Unit Protection Devices
Preheat Buzzer: The preheat buzzer sounds when the controller energizes the preheat relay. This warns anyone near the unit that the controller is about to start the engine.
Coolant Level Switch: The coolant level switch closes if the coolant level drops below an acceptable level. If it stays closed for a specified time, the A-Series Controller records an alarm code.
Engine Coolant Temperature Sensor: The microprocessor uses the engine coolant temperature sensor to monitor the engine coolant temperature. If the engine coolant temperature rises above an acceptable level, the A-Series Controller records an alarm code. The controller might also shut the unit down.
High Pressure Cutout Switch: The high pressure cutout switch is located on the compressor discharge manifold. If the compressor discharge pressure becomes excessive, the switch opens the circuit to the run relay to stop the unit. The microprocessor will record an alarm code.
High Pressure Relief Valve: This valve is designed to relieve excessive pressure in the refrigeration system. It is located on the receiver tank. If the high pressure relief valve opens, much of the refrigerant will be lost. Take the unit to a Thermo King dealer if this occurs.
Low Oil Level Switch: The low oil level switch closes if the oil drops below an acceptable level. If it stays closed for a specified time, the microprocessor shuts the unit down and records an alarm code.
Low Oil Pressure Switch: The low oil pressure switch closes if the oil pressure drops below an acceptable level. If it stays closed for a specified time, the microprocessor shuts the unit down and records an alarm code.
Overload Relay - Automatic Reset: An overload relay protects the CMG - Combined Motor Generator. The overload relay opens the circuit to the electric motor if the motor overloads for any reason (e.g., low line voltage or improper power supply) while the unit is on electric standby operation. the A-Series Controller records an alarm code.
Smart FETs: Smart FETs in the microprocessor protect some circuits and components from an overcurrent condition.
Fuses: Fuses are located in harnesses and in the Power Distribution Module (PDM). All fuses must be serviced only by qualified Thermo King technicians. Contact your nearest Thermo King Dealer for assistance.
48 Volt Fuses in PDM (Single Temperature Units Only)
Fuse | Size | Function |
F8 | 20A | Blowers Condenser Roadside |
F10 | 20A | Blowers Condenser Curbside |
F12 | 20A | DC Charger |
F14 | 20A | Blowers Evaporator Roadside |
F16 | 20A | Blowers Evaporator Curbside |
48 Volt Fuses in PDM (Multi Temperature Units Only)
Fuse | Size | Function |
F8 | 20A | Blowers Condenser Roadside |
F10 | 20A | Blowers Condenser Curbside |
F12 | 20A | Blowers Evaporator Curbside |
F14 | 20A | Blowers Evaporator Roadside |
F100 | 3A | Fan |
F200 | 50A | DCDC Converter |
12 Volt Fuses in PDM
Fuse | Size | Function |
F1 | 5A | BlueBox Power Out |
F2 | 5A | LPM Power Out |
F3 | 3A | 3rd Party Power Out |
F4 | 5A | PSM Power Out |
F5 | 5A | HMI Power Out |
F6 | 5A | Printer Power Out |
F7 | 10A | ECU Power Out |
12 Volt Fuses in Harness
Fuse | Size | Function |
60A | Air Heater | |
40A | Charge Supply | |
40A | Starter Solenoid | |
20A | LPM (Low Power Module) | |
20A | HPM (High Power Module |