MAINS operating mode (supply via 400 V CEE socket)

The figure shows the classic version for all refrigeration machines. Always select this supply if a CEE socket is available and the refrigeration machine supports this supply.

To ensure the refrigeration machine's safe and reliable operation in mains operation mode, observe the following recommendations:

  • The mains supply cables must comply with the specifications of the applicable regulations at the site of use. We recommend using type H07BQ-F cable.

  • The mains cable must be completely unwound. The maximum cable length must not exceed X metres.

  • Power connection to a 5-pin CEE socket with 400 Volt / 50 Hz output. 32 A D-characteristic automatic circuit breaker, slow-blow fuse or motor protection switch. The series resistance of the fuse must not exceed X ohms.

  • If a ground-fault circuit interrupter is used (see DIN VDE 010-410/DIN VDE 0100-530), FRIGOBLOCK recommends using an RCCB2-type 30 mA all-current sensitive variant.

Plug in the mains cable with switch position set to "0" and then select the "Mains" switch position. The universal remote control indicates operational readiness. If the "Phase error" error message is displayed, the pins marked red in the CEE plug must be turned with a screwdriver.

  • The CEE plug has two pins (contrasting in colour) that can be turned.

  • Turn these pins in the CEE plug about 180° using a screwdriver.

  • Plug the CEE plug back into the socket.

  • Set the Mains-0-Alternator switch to the "Mains" position.

  • Turn on the FRIGOBLOCK refrigeration machine using the universal remote control.

  • Check the direction of rotation once again using the flag.

  • FRIGOBLOCK refrigeration machines that are equipped with a direction of rotation monitor now run in the correct direction of rotation.