C-Series

C-Series (CSR)

i Introduction

This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.

This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.

This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.

Thermo King’s warranty shall not apply to any equipment which has been so installed, maintained, repaired or altered as, in the manufacturer’s judgment, to affect its integrity.

Manufacturer shall have no liability to any person or entity for any personal injury, property damage or any other direct, indirect, special, or consequential damages whatsoever, arising out of the use of this manual or any information, recommendations or descriptions contained herein. The procedures described herein should only be undertaken by suitably qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.

There is nothing complicated about operating and maintaining your Thermo King unit, but a few minutes studying this manual will be time well spent.

Performing pre-trip checks and enroute inspections on a regular basis will minimize operating problems. A regular maintenance program will also help to keep your unit in top operating condition. If factory recommended procedures are followed, you will find that you have purchased the most efficient and dependable temperature control system available.

All service requirements, major and minor, should be handled by a Thermo King dealer for four very important reasons:

  • They are equipped with the factory recommended tools to perform all service functions.

  • They have factory trained and certified technicians.

  • They have genuine Thermo King replacement parts.

  • The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.

 

Copies of the approved Thermo King documentation can be found on the Thermo King iService Portal: http://iservice.thermoking.com/esa.

Customer Satisfaction Survey Assistance/Feedback

Let your voice be heard!

Your feedback will help improve our manuals. The survey is accessible through any internet-connected device with a web browser.

Scan the Quick Response (QR) code or click Technical Publications EMEA Feedback to complete the survey.

Need assistance finding technical literature, to report missing content, or to provide feedback on our technical literature? Email Thermo King Americas Publications at thermokingamericaspublications@thermoking.com.

Chapter 1: Safety Precautions

1.1: Danger, Warning, Caution, and Notice

Thermo King®/ FRIGOBLOCK recommends that all service be performed by a Thermo King/FRIGOBLOCK dealer and to be aware of several general safety practices.

Thermo King® recommends that all service be performed by a Thermo King dealer and to be aware of several general safety practices.

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this unit depend upon the strict observance of these precautions. The four types of advisories are defined as follows:

    Danger
  • Hazard
  • Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
    Warning
  • Hazard
  • Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
    Caution
  • Hazard
  • Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury and unsafe practices.
    Notice
  • Hazard
  • Indicates a situation that could result in equipment or property-damage only accidents.

1.2: General Practices

    Danger
  • Hazard of Explosion
  • Never apply heat to a sealed refrigeration system or container. Heat increases internal pressure, which might cause an explosion resulting in death or serious injury.
    Danger
  • Hazardous Gases - Personal Protective Equipment (PPE) Required
  • Refrigerant in the presence of an open flame, spark, or electrical short produces toxic gases that are severe respiratory irritants which can cause serious injury or possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Danger
  • Risk of Injury
  • Keep your hands, clothing, and tools clear of fans and/or belts when working on a unit that is running or when opening or closing compressor service valves. Loose clothing might entangle moving pulleys or belts, causing serious injury or possible death.
    Danger
  • Refrigerant Vapor Hazard
  • Do not inhale refrigerant. Use caution when working with refrigerant or a refrigeration system in any confined area with a limited air supply. Refrigerant displaces air and can cause oxygen depletion, resulting in suffocation and possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Warning
  • Hazard of Explosion
  • Never close the compressor discharge service valve when the unit is operating. Never operate the unit with the discharge valve closed (front seated). This condition increases internal pressure, which can cause an explosion.
    Warning
  • Proper Equipment Condition
  • Gauge manifold hoses must be in good condition before using them. Never let them come in contact with moving belts, fans, pulleys or hot surfaces. Defective gauge equipment can damage components or cause serious injury.
    Warning
  • Personal Protective Equipment (PPE) Required
  • Always wear goggles or safety glasses and proper PPE when working on a unit. Refrigerant liquid, oil, and battery acid can permanently damage your eyes. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Warning
  • Equipment Damage and Risk of Injury
  • Never drill holes into the unit unless instructed by Thermo King. Holes drilled into high voltage cables could cause an electrical fire, severe personal injury, or even death.
    Warning
  • Risk of Injury
  • When using ladders to install or service refrigeration systems, always observe the ladder manufacturer’s safety labels and warnings. A work platform or scaffolding is the recommended method for installations and servicing.
    Caution
  • Sharp Edges
  • Exposed coil fins can cause lacerations. Service work on the evaporator or condenser coils should only be accomplished by a certified Thermo King technician.
    Notice
  • Equipment Damage
  • All unit mounting bolts must be installed, be the correct length for their application, and torqued to specifications. Missing bolts, incorrect bolt lengths and improper torque specifications can damage equipment and void the warranty.

    Danger
  • Risk of Injury
  • Keep your hands, clothing, and tools clear of fans and/or belts when working on a unit that is running or when opening or closing compressor service valves. Loose clothing might entangle moving pulleys or belts, causing serious injury or possible death.
    Caution
  • Sharp Edges
  • Exposed coil fins can cause lacerations. Service work on the evaporator or condenser coils should only be accomplished by a certified Thermo King technician.

1.3: Auto Start/Stop Auto Start Hazards

    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Turn the unit On/Off switch Off and disconnect the Auto Start Disable switch on top of the electrical cabinet before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King unit.
    Caution
  • Risk of Injury
  • The vehicle's engine may be equipped with Auto Start/Stop. The vehicle must be turned off before servicing the unit.

    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Turn the unit On/Off switch Off before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King unit.
    Caution
  • Risk of Injury
  • The vehicle's engine may be equipped with Auto Start/Stop. The vehicle must be turned off before servicing the unit.

    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Turn the unit On/Off switch Off before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King unit.
    Caution
  • Risk of Injury
  • Some vehicles may be equipped with an Auto Start-Stop feature allowing the engine to restart automatically if required by the system. Refer to your vehicle’s operator’s manual regarding the Auto Start-Stop safety warnings before accessing the engine compartment. Failure to do so may result in serious injuries due to automatic engine restart.

    Caution
  • Risk of Injury
  • Thermo King units can start and run automatically any time the unit’s HMI controller is on. Before removing covers, or working on any part of the unit, always turn off the HMI Main Power On/Off switch.
    Caution
  • Risk of Injury
  • Some vehicles may be equipped with Auto Start-Stop feature allowing the engine to restart automatically if required by the system. Switch the ignition off before opening the hood or performing any maintenance. Failure to do so may result in serious injuries due to automatic engine restart. Always switch the ignition off before leaving vehicle, as the system may have turned the engine off, but the ignition will still be on and automatic restart may occur. Refer to your vehicle owners manual for further information.

1.4: Electrical Hazards

    Notice
  • Equipment Damage
  • Do not connect other manufacturers’ equipment or accessories to the unit or to the Thermo King batteries unless approved by Thermo King. Failure to do so can result in severe damage to equipment and void the warranty.

    Danger
  • Hazardous Voltage
  • Units equipped with Electric Standby option operate on 115 or 230 volts ac. This voltage is potential dangerous, causing serious injury or death.
    Warning
  • Live Electrical Components
  • Control circuits are low voltage (24 Vac and 12 Vdc). This voltage potential is not considered dangerous. Large amount of current available (over 30 amperes) can cause severe burns if shorted to ground. Do not wear jewelry, watch or rings. These items can shortcut electrical circuits and cause severe burns to the wearer.

High Voltage

    Danger
  • Hazardous Voltage
  • When servicing or repairing a temperature control unit, the possibility of serious or even fatal injury from electrical shock exists. Extreme care must be used when working with a refrigeration unit that is connected to a source of operating power, even if the unit is not operating. Lethal voltage potentials can exist at the unit power cord, inside the control box, at the motors and within the wiring harnesses.
    Warning
  • Hazardous Voltage
  • The unit On/Off switch must be turned Off before connecting or disconnecting the standby power plug. Never attempt to stop the unit by disconnecting the power plug.
    Warning
  • Risk of Injury
  • The unit power plug must be clean and dry before connecting it to a power source.
    Warning
  • Risk of Injury
  • Do not make rapid moves when working on high voltage circuits in the refrigeration unit. Do not grab for falling tools because you might accidentally touch a high voltage source.
    Warning
  • Hazardous Voltage
  • Treat all wires and connections as if they were high voltage until a meter and wiring diagram indicate otherwise. Only use tools with insulated handles. Never hold uninsulated metal tools near exposed, energized conductors. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
    Warning
  • Hazardous Voltage
  • Never work alone on high voltage circuits in the refrigeration unit. Another person should be nearby to shut off the unit and provide aid in the event of an accident. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
    Warning
  • Personal Protective Equipment (PPE) Required
  • In the event of an electrical accident, all required PPE should be near the work area in accordance with OSHA, NFPE 70E, or other local, state, or country-specific requirements for a Category 3 risk.
    Warning
  • Hazardous Voltage w/Capacitors
  • Be careful when working with electrical circuits that contain capacitors. Some capacitors hold a significant electrical charge that might cause burns or shocks if accidentally discharged. Capacitors must be discharged before working on electrical circuits. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.

Low Voltage

    Warning
  • Live Electrical Components
  • Control circuits used in refrigeration units are low voltage (12 to 48 Vdc). However, the large amount of amperage available can cause severe burns if accidentally shorted to ground with metal objects, such as tools. Do not wear jewelry, watches, or rings because they increase the risk of shorting out electrical circuits and damaging equipment or causing severe burns. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.

1.5: Refrigerant Hazards

Although fluorocarbon refrigerants (R-404A/R-452A and R-134a) are classified as safe, observe caution when working with refrigerants or around areas where they are being used in the servicing of your unit.

    Danger
  • Hazardous Gases - Personal Protective Equipment (PPE) Required
  • Refrigerant in the presence of an open flame, spark, or electrical short produces toxic gases that are severe respiratory irritants which can cause serious injury or possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Danger
  • Refrigerant Vapor Hazard
  • Do not inhale refrigerant. Use caution when working with refrigerant or a refrigeration system in any confined area with a limited air supply. Refrigerant displaces air and can cause oxygen depletion, resulting in suffocation and possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Warning
  • Personal Protective Equipment (PPE) Required
  • Refrigerant in a liquid state evaporates rapidly when exposed to the atmosphere, freezing anything it contacts. Wear butyl lined gloves and other clothing and eye wear when handling refrigerant to help prevent frostbite. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

    Danger
  • Hazardous Pressures
  • Always store refrigerant in proper containers, out of direct sunlight and away from intense heat. Heat increases pressure inside storage containers, which can cause them to burst and could result in severe personal injury.
    Danger
  • Combustible Hazard
  • Do not use oxygen (O2 ) or compressed air for leak testing. Oxygen mixed with refrigerant is combustible.
    Warning
  • Hazardous Gases
  • Do not use a Halide torch. When a flame comes in contact with refrigerant, toxic gases are produced. These gases can cause suffocation, even death.
    Warning
  • Personal Protective Equipment (PPE) Required
  • Refrigerant in a liquid state evaporates rapidly when exposed to the atmosphere, freezing anything it contacts. Wear butyl lined gloves and other clothing and eye wear when handling refrigerant to help prevent frostbite. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

1.6: Refrigerant Oil Hazards

Observe the following when working with or around refrigerant oil.

    Warning
  • Personal Protective Equipment (PPE) Required
  • Protect your eyes from contact with refrigerant oil. The oil can cause serious eye injuries. Protect skin and clothing from prolonged or repeated contact with refrigerant oil. To prevent irritation, wash your hands and clothing thoroughly after handling the oil. Rubber gloves are recommended. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

    Warning
  • Personal Protective Equipment (PPE) Required
  • Protect your eyes from contact with refrigerant oil. The oil can cause serious eye injuries. Protect skin and clothing from prolonged or repeated contact with refrigerant oil. To prevent irritation, wash your hands and clothing thoroughly after handling the oil. Rubber gloves are recommended. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Notice
  • Equipment Damage
  • Use the correct oil in Thermo King systems to avoid damaging equipment and nullifying its warranty.
    Notice
  • Equipment Damage
  • Do not mix refrigerant oils. Mixing incompatible oils will damage the system.
    Notice
  • Equipment Damage
  • Use dedicated refrigeration equipment to prevent contaminating refrigeration systems with the wrong type of oil or refrigerant.
    Notice
  • System Contamination
  • Do not expose the refrigerant oil to the air any longer than necessary. Store refrigerant oil in an approved sealed container to avoid moisture contamination. The oil will absorb moisture, which results in much longer evacuation times and possible system contamination.
    Notice
  • Material Damage
  • Wipe up spills immediately. Refrigerant oil can damage paints and rubber materials.

1.7: First Aid

REFRIGERANT

  • Eyes: For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical attention.

  • Skin: Flush area with large amounts of warm water. Do not apply heat. Remove contaminated clothing and shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection. Get prompt medical attention. Wash contaminated clothing before reuse.

  • Inhalation: Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.

  • Frost Bite: In the event of frost bite, the objectives of First Aid are to protect the frozen area from further injury, warm the affected area rapidly, and to maintain respiration.

REFRIGERANT OIL

  • Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.

  • Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.

  • Inhalation: Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.

  • Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.

ENGINE COOLANT

  • Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.

  • Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.

  • Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.

BATTERY ACID
Under normal usage, the Ni-MH batteries are hermetically sealed. In case of accident, perform the following instructions:

  • Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention. Wash skin with soap and water.

  • Skin: Immediately remove contaminated clothing. Wash skin with large volumes of water, for at least 15 minutes. Wash skin with soap and water. Do not apply fatty compounds. Seek immediate medical assistance.

  • Inhalation: Provide fresh air. Rinse mouth and nose with water. Seek immediate medical assistance.

  • Ingestion: If the injured person is fully conscious: make the person drink extensive amounts of milk. Do not induce vomiting. Take the injured person immediately to a hospital.

ELECTRICAL SHOCK

Take IMMEDIATE action after a person has received an electrical shock. Get quick medical assistance, if possible.

The source of the shock must be quickly stopped, by either shutting off the power or removing the victim. If the power cannot be shut off, the wire should be cut with a non-conductive tool, such as a wood-handle axe or thickly insulated cable cutters. Rescuers should wear insulated gloves and safety glasses and avoid looking at wires being cut. The ensuing flash can cause burns and blindness.

If the victim must be removed from a live circuit, pull the victim away with a non-conductive material. Use wood, rope, a belt or coat to pull or push the victim away from the current. DO NOT TOUCH the victim. You will receive a shock from current flowing through the victim’s body. After separating the victim from power source, immediately check for signs of a pulse and respiration. If no pulse is present, start Cardiopulmonary Resuscitation (CPR). If a pulse is present, respiration might be restored by using mouth-to-mouth resuscitation. Call for emergency medical assistance.

ASPHYXIATION

Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.

1.8: Safety Decals

Safety decals and locations vary depending on model.

Fan Caution
Automatic Start Caution

Observe all safety decals placed in various locations on the unit.

Typical Safety Decals

Electric Standby Nameplates (Models 20 and 50 Only)

Electrical Hazard Cautions
Belt Caution

Refrigerant

Refrigerant Decal is located adjacent to the service ports for charging or recovering the gas, as per the F-Gas regulation.

F Gas decal indicates that this equipment Contains fluorinated greenhouse gases.

Chapter 2: Unit Description

2.1: Introduction

Unit — Example

The Thermo King truck refrigeration systems are two-piece nose/roof-mounted units. The compressor is powered from the vehicle engine via a belt. Refrigeration hoses and tubing are used to connect the unit to the compressor.

The Thermo King refrigeration units are designed for fresh and frozen applications on vans and small trucks.

The control circuits operate on 12V or 24VDC supplied by the truck batteries for over-the-road operation. The refrigeration system is protected by a high pressure cutout switch and a low pressure cutout switch.

The digital controller with a programmable microprocessor controls unit operation and quickly and accurately shows information on the display.

Compressor operation is controlled by the thermostat, energizing the clutch during engine operation.

C-Series Units Include:

  • C-150, C-150 10, C-150 MAX 10 and C-150 MAX 30

  • C-250, C-250 10, C-250 MAX 10 and C-250 MAX 30

  • C-350, C-350 10, C-350 MAX 10 and C-350 MAX 30

  • C-450, C-450 10, C-450 MAX 10 and C-450 MAX 30

  • C-550, C-550 10, C-550 MAX 10 and C-550 MAX 30

  • C-650, C-650 10, C-650 MAX 10 and C-650 MAX 30

  • C-750 MAX 10 and C-750 MAX 30

There are two basic models:

  • C-150, C-250, C-350 and C-450: Cool with only vehicle powered engine driven compressor operation.

  • Model 10: Cool and Defrost with only vehicle powered engine driven compressor operation.

  • Model 30: Hot gas heat, Cool, and Defrost with only vehicle powered engine driven compressor operation.

2.2: Standard Unit Features

  • Condenser - Lightweight design, easy to service with automotive grade polypropylene cover.

  • Evaporator - Ultra slim design, aluminum construction automotive grade Acrylonitrile Butadiene Styrene (ABS) cover.

  • In-cab controller: CSR

  • Digital thermometer

  • Electronic thermostat - adjustable:

    • R-134a without defrost: 0ºC to +22ºC

    • R-134a with defrost: -10ºC to +22ºC

    • R-404A: -32ºC to +22ºC

  • Hot gas automatic defrost

  • Road compressor QP08 (C–150 Unit)

  • Road compressor QP13 (C-250 Unit)

  • Road compressor QP15 (C–350 Unit)

  • Road compressor QP16 (C-450 Unit)

  • Refrigerant - R-134a, R-452A or R-404A (depending on unit model).

2.3: Electronic Control System

Thermo King direct drive refrigeration units are composed of a condenser unit, an evaporator unit, a vehicle compressor and a control panel (Incab Control Box) which operates the unit. The Electronic Control System is composed of an Electronic Control Module (located inside the condenser unit) and the In-cab Control Box. This In-cab Control Box allows the truck driver to operate the Thermo King refrigeration unit.

In-cab Control Box

Description of the Electronic Control System

The Electronic Control System has the following characteristics:

  • Auto Start

  • Delayed Start

  • Active Display

  • Low Battery Voltage Alarm

  • Battery voltage value display

  • Unit Control without In-cab Control Box

  • Manual or Automatic Defrost

  • Return Air Temperature Sensor

  • Setpoint Temperature Reading

Auto Start: In case of power shut off, if the unit was on, the unit will come back on again when the power is re-started.

Delayed Start: After an automatic start-up, the unit will remain inactive for few seconds.

Active Display: The In-cab Control Box display is always active except when the unit is disconnected (no power) or when the unit is connected but has been manually switched off from the In-cab Control Box (when there is no active alarm).

Total Hourmeter: Total number of hours the unit is in operation.

Vehicle Compressor Hourmeter: Number of hours the unit has been operating on-the-road.

Low Battery Voltage Alarm: Disconnects the unit when the battery voltage is too low.

Battery voltage value display: The battery voltage value is displayed in the information menu.

Unit Control without In-cab Control Box: The unit can also be operated by the Electronic Control System without the In-cab Control Box, under conditions selected by the In-cab Control Box before it is disconnected.

Manual or Automatic defrost: It is possible to choose between manual or automatic defrost and to select the defrost time interval in auto defrost mode.

Return Air Temperature Sensor: On-screen reading of the temperature in the load compartment.

Setpoint Temperature Reading: On-Screen Setpoint Temperature Reading.

Unit Controls

    Warning
  • Risk of Injury
  • Never operate the unit unless you completely understand the controls; otherwise serious injury may occur.
In-cab Control Box — Display, Keys and Symbols
  1. Display. It is always active except when the unit is disconnected (no power) or when the unit is connected but has been manually switched off from the In-cab Control Box. It normally displays the return air temperature.

  2. ON/OFF Key. This key is used to start/stop the unit by holding the key down for at least 1 second. Single press for exit to the previous level menu.

  3. Set Key. Selects prompt screens and information screens. Single press: enter the next level menu.

  4. Up Key. Is used to increase the setpoint temperature, display values, and for menu scroll up.

  5. Down Key. Is used to reduce the setpoint temperature, display values, and for menu scroll down.

  6. Cool Symbol. The unit is cooling.

  7. Heat Symbol. The unit is heating.

  8. ºC/ºF Display. Indicates whether the on-screen temperature reading is in degrees Celsius (ºC) or degrees Fahrenheit (ºF).

  9. Alarm Symbol. Indicates that there is an alarm in the system.

  10. Defrost Symbol. Indicates the evaporator unit is in Defrost Mode.

  11. Dot Symbol (decimal). Indicates power presence, only when unit is off.

Chapter 3: Operation Instructions

3.1: Weekly Pre-Trip Inspections

The following weekly pre-trip inspection should be completed before loading the truck. Weekly inspection does not replace the regular maintenance inspections (see the scheduled maintenance inspection section); however, it is an important part of the preventive maintenance program to avoid operating problems before they occur.

Leaks. Inspect for refrigerant leaks and worn coolant lines.

Battery. Terminals should be properly tightened and show no signs of corrosion.

Belts. Check for cracks, wear, and proper belt tension.

Mounting Bracket. Ensure that bolts are fully tightened.

Electrical system. Electrical connections should be securely fastened. Wires and terminals should show no signs of corrosion, cracks or dampness.

Structural. Visually check for physical damage.

Coils. The condenser and evaporator coils should be clean and free of debris. Washing with clean water should be sufficient. The use of cleaning agents or detergents is strongly discouraged due to the possibility of degradation of the construction. If using a power washer, the nozzle pressure should not exceed 600 psi (41 bar). For the best results, spray the coil perpendicular to the face of the coil. The spray nozzle should be kept between 1 inch and 3 inches (25 to 75 millimetres) from the coil surface. If necessary to use a chemical cleaner or detergent use a cleaner that does not contain any hydrofluoric acids and is between 7 and 8 on the pH scale. Ensure dilution instructions provided by the detergent supplier are followed. In case of doubt about the compatibility of the detergent with the type of materials listed above, always ask the supplier a written confirmation of the compatibility. Should a chemical cleaner be required, it is MANDATORY that all components are thoroughly rinsed with water even if the instructions of the cleaner specify that it is a “no rinse” cleaner. Failure to comply with above mentioned guidelines will lead to a shortened life of the equipment to an indeterminable degree. The repeated transportation of meat and fish waste can cause extensive corrosion to the evaporator coils and evaporator section tubing over time due to ammonia formation and can reduce the lifespan of the coils. Appropriate additional measures should be taken to protect the coils against the aggressive corrosion that can result from transportation of such products.

Load Compartment. Inspect the interior and exterior of the truck for any damage. Any damage to the walls or insulation should be repaired.

Defrost Drains. Check the defrost drain hoses and fittings to ensure they are not blocked.

Doors. Ensure that doors and weather seals are in good condition and seal hermetically.

Sight Glass. Check that the refrigerant charge sight glass on the running unit is totally full (the cargo compartment temperature must be approximately 0ºC).

3.2: Starting the unit

Engine Operation

  1. Start the truck engine. The Dot Symbol will remain lit.

  2. Press the On/Off switch located in the In-cab Control Box for at least 1 second. The In-cab Control Box display will be activated.

  3. Check the setpoint, and adjust if needed.

Note Regular monitoring of the unit is recommended, the frequency of this monitoring will depend on the type of cargo.

3.3: Standard Display

This is the display that appears when the ON/OFF key is pressed 1 second and the unit started. It normally displays the return air temperature and the current operating mode with the appropriate symbol.

If there is an alarm, the alarm symbol will also be shown on the screen.

The example in the drawing shows: 10ºC temperature, cool mode.

3.4: Entering the setpoint temperature

The Setpoint Temperature can be quickly and easily changed.

  1. Press and release the SET key once, and the letters SP will appear on screen.

  2. Press SET key again and the current Setpoint Temperature will appear on screen.

  3. Press the UP or DOWN arrow keys to select the desired Setpoint Temperature. Each time either of these buttons is pressed and released, the Setpoint Temperature will change 1 degree. Setpoint Temperature will also change continuously if UP/ DOWN key is continuously pressed without release.

  4. Press and release the SET key to set the setpoint.

  5. Press and release ON/OFF key twice to return to the Standard Display.

    Caution
  • Service Procedure
  • If the SET key is not pressed within 20 seconds to select the new Setpoint Temperature, the unit will continue to run at the original Setpoint Temperature.

3.5: Initializing the evaporator manual defrost cycle

    Caution
  • Service Procedure
  • Before initiating a manual defrost, make sure that the unit is not already in a defrost cycle. The defrost symbol will appear in the display when the unit starts a defrost cycle.
  1. Note Defrost option is available on all the models except: C-150 / C-250 / C-350 / C-450.

    Press and release the SET key once, then press UP or DOWN and the letters dEF will appear on screen.

  2. To activate manual defrost, press the SET key 3 seconds.

  3. Press the ON/OFF key once to return to the STANDARD DISPLAY, where the DEFROST symbol will appear when the defrost cycle begins (the temperature in the cargo compartment must be less than 0ºC).

Note for manually disabling the defrost repeat the same operation.

3.6: Alarms

When the unit is not operating properly, the microprocessor records the alarm code, alerts the operator by displaying the ALARM symbol and, depending on the type of alarm, shuts the unit down.

There are two alarm categories:

Manual start

The alarm stops the unit, the dot and the ALARM symbols appears on screen.

Once the alarm condition has been rectified, the ON/OFF key must be pressed to start up again.

Press and release the SET key twice to display the current alarm code on screen. If there is more than one active alarm, all the alarm codes on the unit can be viewed in sequence by pressing and releasing the SET and ARROW keys.

Auto start

The alarm stops the unit, the ALARM symbol appears on screen and the unit starts up automatically once the alarm condition has been rectified.

Should a P1E alarm occur- return air temperature read error alarm code - appear, --- will appear on screen together with the alarm symbol, instead of the return air temperature reading.

Press and release the SET key twice to display the current alarm code on screen. If there is more than one active alarm, all the alarm codes on the unit can be viewed in sequence by pressing and releasing the SET and ARROW keys.

3.7: Alarm Code Descriptions

  Manual start
bAt Low battery voltage. Unit and battery protection system.
  Automatic start
P1E Cargo Box Return Air Temperature Reading Error (open circuit or short-circuit). Contact your Service Dealer.
E7 Communications Failure (It is not possible to read any value from the In-cab, but the unit continues to work with previous operating command). Contact your Service Dealer.

3.8: Clearing Alarm Codes

The alarm condition in the unit must first be cleared. After clearing the alarm condition, press and release once the SET key to remove existing ALARM codes. The standard display will appear once the ALARM codes have been cleared.

3.9: Viewing Information Screens

Main Manu

From the Standard Display use the SET key to open the Main Menu, then use the ARROW keys to display:

  1. Alarms (if any active)

  2. Temperature Setpoint

  3. Evaporator Manual Defrost

Press ON/OFF key once to return to Standard Display

Information Menu

From the Standard Display press the UP key for 1 second to open the Information Menu, then use the SET key to display:

  1. tSt: Display test (all icons on)

  2. reL: Software version

  3. bAt: Current battery voltage

  4. toH: The total amount of time the unit has been switched on protecting the load

  5. coH: Engine-driven compressor operating hours

Return to Main Menu by pressing ON/OFF key.

Note Each Hour counter will be displayed in hours when the counted value is <1000. When the value will be >= 1000, the hours number will be displayed alternatively between hours and thousands, into “toh” or “coh” folders. For instance, if the counted value is 12055, “055” will be displayed alternatively with “12”, where the number with 3 digits is always the number of “hours”, the number with 2 digits is always the number of “thousand of hours”.

3.10: After Start Inspection

Thermostat. Dial the thermostat setting above and below the box temperature to check thermostat operation (see Operating Modes).

Pre-Cooling. With the thermostat set at the desired temperature, allow the unit to run for one-half to one hour (longer if possible) before loading the truck. Pre-cooling will remove residual body heat and moisture from the box interior and provide a good test of the cooling system.

Defrost. When the unit has finished pre-cooling the truck interior, the evaporator temperature should have dropped below 35.6°F (2°C); initiate a manual defrost cycle. The defrost cycle should stop automatically.

Chapter 4: Pretrip Inspection (Before Loading Refrigerated Cargo)

Pretrip inspections are an important part of preventative maintenance designed to minimize on-the-road operating problems. Perform this visual pretrip inspection before loading refrigerated cargo.

Note Pretrip inspections are not intended to take the place of regular maintenance inspections.

Visual Pretrip Inspection

Visual Pretrip Inspection

1. Check that engine driven compressor belt is in good condition.
2. Check that condenser inlet and outlet areas are clean and free of debris.
3. Check that evaporator inlet and outlet areas are clean and free of debris and the drain hoses are in place and operational.
4. Check that doors and seals are in good condition. Doors should latch securely and the seals should fit tightly.
5. Check interior and exterior of cargo box for damage. Any damage to walls or insulation must be repaired.

Chapter 5: Unit Operation and Loading Procedures

This chapter describes unit operation and proper loading procedures. Thermo King refrigeration units are designed to maintain the required product load temperature during transit. Transport refrigeration units are not designed to reduce the load temperature. Follow these recommended procedures to help prevent cargo spoilage.

5.1: Unit Operation (Before Loading Refrigerated Cargo)

Start Unit: Adjust the thermostat setting to above and below the compartment temperature to check thermostat operation.

Pre-Cooling: With the thermostat set at the desired temperature, run the unit for half-an-hour to one hour (or until the desired setpoint is reached) before loading the refrigerated cargo. Pre-cooling eliminates residual heat and acts as a good test of the refrigeration system.

Defrost: When the unit has finished pre-cooling the cargo box the evaporator temperature should have dropped below 36°F (2.2°C). Initiate a manual defrost cycle with the In-Cab Controller. The defrost cycle will stop automatically.

5.2: Loading Procedure

  1. Verify the unit is turned off before opening the doors to minimize frost accumulation on the evaporator coil and heat gain in the load compartment (Unit may be running when loading the truck from a warehouse with door seals).

  2. Carefully check and record the load temperature when loading the truck. Note whether any products are out of temperature range.

  3. Products should be pre-cooled before loading. Thermo King transport refrigeration units are designed to maintain loads at the temperature at which they were loaded. Transport refrigeration units are not designed to pull hot loads down to temperature.

  4. Load the product so that there is adequate space for air circulation completely around the load. DO NOT block the evaporator inlet or outlet.

Important Product should be pre-cooled before loading. Thermo King units are designed to maintain the load at the temperature at which it is loaded. Transport refrigeration units are not designed to reduce the load temperature.
Note To minimize frost accumulation in the evaporator coil and a heat increase inside the load compartment, ensure that the unit is OFF before opening the doors.
  1. Carefully check and record the load temperature when loading the refrigerated cargo. Note whether any products are out of temperature range.

  2. Load the product to verify sufficient air space is maintained around and through the load in compartment. Airflow around the cargo must not be restricted. DO NOT block the evaporator inlet or outlet. Refer to the Air Circulation Diagram on the following page.

  3. Minimize door opening times and close door(s) in between loading to preserve box temperature.

Air Circulation Diagram

Air Circulation Diagram

1. Evaporator air outlet not blocked by cargo.
2. Sufficient air space is maintained above cargo.
3. Good air circulation around and between cargo.
4. Cargo separated from bulkhead and walls a minimum of 4.00 inch (100 mm).
5. Evaporator air inlet not blocked by cargo.

5.3: Enroute Inspections

To help prevent damage to the cargo, complete the following enroute inspection every four hours.

Inspection Procedure

  1. Verify the setpoint is correct.

  2. Check the return air temperature readings. The temperature readings should be within the desired temperature range. If the readings are not within this range, refer to ( Inspection Troubleshooting).

Inspection Troubleshooting

  1. If a return air temperature reading is not within the desired temperature range, refer to ( Inspection Troubleshooting). Correct the problem as needed.

  2. Repeat the Enroute Inspection every 30 minutes until the compartment temperature is within the desired temperature range. Stop the unit if the compartment temperature is not within desired temperature range on two consecutive 30 minute inspections, especially if the compartment temperature appears to be moving away from the setpoint.

  3. Immediately contact the nearest Thermo King Dealer.

  4. Take the necessary steps to protect and maintain proper load temperature.

Inspection Troubleshooting
Problem Cause Remedy
Return air temperature reading is not within desired temperature range of the setpoint. Unit has not had time to cool cargo to correct temperature. Refer to load log history. Look for above temperature load records, properly pre-cooled cargo compartment, length of time on road, etc. Correct as required. Continue monitoring return air temperature until reading is within desired temperature range of the setpoint.
  Unit may have a low refrigerant charge Contact nearest Thermo King dealer, or call the Thermo King Cold Line for referral.
  Unit is in defrost or has just completed a defrost cycle. Monitor return air temperature after defrost cycle is completed to see if temperature returns to desired temperature range of the setpoint.
Note Temperature will increase slightly during defrost cycle.
  Evaporator is plugged with frost. Initiate a manual defrost cycle. Defrost cycle will automatically terminate when complete. Continue monitoring return air temperature until reading is within desired temperature range of the setpoint.
Return air temperature reading is not within desired temperature range of the setpoint. Improper air circulation in the cargo compartment. Inspect unit and cargo compartment to determine if evaporator fans are working and properly circulating the air. Poor air circulation may be due to improper loading of the cargo or shifting of the load. Correct as required. Continue monitoring return air temperature until problem is corrected.
    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Turn the unit On/Off switch Off before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King unit.
  The unit did not start automatically. Contact nearest Thermo King dealer, or call the Thermo King Cold Line for referral.
  Air leaks in cargo box. Inspect cargo box for air leaks such as doors that are not fully closed or bad/missing door seals. Repair as necessary.

Chapter 6: Specifications

6.1: Electrical System

B-100
Fuses
  12 Vdc 24 Vdc
Fuse 1: Main Fuse 100 amps 60 amps
Fuse 3: Evaporator Fan Motor (EFM1) 15 amps 10 amps
Fuse 5: Roadside (Engine) Compressor Clutch (CCL1), Liquid Injection Switch (LIS), Liquid Injection Valve (LIV), EVAP1 Defrost Hot Gas Solenoid Valve (PS1), Compressor Motor Contactor (CMC), Heat Pilot Solenoid (PS5) 20 amps 10 amps
Fuse 6: Drain Heaters (H3 and H4) 2 amps 2 amps
Fuse 7: Transformer AC Power Supply 2 10 amps 10 amps
Fuse 8: Heater 72 °C (161.5 °F) 72 °C (161.5 °F)
Fuse 9: Heater 72 °C (161.5 °F) 72 °C (161.5 °F)
Fuse 10: Heater 72 °C (161.5 °F) 72 °C (161.5 °F)
Fuse 11: Heater 72 °C (161.5 °F) 72 °C (161.5 °F)
Fuse 14: Vehicle Ignition Switch 5 amps 5 amps
Fuse 20: Transformer AC Power Supply (located at compressor motor contactor in condenser section) 4 amps 4 amps
Fuse 16: Thermal Fuse 10 A 84ºC 10 A 84ºC
Fuse 17: Thermal Fuse 10 A 84ºC 10 A 84ºC
Fuse 25: Battery Fuse 5 amps 5 amps
Fuse 30: Condenser Fan Motor (CFM) (located in CF1 wire near terminal strip in condenser section) 16 amps 10 amps
Fuse 31: Fuse - Heater 1 20 amps 20 amps
Fuse 32: Fuse - Heater 2 20 amps 20 amps
Fuse 33: Fuse - Heater 3 20 amps 20 amps
Fuse 34: Fuse - Heater 4 20 amps 20 amps
       
Condenser Fan Motor
Voltage 13 Vdc 26 Vdc
Full Load Current 10 Amps 4.7 Amps
Power Rating 130 W 122 W
RPM with Full Load 2,800 2,800
       
Evaporator Fan Motors (Each)
Voltage 13 Vdc 26 Vdc
Full Load Current 7.5 Amps 4 Amps
Power Rating 97.5 W 104 W
RPM with Full Load 2,800 2,800
       
AC Electrical Power Supply Motor
Voltage/Phase/Frequency 230/1/50
Output Power 0.75 kW
Nominal Current Drawn 5.2 amps
OL Relay Adjustment

10 / 20 Units - 5.2 Amps

30 / 50 Units - 10.5 Amps

       
DC Electrical Power Supply Motor
Voltage 12 Vdc 24 Vdc
Output Power 600 W 600 W
Nominal Current Drawn 65 amps 30 amps
       
Coil for Hot Gas Solenoid (PS1)
Voltage 12 Vdc 24 Vdc
Current 2.3 amps 1.3
Resistance 5.2 ohms 20 ohms
       
Coil for Liquid Injection Solenoid (LIS) – MAX Only
Voltage 12 Vdc
Current 1.2 amps
Resistance 10.0 ohms
       
Coil for Heat Pilot Solenoid (PS5) - Truck Engine Coolant Heat Option Only
Voltage 12 Vdc
Current 1.5 amps
Resistance 8.0 ohms
       
Drain Line Heaters (Each) - MAX Only
Voltage 12 Vdc
Current 0.9 amps ± 5% at 68 F (20 C)
Resistance 13.8 ohms ± 5% at 68 F (20 C)
       
Battery Relay (BATR)
Type Single Pole Single Throw (SPST)
Contacts   Terminals 30 to 87 Normally Open (NO)
Coil Resistance   Terminals 85 to 86 90 ohms
       
Electric Standby Power Relay (STDR)
Type     Single Pole Single Throw (SPST)
Contacts   Terminals 30 to 87 Normally Open (NO)
Coil Resistance   Terminals 85 to 86 90 ohms
       
Start Key Relay (C1R)
Type     Single Pole Double Throw (SPDT)
Contacts  

Terminals 30 to 87

Terminals 30 to 87A

Normally Open (NO)

Normally Closwe (NC)

Coil Resistance   Terminals 85 to 86 90 ohms
       
Capacitors
Starting Capacitor (CS) – all voltages 250–300 μF
Running Capacitor (CR) 40 μF
       
Start Relay
230/1/50

Start Relay – 1E39543H01

Type: Current

Pick-up - 9.1 Amps

Drop-out: 7.5 Amps

230/1/60

Start Relay – 1E55777G01

Type: Voltage Release

Range: 95-254 VAC

115/1/60

Start Relay – 1E55777G01

Type: Voltage Release

Range: 95-254 VAC

       
Compressor Motor Contactor (CMC)
Contacts Normally Open
Coil Voltage 12 Vdc
Coil Current 0.25 amps
Coil Resistance 48 ohms
       
Transformer
Power 500 VA
Frequency 50/60 Hz
Primary Inputs 115-208-230 Vac
Secondary Nominal Voltage 11.7 Vac (21.4 Amps)
 
AC / DC Power Supply Converter - 330 W  
Power 320W
Frequency 50/60 Hz
Input

Voltage Range: 85~264 VAC / 120~370 VDC

Frequency Range: 47~63 Hz

Secondary Nominal Voltage and Specs   12V 24V
Rated Current 27 amps 14 amps
Current Range 0~27 amps 0~14 amps
Rated Power 324W 336W
Ripple and Noise (max) 120mVp-p 150mVp-p
Voltage Adj. Range 10.2~13.8V 21.6~28.8V
Voltage Tolerance 1.0% 1.0%
Line Regulator 0.3% 0.2%
Load Regulation 0.5% 0.5%
Input 27 amps 14 amps
  12 Vdc
Fuses
E-200
Fuse 1: Main Fuse 150 amps
Fuse 3: Evaporator Fan 15 amps
Fuse 4: Evaporator second Fan 15 amps
Fuse 5: Distribution fuse 20 amps
Fuse 6: Drain Heaters 2 amps
Fuse 9: Evaporator Fan second compartment 15 amps
Fuse 11: Drain Heaters second compartment 2 amps
Fuse 14: ACC1 Ignition Fuse 5 amps
Fuse 25: Vehicle Battery 5 amps
Fuse 63: TK Battery 1 Battery 150 amps
Fuse 83: 2 Battery 80 amps
Fuse 71: SCM Fuse 60 amps
Fuse 72: SCM Fuse 60 amps
Fuse 8: BMS Fuses   10 amps
Fuse 84:  
 
Condenser Fan Motor
Voltage 13 Vdc
Full Load Current 10 Amps
Power Rating 130 W
RPM with Full Load 2,800
     
Condenser Fan Motor
Voltage 13 Vdc
Full Load Current 11 Amps
Power Rating 145 W
RPM with Full Load 2,670
     
Evaporator Fan Motors (Each)
Voltage 13 Vdc
Full Load Current 7.5 Amps
Power Rating 97.5 W
RPM with Full Load 2,800
     
Compressor driver module
Battery Input 11.5 to 14.5 VDC
Isolated, balanced three-phase output: 240 VAC Maximum
30–300 Hz (speed controlled)
Electrical output power: 1150 W continuous, 1400 W for 30 sec
       
Smart Charger module
Bidirectional battery Charger / Discharger  
Voltage 13 Vdc
Maximum Charge Current 40 A dc
Maximum Discharge Current 40 A dc
  12 Vdc
Fuses
E-100e and E-200e Series
Fuse 1: Main Fuse for E-100e 100 amps
Fuse 1: Main Fuse for E-200e 150 amps
Fuse 3: Evaporator Fan 15 amps
Fuse 4: Evaporator second Fan 15 amps
Fuse 5: Distribution fuse 20 amps
Fuse 6: Drain Heaters 2 amps
Fuse 8: Solenoids 20 amps
Fuse 9: Evaporator Fan second compartment 15 amps
Fuse 10 (DSR 3.1) 15 amps
Fuse 10 (Fuse Holder): DC BUS Presence 5 amps
Fuse 11 (DSR 3.1) 2 amps
Fuse 11 (Fuse Holder): Battery Power Presence 5 amps
Fuse 12 15 amps
Fuse 13 (Fuse Holder) 5 Amps
Fuse 14: ACC1 Ignition Fuse 5 amps
Fuse 25: Vehicle Battery 5 amps
Fuse 89 5 amps
Fuse 90 5 amps
Condenser Fan Motor — E-100e
Voltage 13 Vdc
Max. Load Current 9.2 Amps
Power Rating 119.60 W
Max. Airflow 1360 m3/h
     
Condenser Fan Motor — E-200e
Voltage 13 Vdc
Max. Load Current 10.8 Amps
Power Rating 140.4 W
Max. Airflow 1505 m3/h
 
Evaporator Fan Motors (Each)
Voltage 13 Vdc
Max. Load Current 7.9 Amps
Power Rating 102.7 W
Max. Airflow 1166 m3/h

V-Series
  12 Vdc 24 Vdc
Fuses
Common Fuses
Fuse 3: Evaporator Fan Motor (EFM1) 15 amps 10 amps
Fuse 4: Evaporator Fan Motor (EFM2) 15 amps 10 amps
Fuse 5: Roadside (Engine) Compressor Clutch (CCL1), Liquid Injection Switch (LIS), Liquid Injection Valve (LIV), EVAP1 Defrost Hot Gas Solenoid Valve (PS1), Compressor Motor Contactor (CMC), Heat Pilot Solenoid (PS5) 20 amps 10 amps
Fuse 14: Vehicle Ignition Switch 5 amps 5 amps
Fuse 30: Condenser Fan Motor (CFM) (located in CF1 wire near terminal strip in condenser section) 16 amps 10 amps
V-100/V-200s
Fuse 6: Condenser Fan 1/2 2 amps 2 amps
Fuse 21: Battery Power Supply (located in 2 wire near battery) 30 amps 30 amps
V-200/V-300 and Spectrum
Fuse 6: Condenser Fan 1/2 2 amps 2 amps
Fuse 8: (Spectrum Only) EVAP2 Liquid Solenoid Valve (PS2), EVAP1 Liquid Solenoid Valve (PS3), EVAP2 Defrost Hot Gas Solenoid Valve (PS4), Drain Heaters 3 and 4 (HT3, HT4) 20 amps 10 amps
Fuse 9: (Spectrum Only) Evaporator Fan 3 15 amps 10 amps
Fuse 10: (Spectrum Only) Evaporator Fan 4 15 amps 10 amps
Fuse 11: Drain Heaters (H1 and H2) 2 amps 2 amps
Fuse 20: Transformer AC Power Supply (located at compressor motor contactor in condenser section) 4 amps 4 amps
Fuse 21: Battery Power Supply (located in 2 wire near battery) 40 amps 40 amps
V-500/V-600 and Spectrum
Fuse 6: Condenser Fan 1/2 10 amps 7.5 amps
Fuse 8: (Spectrum Only) EVAP2 Liquid Solenoid Valve (PS2), EVAP1 Liquid Solenoid Valve (PS3), EVAP2 Defrost Hot Gas Solenoid Valve (PS4), Drain Heaters 3 and 4 (HT3, HT4) 20 amps 10 amps
Fuse 9: (Spectrum Only) Evaporator Fan 3 15 amps 10 amps
Fuse 10: (Spectrum Only) Evaporator Fan 4 15 amps 10 amps
Fuse 11: Drain Heaters (H1 and H2) 2 amps 2 amps
Fuse 17: Drain Heaters (H3 and H4) 2 amps 2 amps
Fuse 20: Transformer AC Power Supply (located at compressor motor contactor in condenser section) 4 amps 4 amps
Fuse 21: Battery Power Supply (located in 2 wire near battery) 50 amps (Single Temp) 60 amps (Multi-Temp)
Fuse 31: Condenser Fan Motor 2 (CFM2) (located in CF2 wire near terminal strip in condenser section) 16 amps 10 amps
V-800 and Spectrum
Fuse 6: Drain Heaters 1/2 2 amps 2 amps
Fuse 8: (Spectrum Only) EVAP2 Liquid Solenoid Valve (PS2), EVAP1 Liquid Solenoid Valve (PS3), EVAP2 Defrost Hot Gas Solenoid Valve (PS4), Drain Heaters 3 and 4 (HT3, HT4) 20 amps 10 amps
Fuse 9: (Spectrum Only) Evaporator Fan 3 15 amps 10 amps
Fuse 10: (Spectrum Only) Evaporator Fan 4 15 amps 10 amps*
Fuse 11: Drain Heaters (H3 and H4) 2 amps 2 amps
Fuse 15: TracKing 5 amps 5 amps
Fuse 16: TracKing 5 amps 5 amps
Fuse 17: TracKing 5 amps 5 amps
Fuse 20: Transformer AC Power Supply (located at compressor motor contactor in condenser section) 2 x 2 amps 2 x 2 amps
Fuse 21: Battery Power Supply (located in 2 wire near battery) 2 x 30 amps 2 x 30 amps
Fuse 31: Condenser Fan Motor 2 (CFM2) (located in CF2 wire near terminal strip in condenser section) 16 amps 10 amps
Note * 15 A in Spectrum Versions with Double Evaporator Fan 4
Condenser Fan Motor (All except V-800)
Voltage 13 Vdc 26 Vdc
Full Load Current 10 Amps 4.7 Amps
Power Rating 130 W 122 W
RPM with Full Load 2,800 2,800
       
Condenser Fan Motor (V-800)
Voltage 13 Vdc 26 Vdc
Full Load Current 11 Amps 9 Amps
Power Rating 145 W 230 W
RPM with Full Load 2,670 2,900
       
Evaporator Fan Motors (Each)
Voltage 13 Vdc 26 Vdc
Full Load Current 7.5 Amps 4 Amps
Power Rating 97.5 W 104 W
RPM with Full Load 2,800 2,800
       
Coil for Hot Gas Solenoid (PS1, PS2, PS3, PS4)
Voltage 12 Vdc 24 Vdc
Current 2.3 amps 1.3 amps
Resistance 5.2 ohms 20 ohms
       
Coil for Liquid Injection Solenoid (LIS) – MAX Only
Voltage 12 Vdc
Current 1.2 amps
Resistance 10.0 ohms
       
Coil for Heat Pilot Solenoid (PS5) - Truck Engine Coolant Heat Option Only
Voltage 12 Vdc
Current 1.5 amps
Resistance 8.0 ohms
       
Drain Line Heaters (Each) - MAX Only
Voltage 12 Vdc
Current 0.9 amps ± 5% at 68 F (20 C)
Resistance 13.8 ohms ± 5% at 68 F (20 C)
       
Battery Relay (BATR)
Type Single Pole Single Throw (SPST)
Contacts   Terminals 30 to 87 Normally Open (NO)
Coil Resistance   Terminals 85 to 86 90 ohms
       
Electric Standby Power Relay (STDR)
Type     Single Pole Single Throw (SPST)
Contacts   Terminals 30 to 87 Normally Open (NO)
Coil Resistance   Terminals 85 to 86 90 ohms
       
Start Key Relay (C1R)
Type     Single Pole Double Throw (SPDT)
Contacts  

Terminals 30 to 87

Terminals 30 to 87A

Normally Open (NO)

Normally Closwe (NC)

Coil Resistance   Terminals 85 to 86 90 ohms
       
Capacitors
Starting Capacitor (CS) – all voltages 250–300 μF
Running Capacitor (CR) 40 μF
       
Compressor Motor Contactor (CMC)
Contacts Normally Open
Coil Voltage 12 Vdc
Coil Current 0.25 amps
Coil Resistance 48 ohms
       
Transformer
Power 500 VA
Frequency 50/60 Hz
Primary Inputs 115-208-230 Vac
Secondary Nominal Voltage 11.7 Vac (21.4 Amps)

Fuses
V-800/ V-1000 and Spectrum 12 Vdc 24 Vdc
Fuse 1: Condenser Fan Motor (CFM1) 15 amps 10 amps
Fuse 2: Condenser Fan Motor (CFM2) 15 amps 10 amps
Fuse 3: Evaporator Fan 1 15 amps 10 amps
Fuse 4: Evaporator Fan 2 15 amps 10 amps
Fuse 5: PS1, PS7, CMC, LIV,PS5, RCV, CCL 20 amps 10 amps
Fuse 6: Drain Heaters 1/2 2 amps 2 amps
Fuse 8: (Spectrum Only) EVAP2 Liquid Solenoid Valve (PS2), EVAP1 Liquid Solenoid Valve (PS3), EVAP2 Defrost Hot Gas Solenoid Valve (PS4), Drain Heaters 3 and 4 (HT3, HT4) 20 amps 10 amps
Fuse 9: (Spectrum Only) Evaporator Fan 3 15 amps 10 amps
Fuse 10: (Spectrum Only) Evaporator Fan 4 15 amps 10 amps*
Fuse 11: Drain Heaters (H3 and H4) 2 amps 2 amps
Fuse 14: Ignition 5 amps 5 amps
Fuse 17: TracKing 5 amps 5 amps
Fuse 20: Transformer AC Power Supply

5 amps

(time delay fuse)

5 amps

(time delay fuse)

Fuse 21: Battery Power Supply 100 amps 60 amps
Fuse 41: Evaporator Fan 5 15 amps 10 amps
Fuse 42: Evaporator Fan 6 15 amps 10 amps
       
Condenser Fan Motor
Voltage 13 Vdc 26 Vdc
Full Load Current 11 amps 4.7 amps
Power Rating 145 W 288 W
RPM with Full Load 2,570 3,400
Control voltage range 1-10 Vdc 6.5-10 Vdc
       
Evaporator Fan Motors (Each)
Voltage 13 Vdc 26 Vdc
Full Load Current 7.5 amps 4 amps
Power Rating 97.5 W 104 W
RPM with Full Load 2,800 2,800
       
AC Electrical Power Supply Motor
Voltage/Phase/Frequency 230/1/50, 230/3/60, 400/3/50
Output Power 0.75 kW
Nominal Current Drawn 5.2 amps
OL Relay Adjustment

10 / 20 Units - 5.2 amps

30 / 50 Units - 10.5 amps

       
DC Electrical Power Supply Motor
Voltage 12 Vdc 24 Vdc
Output Power 600 W 600 W
Nominal Current Drawn 65 amps 30 amps
       
Coil for Hot Gas Solenoid (PS1, PS2, PS3, PS4)
Voltage 12 Vdc 24 Vdc
Current 14 W 14 W
       
Coil for Liquid Injection Solenoid (LIS) – MAX Only
Voltage 12 Vdc 24 Vdc
Current 14 W 14 W
       
Coil for Heat Pilot Solenoid (PS5) - Truck Engine Coolant Heat Option Only
Voltage 12 Vdc 24 Vdc
Current 21 amps 21 W
       
Drain Line Heaters (Each) - MAX Only
Voltage 12 Vdc 24 Vdc
Resistance 2.095 ohm 7.5 ohm
       
Battery Relay (BATR)
Type Single Pole Single Throw (SPST)
Contacts   Terminals 30 to 87 Normally Open (NO)
Coil Resistance   Terminals 85 to 86 90 ohms
       
Electric Standby Power Relay (STDR)
Type     Single Pole Single Throw (SPST)
Contacts   Terminals 30 to 87
Terminals 30 to 87A
Normally Open (NO)
Normally Close (NC)
Coil Resistance   Terminals 85 to 86 90 ohms
       
Compressor Motor Contactor (CMC)
Contacts Normally Open Normally Open
Coil Voltage 12 Vdc 24 Vdc
Coil Current 0.25 amps 5.4 Watt
       
Transformer
Power 1100 VA
Frequency 50/60 Hz
Primary Inputs 230-400 Vac
Secondary Nominal Voltage 2 windings:
11.7 Vac (47 amps)
11.7 Vac (47 amps)

AC Electric Compressor Motors and Overload Relays
Voltage/Phase/Frequency Horsepower Kilowatts RPM Full Load (amps) Overload Relay Setting (amps)
V-100/V-200s
230/1/50 2.0 1.5 1750 5.4 5.5
V-200/V-300
230/1/50 2.0 1.5 1750 8.6 8.6
230/1/60 2.0 1.5 1750 9 9
230/3/60 2.4 1.8 1750 6.9 6.9
400/3/50 2.4 1.8 1750 4 4
400/3/60 2.4 1.8 1750 4 4
V-500/V-600
115/1/60 1.5 1.1 1710 14 14
208/1/60 2.0 1.5 1740 9.5 9.5
230/1/60 2.0 1.5 1750 9 9
208/3/60 2.4 1.8 1730 7.2 7.2
230/3/60 2.4 1.8 1750 6.9 7
V-800 (ES600+2xES150)
230/3/50 2.4 1.8 1750 66.6/9.6 amps 9.6
230/3/60 2.4 1.8 1750 19.9/11.5 amps 11.5
V-800
230/3/50 3 2.3 1450 57/16.6 amps 18
400/3/50 3 2.3 1450 32.9/9.6 amps 14
230/3/60 3 2.3 1740 68.4/19.9 amps 18
400/3/60 3 2.3 1740 39.5/11.5 amps 14
V-1000
230/3/50 5 3.7 1450 22/109 amps 24
400/3/50 5 3.7 1450 12.7/63.1 amps 16
230/3/60 5 3.7 1740 26.5/121 amps 24
400/3/60 5 3.7 1740 15.3/70.1 amps 16

Fuses
C-150, C-250, C-350, C-450, C-550, C-650, C-750 12 Vdc 24 Vdc
Fuse 1 3 amps 3 amps
Fuse 2 15 amps 7.5 amps
Fuse 3 15 amps 7.5 amps
Fuse 4 15 amps 7.5 amps
Fuse 5 15 amps 7.5 amps
Fuse 14 5 amps 5 amps
Fuse 21 40 amps 30 amps
Fuse 30 2 amps 2 amps
       
Condenser Fan Motor
Voltage 13 Vdc 26 Vdc
Full Load Current 9.2 amps 4.1 amps
Power Rating 100 W 100 W
RPM with Full Load 2,800 2,800
Control voltage range ?? Vdc ?? Vdc
       
Evaporator Fan Motors (Each)
Voltage 13 Vdc 26 Vdc
Full Load Current 6.2 amps 3.7 amps
Power Rating 100 W 100 W
RPM with Full Load 2,800 2,800
Coil for Hot Gas Solenoid (PS1, PS2, PS3, PS4)
Voltage 12 Vdc 24 Vdc
Current 14 W 14 W
       
Coil for Liquid Injection Solenoid (LIS) – MAX Only
Voltage 12 Vdc 24 Vdc
Current 14 W 14 W
       
Drain Line Heaters (Each) - MAX Only
Voltage 12 Vdc 24 Vdc
Resistance 2.095 ohm 7.5 ohm

6.2: Refrigeration System Specifications

Note Units from January 2016 are available with R-404A, R-452A or R-134A Refrigerants. All of which comply with F-Gas legislation revision 2014 (Regulation (EC) No 517/2014).
Note Units are available with R-404A, R-452A or R-134A Refrigerants. All of which comply with F-Gas legislation revision 2014 (Regulation (EC) No 517/2014).
Note Units are available with R-404A, R-452A or R-134A Refrigerants. All of which comply with F-Gas legislation revision 2014 (Regulation (EC) No 517/2014).
Refrigerant GWP
R-404A 3922
R-452A 2140
R-134A 1430
    Caution
  • Service Procedure
  • Fluorinated Refrigerant gases should not be ventilated to atmosphere. Take note of the refrigerant type (label on outside of unit) and do not cross-contaminate.
Refer to the Vehicle Powered Truck Installation Standards and Procedures TK 61588 (Section 10 – System Evacuation Procedures) and Section 12 – System Charging Procedures) for service information about evacuating and charging the refrigeration system.
Note *Final refrigerant charge will vary based on each unique installation

All refrigeration service requirements, major and minor, should be handled by a Thermo King dealer.

R-134a Refrigeration System B-100/B-100 ECO NEED 404 and 452 INFO ???????????
Refrigerant Charge:

B-100

B-100 ECO

??????

??????

B-100 50 MAX

1.87 lb (0.85 kg) R-134a

1.87 lb (0.85 kg) R-134a

X.XX lb (0.XX kg) R-404A

X.XX lb (0.XX kg) R-452A

2.09 lbs (0.95 kg) R-404A

Defrost Method   Hot Gas
Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

R-134a Refrigeration System E-Series
Refrigerant Charge:

E-200 20

1.3kg (2.8lb) (including 1.5m (60") hoses supplied as standard) R134a

Defrost Method   Hot Gas
Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

R-452A Refrigeration System E-Series MAX
Refrigerant Charge:

E-200 MAX 50

E-200 MAX 50 Spectrum

1.3kg (2.8lb) (including 1.5(60") hoses supplied as standard) R452A/R404A

1.6kg (3.5lb) (including 6m(237") hoses supplied as standard) R452A/R404A

    Important
  1. For each additional meter (39") of hose extension, add 80g (0.17lb) of refrigerant.

  2. It is a good idea to utilise the WINTRAC tool to set compressor speed at an intermediate level (for example - 60Hz) during refrigeration charge. If the unit is charged with the compressor at full speed, overcurrent protection may trip.

  3. DO NOT overcharge the system. Checking the sight glass is free from bubbles may be misleading if the evaporator box is warm. Decrease the temperature of the box to 5ºC or below before checking the sight glass.

Defrost Method   Hot Gas
Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LISW):   Refer to (Liquid Injection System) for operation description
Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

SPR (Suction Pressure Regulator) Valve Setting 40 psig (275 kPa gauge)
DPR (Discharge Pressure Regulator) Valve Setting Factory setting 87 ± 2 psig (6 ± 0.14 bar)
Important Do not exceed 145 psi (10 bar) to avoid tripping the compressor motor current protection.
R-134a Refrigeration System
Refrigerant Charge:

E-100e ECO

0.8 kg (1.7 lb) (including 1.5m (60") hoses supplied as standard) R134a

E-100e

0.9 kg (1.9 lb) (including 1.5 (60") hoses supplied as standard) R134a

E-200e

1.2 kg (2.6 lb) (including 6m (237") hoses supplied as standard) R134a

Defrost Method:   Reverse Cycle
Defrost Termination Sensor

Opens

Closes

Defined in Parameter Map
Low Pressure Cutout Switch (LPCO):

Opens

Closes

-0.27 ± 0.2 Bar

-0.50 ± 0.3 Bar

R-452A/R-404A Refrigeration System
Refrigerant Charge

E-100e MAX

0.9 kg (1.9 lb) (including 1.5 (60") hoses supplied as standard) R-452A/R-404A

E-200e MAX

1.2 kg (2.6 lb) (including 6m (237") hoses supplied as standard) R-452A/R-404A

E-200e Max Spectrum

1.5 kg (3.3 lb) (including 6m (237") hoses supplied as standard) R-452A/R-404A

    Important
  1. For each additional meter (39") of hose extension, add 80g (0.17lb) of refrigerant.

  2. It is a good idea to utilise the WINTRAC tool to set compressor speed at an intermediate level (for example - 60Hz) during refrigeration charge. If the unit is charged with the compressor at full speed, overcurrent protection may trip.

  3. DO NOT overcharge the system. Checking the sight glass is free from bubbles may be misleading if the evaporator box is warm. Decrease the temperature of the box to 5ºC or below before checking the sight glass.

Defrost Method   Reverse Cycle
Defrost Termination Sensor

Opens

Closes

Defined in Parameter Map
Liquid Injection Switch (LISW)   Refer to (Liquid Injection System) for operation description
Low Pressure Cutout Switch (LPCO)

Opens

Closes

-0.27 ± 0.2 Bar

-0.50 ± 0.3 Bar

R-134a Refrigeration System V-Series
Refrigerant Charge:    
 

V-100 10

V-100 20

1.37 lb (0.62 kg) R-134a

2.20 lb (1.0 kg) R-134a

 

V-200 10

V-200 20

2.20 lb (1.0 kg) R-134a

2.43 lb (1.1 kg) R-134a

 

V-300 10

V-300 20

2.43 lb (1.1 kg) R-134a

2.87 lb (1.3 kg) R-134a

 

V-500 10

V-500 20

4.85 lb (2.2 kg) R-134a

4.85 lb (2.2 kg) R-134a

 

V-800 10

V-800 20

10.03 lb (4.55 kg) R-134a

10.70 lb (4.85 kg) R-134a

 

V-800 10

V-800 20

11.24 lb (5.1 kg) R-134a

11.90 lb (5.4 kg) R-134a

 

V-1000 10

V-1000 20

11.46 lb (5.2 kg) R-134a

12.12 lb (5.5 kg) R-134a

Defrost Method   Hot Gas
Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

High Pressure Cutout Switch (HPCO)

Opens

Closes

2,068 ± 69 kPa (300 ± 10 psi)

1,379 ± 69 kPa (200 ± 10 psi)

CFPS (condenser fan pressure switch)

Opens

Closes

896 ± 69 kPa (130 ± 10 psi)

1,241 ± 69 kPa (180 ± 10 psi)

CFSC (condenser fan speed control) switch

Opens

Closes

1517 ± 48 kPa (220 ± 7 psi)

1,241 ± 48 kPa (180 ± 7 psi)

CSPS (condenser pressure control switch)

Opens

Closes

1,724 + 138 kPa/-0 kPa (250 + 20 psi/-0 kPa)

1,379 ± 138 kPa (200 ± 20 psi)

EFPS (evaporator fan pressure switch) (V-800 heat mode only)

Opens

Closes

620 ± 69 kPa (90 ± 10 psi)

758 ± 69 kPa (110 ± 10 psi)

EFSC (evaporator fan speed control logic switch) (V-800 heat mode only)

Opens

Closes

1,206 + 138 kPa/-0 kPa (175 + 20 psi/-0 kPa)

931 + 138 kPa/-0 kPa (135 + 20 psi/-0 kPa)

R-404A/R-452A Refrigeration System V-Series MAX
Refrigerant Charge:    
 

V-100 MAX 10

V-100 MAX 20

V-100 MAX 30

V-100 MAX 50

V-200s MAX 20

V-200s MAX 50

1.37 lb (0.62 kg) R-452A

2.20 lb (1.0 kg) R-452A

1.37 lb (0.62 kg) R-452A

2.20 lb (1.0 kg) R-452A

.66 lb (1.2 kg) R-452A

.66 lb (1.2 kg) R-452A

 

V-200 MAX 10/30

V-200 MAX 20/50

V-200 MAX 30 Spectrum

V-200 MAX 50 Spectrum

V-300 MAX 10/30

V-300 MAX 20/50

V-300 MAX 50 Spectrum (ES150+ES150)

V-300 MAX 50 Spectrum (ES100+ES150)

V-300 MAX 50 Spectrum (ES100+ES200)

2.20 lb (1.0 kg) R-452A

2.66 lb (1.2 kg) R-452A

3.00 lb (1.35 kg) R-452A

3.00 lb (1.35 kg) R-452A

1.37 lb (0.62 kg) R-452A

2.20 lb (1.0 kg) R-452A

4.10 lb (1.85 kg) R-452A

4.10 lb (1.85 kg) R-452A

4.10 lb (1.85 kg) R-452A

 

V-500 MAX 10

V-500 MAX 20/30

V-500 MAX 50

V-500 MAX Spectrum 10

V-500 MAX Spectrum 20/30

V-500 MAX Spectrum 50

V-600 MAX 10

V-600 MAX 20/30

V-600 MAX 50

4.63 lb (2.1 kg) R-452A

4.85 lb ( 2.2 kg) R-452A

5.07 lb (2.3 kg) R-452A

5.07 lb (2.3 kg) R-452A

5.29 lb (2.4 kg) R-452A

5.51 lb (2.5 kg) R-452A

4.85 lb (2.2 kg) R-452A

5.07 lb (2.3 kg) R-452A

5.29 lb (2.4 kg) R-452A

 

V-800 MAX 10/30

V-800 MAX 20/50

V-800 MAX 30 Spectrum (ES400+ES400)

V-800 MAX 50 Spectrum (ES600+ES150)

V-800 MAX 50 Spectrum (ES600+2xES150)

10.36 lb (4.7 kg) R-452A

11.02 lb (5.0 kg) R-452A

11.46 lb (5.2 kg) R-452A

11.02 lb (5.0 kg) R-452A

11.35 lb (5.15 kg) R-452A

 

V-800 MAX 10

V-800 MAX 20

V-800 MAX 30

V-800 MAX 50

11.68 lb (5.3 kg) R-452A

12.34 lb (5.6 kg) R-452A

12.78 lb (5.8 kg) R-452A

13.44 lb (6.1 kg) R-452A

 

V-1000 MAX 10

V-1000 MAX 20

V-1000 MAX 30

V-1000 MAX 50

11.90 lb (5.4 kg) R-452A

12.56 lb (5.7 kg) R-452A

13.00 lb (5.9 kg) R-452A

13.66 lb (6.2 kg) R-452A

 

V-800 MAX 30 Spectrum (ES400+ES400)

V-800 MAX 30 Spectrum (ES600+ES150)

V-800 MAX 30 Spectrum (ES600+2xES150)

V-800 MAX 50 Spectrum (ES400+ES400)

V-800 MAX 50 Spectrum (ES600+ES150)

V-800 MAX 50 Spectrum (ES600+2xES150)

12.78 lb (5.8 kg) R-452A

12.78 lb (5.8 kg) R-452A

12.78 lb (5.8 kg) R-452A

13.44 lb (6.1 kg) R-452A

13.44 lb (6.1 kg) R-452A

13.44 lb (6.1 kg) R-452A

 

V-1000 MAX SPECTRUM 30 (ES600+ES600)

V-1000 MAX SPECTRUM 30 (ES600+ES150)

V-1000 MAX SPECTRUM 30 (ES600+2xES150)

V-1000 MAX SPECTRUM 30 (ES800+ES300)

V-1000 MAX SPECTRUM 50 (ES600+ES600)

V-1000 MAX SPECTRUM 50 (ES600+ES150)

V-1000 MAX SPECTRUM 50 (ES600+2xES150)

V-1000 MAX SPECTRUM 50 (ES800+ES300)

13.00 lb (5.9 kg) R-452A

13.00 lb (5.9 kg) R-452A

13.00 lb (5.9 kg) R-452A

13.00 lb (5.9 kg) R-452A

13.66 lb (6.2 kg) R-452A

13.66 lb (6.2 kg) R-452A

13.66 lb (6.2 kg) R-452A

13.66 lb (6.2 kg) R-452A

Defrost Method*   Hot Gas
Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LIS):

Opens

Closes

200 ± 5 F (93 ± 3 C)

230 ± 5 F (110 ± 3 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

High Pressure Cutout Switch (HPCO)

Opens

Closes

3,100 ± 69 kPa (450 ± 10 psi)

2,585 ± 69 kPa (375 ± 10 psi)

CFPS (condenser fan pressure switch)

Opens

Closes

896 ± 69 kPa (130 ± 10 psi)

1,241 ± 69 kPa (180 ± 10 psi)

CFSC (condenser fan speed control) switch

Opens

Closes

2,068 + 138 kPa/-0 kPa (300 + 20 psi/-0 kPa)

1,379 ± 138 kPa (200 ± 20 psi)

CSPS (condenser pressure control switch)

Opens

Closes

2,068 + 138 kPa/-0 kPa (300 + 20 psi/-0 kPa)

1,586 + 138 kPa/-0 kPa (230 + 20 psi/-0 kPa)

EFPS (evaporator fan pressure switch) (V-800 heat mode only)

Opens

Closes

620 ± 69 kPa (90 ± 10 psi)

758 ± 69 kPa (110 ± 10 psi)

EFSC (evaporator fan speed control logic switch) (V-800 heat mode only)

Opens

Closes

1,206 + 138 kPa/-0 kPa (175 + 20 psi/-0 kPa)

931 + 138 kPa/-0 kPa (135 + 20 psi/-0 kPa)

CPR (Compressor Pressure Regulator) Valve Setting - Model 30 and 50 Only 24 ± 2 psig (165 ± 14 kPa)
SPR (Electric Standby Suction Pressure Regulator) Valve Setting - Model 20 MAX Only 24 ± 2 psig (165 ± 14 kPa)
Note *Reverse Cycle Defrost on V-800 MAX 30/50
R-134a Refrigeration System V-220/V-320
Refrigerant Charge:

V-220 - Model 10

V-220 - Model 20

V-320 - Model 10

V-320 - Model 20

2.8 lb (1.27 kg) R-134a

2.8 lb (1.27 kg) R-134a

3.3 lb (1.50 kg) R-134a

3.4 lb (1.54 kg) R-134a

Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

R-404A / R-452A Refrigeration System V-220/V-320 MAX

Important MAX units built Before December 12, 2022 were originally built using R-404A refrigerant.

MAX units built on and after December 12, 2022 are equipped with R-452A refrigerant.

See Service Bulletin SB874 Transition to R–452A Refrigerant for Vehicle-Powered (VP) Truck Units in North America

Refrigerant Charge:

V-220 MAX - Model 10 (before December 12, 2022)

V-220 MAX - Model 10 (on or after December 12, 2022)

V-220 MAX - Model 20 (before December 12, 2022)

V-220 MAX - Model 20 (on or after December 12, 2022)

V-320 MAX - Model 10 (before December 12, 2022)

V-320 MAX - Model 10 (on or after December 12, 2022)

V-320 MAX - Model 20 (before December 12, 2022)

V-320 MAX - Model 20 (on or after December 12, 2022)

V-320 MAX - Model 30 (before December 12, 2022)

V-320 MAX - Model 30 (on or after December 12, 2022)

V-320 MAX - Model 50 (before December 12, 2022)

V-320 MAX - Model 50 (on or after December 12, 2022)

2.5 lb (1.13 kg) R-404A

2.5 lb (1.13 kg) R-452A

2.6 lb (1.18 kg) R-404A

2.6 lb (1.18 kg) R-452A

3.0 lb (1.36 kg) R-404A

3.0 lb (1.36 kg) R-452A

3.1 lb (1.41 kg) R-404A

3.1 lb (1.41 kg) R-452A

3.1 lb (1.41 kg) R-404A

3.1 lb (1.41 kg) R-452A

3.2 lb (1.45 kg) R-404A

3.2 lb (1.45 kg) R-452A

Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LISW):

Opens

Closes

200 ± 5 F (93 ± 3 C)

230 ± 5 F (110 ± 3 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

Compressor Pressure Regulator (CPR) Valve Setting - Model 30 and 50 Only 24 ± 2 psig (165 ± 14 kPa)
Electric Standby Suction Pressure Regulator (SPR) Valve Setting - Model 20 MAX Only 24 ± 2 psig (165 ± 14 kPa)
R-134a Refrigeration System V-520
Refrigerant Charge:

V-520 - Model 10

V-520 - Model 20

V-520 - Model 30

V-520 - Model 50

5.3 lb (2.42 kg) R-134a

5.7 lb (2.57 kg) R-134a

5.8 lb (2.63 kg) R-134a

5.7 lb (2.57 kg) R-134a

Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LISW):

Opens

Closes

200 ± 5 F (93 ± 3 C)

230 ± 5 F (110 ± 3 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Engine Driven Compressor Pressure Regulator (CPR) Valve Setting - Model 30 and 50 Only 50.0 ± 5 psig (345 ± 34 kPa)
Electric Standby Suction Pressure Regulator (SPR) Valve Setting - Model 20 and 50 Only

230V 1 Phase Electric Motor

230V 3 Phase Electric Motor

24.0 ± 4 psig (165.5 ± 28 kPa)

39.0 ± 4 psig (269 ± 28 kPa)

R-404A / R-452A Refrigeration System V-520 MAX

Important MAX and SPECTRUM units built Before December 12, 2022 were originally built using R-404A refrigerant.

MAX and SPECTRUM units built on and after December 12, 2022 are equipped with R-452A refrigerant.

See Service Bulletin SB874 Transition to R–452A Refrigerant for Vehicle-Powered (VP) Truck Units in North America

 
Refrigerant Charge:

V-520 MAX - Model 10 (before December 12, 2022)

V-520 MAX - Model 10 (on or after December 12, 2022)

V-520 MAX - Model 20 (before December 12, 2022)

V-520 MAX - Model 20 (on or after December 12, 2022)

V-520 MAX - Model 30 (before December 12, 2022)

V-520 MAX - Model 30 (on or after December 12, 2022)

V-520 MAX - Model 50 (before December 12, 2022)

V-520 MAX - Model 50 (on or after December 12, 2022)

V-520 SPECTRUM - Model 10 (before December 12, 2022)

V-520 SPECTRUM - Model 10 (on or after December 12, 2022)

V-520 SPECTRUM - Model 20 (before December 12, 2022)

V-520 SPECTRUM - Model 20 (on or after December 12, 2022)

V-520 SPECTRUM - Model 50 (before December 12, 2022)

V-520 SPECTRUM - Model 50 (on or after December 12, 2022)

4.9 lb (2.22 kg) R-404A

4.9 lb (2.22 kg) R-452A

5.2 lb (2.37 kg) R-404A

5.2 lb (2.37 kg) R-452A

5.5 lb (2.52 kg) R-404A

5.5 lb (2.52 kg) R-452A

5.4 lb (2.43 kg) R-404A

5.4 lb (2.43 kg) R-452A

5.3 lb (2.42 kg) R-404A

5.3 lb (2.42 kg) R-452A

5.7 lb (2.57 kg) R-404A

5.7 lb (2.57 kg) R-452A

5.8 lb (2.63 kg) R-404A

5.8 lb (2.63 kg) R-452A

Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LISW):

Opens

Closes

200 ± 5 F (93 ± 3 C)

230 ± 5 F (110 ± 3 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

Engine Driven Compressor Pressure Regulator (CPR) Valve Setting - Model 30 and 50 Only 50.0 ± 5 psig (345 ± 34 kPa)
Electric Standby Suction Pressure Regulator (SPR) Valve Setting - Model 20 and 50 Only

230V 1 Phase Electric Motor

230V 3 Phase Electric Motor

24.0 ± 4 psig (165.5 ± 28 kPa)

39.0 ± 4 psig (269 ± 28 kPa)

Suction Bypass CPR Valve Setting - SPECTRUM Only See “Compressor Pressure Regulator Valve Setup Procedure” under “Compressor Pressure Regulator Valve in SPECTRUM Units”.
R-134a Refrigeration System V-520 RT
Refrigerant Charge:

V-520 RT - Model 10

V-520 RT - Model 20

V-520 RT - Model 30

V-520 RT - Model 50

4.1 lb (1.85 kg) R-134a

4.2 lb (1.90 kg) R-134a

4.2 lb (1.9 kg) R-134a

4.3 lb (1.95 kg) R-134a

Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LISW):

Opens

Closes

200 ± 5 F (93 ± 3 C)

230 ± 5 F (110 ± 3 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Engine Driven Compressor Pressure Regulator (CPR) Valve Setting - Model 30 and 50 Only 50.0 ± 5 psig (345 ± 34 kPa)
Electric Standby Suction Pressure Regulator (SPR) Valve Setting - Model 20 and 50 Only

230V 1 Phase Electric Motor

230V 3 Phase Electric Motor

24.0 ± 4 psig (165.5 ± 28 kPa)

35.3 ± 4 psig (243 ± 28 kPa)

R-404A and R-452A Refrigeration System V-520 RT MAX

Important MAX and SPECTRUM units built Before December 12, 2022 were originally built using R-404A refrigerant.

MAX and SPECTRUM units built on and after December 12, 2022 are equipped with R-452A refrigerant.

See Service Bulletin SB874 Transition to R–452A Refrigerant for Vehicle-Powered (VP) Truck Units in North America

 
Refrigerant Charge:

V-520 RT MAX - Model 10 (before December 12, 2022)

V-520 RT MAX - Model 10 (on or after December 12, 2022)

V-520 RT MAX - Model 20 (before December 12, 2022)

V-520 RT MAX - Model 20 (on or after December 12, 2022)

V-520 RT MAX - Model 30(before December 12, 2022)

V-520 RT MAX - Model 30 (on or after December 12, 2022)

V-520 RT MAX - Model 50(before December 12, 2022)

V-520 RT MAX - Model 50 (on or after December 12, 2022)

V-520 RT SPECTRUM MAX - Model 50(before December 12, 2022)

V-520 RT SPECTRUM MAX - Model 50 (on or after December 12, 2022)

3.7 lb (1.68 kg) R-404A

3.7 lb (1.68 kg) R-452A

3.8 lb (1.73 kg) R-404A

3.8 lb (1.73 kg) R-452A

3.8 lb (1.73 kg) R-404A

3.8 lb (1.73 kg) R-452A

3.9 lb (1.78 kg) R-404A

3.9 lb (1.78 kg) R-452A

4.3 lb (1.95 kg) R-404A

4.3 lb (1.95 kg) R-452A

Defrost Termination Switch:

Opens

Closes

48.0 ± 5.0 F (8.9 ± 2.8 C)

36.0 ± 5.0 F (2.2 ± 2.8 C)

Liquid Injection Switch (LISW):

Opens

Closes

200 ± 5 F (93 ± 3 C)

230 ± 5 F (110 ± 3 C)

Low Pressure Cutout Switch (LPCO):

Opens

Closes

5 to 11 in. Hg vacuum (-17 to -37 kPa)

4 to 7 psig (28 to 48 kPa)

Over Temperature Switch - Electric Heater Option Only:

Opens

Closes

105 ± 5 F (41 ± 3 C)

90 ± 5 F (32 ± 3 C)

Engine Driven Compressor Pressure Regulator (CPR) Valve Setting - Model 30 and 50 Only 50.0 ± 5 psig (345 ± 34 kPa)
Electric Standby Suction Pressure Regulator (SPR) Valve Setting - Model 20 and 50 Only

230V 1 Phase Electric Motor

230V 3 Phase Electric Motor

24.0 ± 4 psig (165.5 ± 28 kPa)

35.3 ± 4 psig (243 ± 28 kPa)

Suction Bypass CPR Valve Setting - SPECTRUM Only See “Compressor Pressure Regulator Valve Setup Procedure” under “Compressor Pressure Regulator Valve in SPECTRUM Units”.
Refrigeration System C-Series
Refrigerant Charge:

C-150

C-150 10

C-150 10 MAX

C-150 30 MAX


C-250

C-250 10

C-250 10 MAX

C-250 30 MAX


C-350

C-350 10

C-350 10 MAX

C-350 30 MAX


C-450

C-450 10

C-450 10 MAX

C-450 30 MAX


C-550

C-550 10

C-550 10 MAX

C-550 30 MAX


C-650

C-650 10

C-650 10 MAX

C-650 30 MAX


C-750 10 MAX

C-750 30 MAX

1.54 lb (0.70 kg) R-134a

1.54 lb (0.70 kg) R-134a

1.54 lb (0.70 kg) R-404A

1.54 lb (0.70 kg) R-404A


2.09 lb (0.95 kg) R-134a

2.09 lb (0.95 kg) R-134a

2.09 lb (0.95 kg) R-404A

2.09 lb (0.95 kg) R-404A


2.64 lb (1.2 kg) R-134a

2.64 lb (1.2 kg) R-134a

2.64 lb (1.2 kg) R-404A

2.64 lb (1.2 kg) R-404A


2.64 lb (1.2 kg) R-134a

2.64 lb (1.2 kg) R-134a

2.64 lb (1.2 kg) R-404A

2.64 lb (1.2 kg) R-404A


2.86 lb (1.3 kg) R-134a

2.86 lb (1.3 kg) R-134a

3.52 lb (1.6 kg) R-452A

3.52 lb (1.6 kg) R-452A


3.52 lb (1.6 kg) R-134a

3.52 lb (1.6 kg) R-134a

3.75 lb (1.7 kg) R-452A

3.75 lb (1.7 kg) R-452A


4.20 lb (1.9 kg) R-452A

4.20 lb (1.9 kg) R-452A

Defrost Method (10/ MAX 10/ MAX 30 versions)   Hot Gas
Defrost thermostat (Klixon) (10/ MAX 30 versions):

Opens

Closes

48.0 ± 37.4 F (8.9 ± 3.0 C)

36.0 ± 37.4 F (2.2 ± 3.0 C)

Liquid injection switch (R-404A/ R452A):

Opens

Closes

48.0 ± 37.4 F (93 ± 3.0 C)

36.0 ± 37.4 F (110 ± 3.0 C)

High Pressure Cutout Switch (HPCO), R-134a

Opens

Closes

300 ± 10 psi (2,068 ± 70 kPa)

200 ± 10 psi (1,379 ± 70 kPa)

High Pressure Cutout Switch (HPCO), R-404A

Opens

Closes

450 ±10 psi (3,100 ± 70 kPa)

375 ±10 psi (2,585 ± 70 kPa)

CSPS (Condenser Pressure Control Switch)

Opens

Closes

300+20 psi/-0 psi (2,068+138 kPa/-0 kPa)

200 ± 20 psi (1,379 ± 138 kPa)

Low Pressure Cutout Switch (LPCO)

Opens

Closes

5 to 11 inch vacuum

4 to 7 psi (27.6 to 48.3 kPa)

Suction Pressure Regulator (SPR) Valve Setting - Model MAX 10 & 30 Versions  

29 psi (199.95 kPa)

Chapter 7: Inspection and Service Intervals

7.1: Weekly Pre-Trip Checks

  1. Visually inspect belt.

  2. Listen for unusual noises, vibrations, etc.

  3. Visually inspect unit for fluid leaks (coolant, oil, refrigerant).

  4. Visually inspect unit for damaged, loose or broken parts (including air ducts and bulkheads, if so equipped).

  5. In the event of excess of dirt or obstruction clean the unit, including condenser and evaporator coils.

7.1.1: Weekly Pretrip Inspection

The following Weekly Pretrip Inspection should be completed before starting the unit and loading the truck. While the weekly inspection in not a substitute for regularly scheduled maintenance inspections, it is important part of the preventive maintenance program designed to head off operating problems before they happen.

Leaks: Inspect for refrigerant leaks and worn refrigerant lines.

Battery: Terminals should be properly tightened and show no signs of corrosion.

Belts: Inspect for cracks, wear, and proper belt tension.

Mounting Bolts: Verify bolts are properly tightened.

Electrical: Electrical connections should be securely fastened. Wires and terminals should be free of corrosion, cracks, or moisture.

Structural: Visually check for physical damage.

Coils: The condenser and evaporator coils (evaporator coils in multi–temperature units) should be clean and free of debris.

Coils: The condenser and evaporator coils should be clean and free of debris.

  • Washing with clean water should be sufficient. The use of cleaning agents or detergents is strongly discouraged due to the possibility of degradation of the construction. If using a power washer, the nozzle pressure should not exceed 600 psi (41 bar). For the best results, spray the coil perpendicular to the face of the coil. The spray nozzle should be kept between 1 inch and 3 inches (25 to 75 millimeters) from the coil surface.

    Important Models V–500 and V–800/V–1000 feature a high efficient micro channel aluminum condenser coil, in these cases the spray nozzle should be kept 300mm away from the coil and aimed perpendicularly to the coil surface to avoid damaging the aluminum fins.
    If necessary to use a chemical cleaner or detergent use a cleaner that does not contain any hydrofluoric acids and is between 7 and 8 on the pH scale. Ensure dilution instructions provided by the detergent supplier are followed. In case of doubt about the compatibility of the detergent with the type of materials listed above, always ask the supplier a written confirmation of the compatibility. Should a chemical cleaner be required, it is MANDATORY that all components are thoroughly rinsed with water even if the instructions of the cleaner specify that it is a “no rinse” cleaner. Failure to comply with above mentioned guidelines will lead to a shortened life of the equipment to an indeterminable degree. The repeated transportation of meat and fish waste can cause extensive corrosion to the evaporator coils and evaporator section tubing over time due to ammonia formation and can reduce the lifespan of the coils. Appropriate additional measures should be taken to protect the coils against the aggressive corrosion that can result from transportation of such products.

Load Compartment: Inspect the interior and exterior of the truck for any damage. Any damage to the walls or insulation should be repaired.

Defrost Drains: Check the defrost drain hoses and fittings to ensure they are not blocked.

Doors: Verify doors and weather seals are in good condition and seal hermetically.

Sight glass: Check that the refrigerant charge sight glass on the running unit is totally full (the cargo compartment temperature must be approximately 0ºC).

7.2: Weekly Post-Trip Checks

    Notice
  • Equipment Damage
  • Do not use pressurised water.
  1. Clean the outside cover of the unit. Use a damp cloth and neutral detergents. Do not use harsh cleaning products or solvents.

  2. Check for leaks.

  3. Check for loose or missing hardware.

  4. Check for physical damage to the unit.

7.3: Inspection and Service Schedules

To ensure that your Thermo King unit operates reliably and economically over its full life, and to avoid limiting its warranty cover, the appropriate inspection and service schedule must be followed. Inspection and Service intervals are determined by the number of unit operating hours and by the age of the unit. Examples are shown in the table below. Your Dealer will prepare a schedule to suit your specific needs.

Operating Hours per Year 1000 2000 3000
Inspection 6 months/ 500 hours    
Inspection 12 months/ 1000 hours (+ preventative maintenance) 6 months/ 1000 hours 4 months/ 1000 hours
Inspection 18 months/ 1500 hours 12 months/ 2000 hours (+ preventative maintenance) 8 months/ 2000 hours
Full Service 24 months/ 2000 hours 18 months/ 3000 hours 12 months/ 3000 hours (+ preventative maintenance)
  (continue as above) (continue as above) (continue as above)
Operating Hours per Year 1000 2000 3000
Service 12 months/ 1000 hours (+ preventative maintenance) 6 months/ 1000 hours 4 months/ 1000 hours
Service   12 months/ 2000 hours (+ preventative maintenance) 8 months/ 2000 hours
Full Service 24 months/ 2000 hours 18 months/ 3000 hours 12 months/ 3000 hours (+ preventative maintenance)
  (continue as above) (continue as above) (continue as above)
Important Installation Inspection needs to be carried out on all the units at 6 months/ 500 hours (whichever occurs first).

Service Record

Each inspection and service performed should be recorded on the Service Record Sheet found at the back of this manual.

Preventative Maintenance

Refer to the previous page for checks that should be carried out daily/weekly on the unit. Please work with your Dealer in order to create a maintenance schedule which fits your needs.
Thermo King has extended the limited warranty on new units from 3,000 total hours to a maximum of 4,000 compressor run hours within the 2 year warranty period.
This limited warranty is dependent on the owner and/ or operator adhering to the preventative maintenance schedule as advised by your Thermo King Dealer.

Chapter 8: Recover Refrigerant

At Thermo King®, and FrigoBlock we recognize the need to preserve the environment and limit the potential harm to the ozone layer that can result from allowing refrigerant to escape into the atmosphere.

We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the atmosphere.

In addition, service personnel must be aware of Federal local regulations concerning the use of refrigerants and the certification of technicians. For additional information on regulations and technician certification programs, contact your local THERMO KING dealer.