Pharma

Single temperature units qualified for pharmaceutical applications under Thermo King protocol are configured with specific Optiset profiles visible on the HMI display as follow:

  • PHARMA AMBIENT: for temperature ranges +15°C to 25°C

  • PHARMA CHILLED: for temperature ranges +2°C to 8°C

  • PHARMA FROZEN: for temperature below -20°C

In case the operator is not using the Optiset profiles, ThermoKing recommends to run the unit with the recommended Setpoints below:

Single Temperature Units

Temperature Range Recommended Setpoint Max Deviation Setpoint Max Deviation Returned Air
Temperature < -20°C -20°C +1.5°C of setpoint + 1°C of setpoint
Temperature between 2°C and 8°C +4°C +/- 2°C of setpoint +/- 1.5°C of setpoint
Temperature between 15°C and 25°C +20°C +/- 2.5°C of setpoint +/- 2°C of setpoint

For multi-temperatures units qualified for pharmaceutical applications under ThermoKing protocol, ThermoKing recommends to operate the unit with:

  • PTC parameter ACTIVATED (ON) [with SLXi this set to default on]

  • Zone 1 DAC Kit switch turned ON with the recommended Setpoints below:

Multi-Temperature Units

Temperature Range Recommended Setpoint Max Deviation Setpoint Max Deviation Returned Air
Temperature < -20°C -25°C +2°C of setpoint + 2°C of setpoint
Temperature between 2°C and 8°C +6°C +/- 2°C of setpoint +/- 2°C of setpoint
Temperature between 15°C and 25°C +20°C +/- 4°C of setpoint +/- 4°C of setpoint