Specifications

System Net Cooling Capacity – Full Cool

Magnum Plus™ Model – Air Cooled Condensing

Net cooling capacity at 37.8 C (100 F) ambient temperature at 60 Hz power
Evaporator Return Air Temperature Power requirement Watt Watts KCal/hr BTU/hr
21.1 C (70 F) 11,500 16,500 13,608 56,700
1.7 C (35 F) 11,000 11,900 10,584 40,945
-17.8 C (0 F) 7,500 7,200 6,300 24,785
-29 C (-20 F) 6,600 5,000 4,360 17,251
-35 C (-31 F) 6,000 4,100 3,528 14,000
-40 C (-40 F) 3,650 3,700 3,184 12,636
  • System net cooling capacity with a 38 C (100 F) ambient air temperature.

CFF Model – Air Cooled Condensing

Net cooling capacity at 37.8 C (100 F) ambient temperature at 60 Hz power
Evaporator Return Air Temperature Power requirement Watt Watts KCal/hr BTU/hr
21.1 C (70 F) 10,650 15,700 13,500 53,618
1.7 C (35 F) 8,800 11,375 9,781 38,847
-17.8 C (0 F) 5,690 6,250 5,374 21,345
-29 C (-20 F) 4,570 4,035 3,469 13,780
  • System net cooling capacity with a 38 C (100 F) ambient air temperature.

System Net Heating Capacity

  60 Hz Power
Heating Capacity
Watts Kcal/hr BTU/hr
MAGNUM PLUS™ 5,250 4,515 17,914
CFF 5,250 4,515 17,914
  • System net heating capacity includes electric resistance rods and fan heat.

MP–5000 Controller Specification

Temperature Controller:
Type MP-5000 is a controller module for the Thermo King Magnum Plus and CFF unit models. Additional requirements can be met by means of expansion modules. The MP–5000 is solely responsible for temperature regulation of the reefer container, but other monitoring equipment can be used in conjunction with the MP-5000, such as a telematics device.
Setpoint Range

-40.0 to +30.0 C (-40.0 to +86.0 F) — Magnum Plus™

-30.0 to +30.0 C (-22.0 to +86.0 F) — CFF

Temperature Display Range -70.0 to +80.0 C (-94.0 to +176.0 F)
Controller Software  
Version See controller display for SW version
Defrost Initiation:
Evaporator Coil Sensor Manual Switch or Demand Defrost Initiation: Coil must be below 18 C (65 F). Defrost cycle starts when technician or controller requests defrost initiation.
Timed Defrost Initiation: Coil must be below 4 C (41 F). Defrost cycle starts 1 minute after the hour immediately following a defrost timer request for defrost initiation. For example, if the defrost timer requests a defrost cycle at 7:35, the defrost cycle will start at 8:01. Datalogger will record a Defrost event for each interval in which a Defrost cycle is pending or active (i.e. both the 8:00 and 9:00 data logs).
Demand Defrost Demand defrost function initiates defrost when: Temperature difference between the return air sensor and defrost (evaporator coil) sensor is too large for 90 minutes Temperature difference between the supply air sensors and return air sensor is too large
 
 
Defrost Timer:
Chilled mode Evaporator Coil Temperature must be below 5C (41 F) to activate the defrost compressor hour timer.
Chilled Mode (continued) There is an interval set for defrosting, however, the defrost timer is built intelligent - it detects whether or not there is ice building up on the coil. If there is no ice building up on the coil, it extends the defrost interval, and if there is Ice building up earlier on the coil it reduces the defrost interval. The maximum interval is 48 hours.
Frozen mode Every 8 hours of compressor operation. Defrost interval increases 2 hours each timed defrost interval. Maximum time interval in Frozen mode is 24 hours.
Reset to Base Time Defrost timer resets if the unit is off more than 12 hours, setpoint is changed more than 5 C (9 F) or PTI pretrip test occurs.
Defrost Termination:
Defrost (Coil) Sensor Chilled mode: Terminates defrost when coil sensor temperature rises to 18 C (65 F). Frozen mode: Terminates defrost when coil sensor temperature rises to 18 C (65 F).
Termination Timer Terminates defrost after 90 minutes at 60 HZ operation if coil sensor has not terminated defrost (120 minutes at 50 Hz operation)
Power Off Turning Unit On/Off switch Off terminates defrost
Compressor Shutdown Protection (Auto Reset):
Stops Compressor 148 C (298 F)
Allows Compressor Start 90 C (194 F)
Bulb Mode:
Evaporator Fan Speed Settings Flow High: High speed only
Flow Low: Low speed only
Flow Cycle: Fans will cycle between low and high speed every 60 minutes
Defrost Termination Temperature Setting 4 to 30 C (40 to 86 F)

Physical Specification

Fresh Air Exchange Venting System (Adjustable):  
MAGNUM PLUS™, CFF

0 to 225 m3/hr (0 to 168 ft3/min.) @ 60 Hz

Weight (net):  
MAGNUM PLUS™, CFF Base Unit 357 kg (787 lbs) before March 1st 2025.
348 kg (767 lbs) after March 1st 2025 (with New Evaporator).
Water-cooled Condenser-Receiver Option, MAGNUM PLUS™ and CFF only 13.6 Kg (30 lb.)

Unit Noise and Vibration

Conformity assessment procedure followed Machinery Frequency Sound power level (Sound Power, dB(A))
 
ISO 3744:2010     Measured Guaranteed
  MAGNUM PLUS™, CFF 50 Hz 90 dB(A) 91 dB(A)
  60 Hz 95 dB(A) 96 dB(A)
Generated vibration to operator: Negligible