | Max Deviation Setpoint | Max Deviation Returned Air |
---|---|---|---|
Temperature < -20°C | -20°C | +1.5°C of setpoint | + 1°C of setpoint |
Temperature between 2°C and 8°C | +4°C | +/- 2°C of setpoint | +/- 1.5°C of setpoint |
Temperature between 15°C and 25°C | +20°C | +/- 2.5°C of setpoint | +/- 2°C of setpoint |
For multi-temperatures units qualified for pharmaceutical applications under ThermoKing protocol, ThermoKing recommends to operate the unit with:
-
PTC parameter ACTIVATED (ON) [with SLXi this set to default on]
-
Zone 1 DAC Kit switch turned ON with the recommended Setpoints below:
Multi-Temperature Units
Temperature Range | Recommended Setpoint | Max Deviation Setpoint | Max Deviation Returned Air |
---|---|---|---|
Temperature < -20°C | -25°C | +2°C of setpoint | + 2°C of setpoint |
Temperature between 2°C and 8°C | +6°C | +/- 2°C of setpoint | +/- 2°C of setpoint |
Temperature between 15°C and 25°C | +20°C | +/- 4°C of setpoint | +/- 4°C of setpoint |