Alarm Code Descriptions

Color Code Definitions

OK TO RUN CHECK AS SPECIFIED TAKE IMMEDIATE ACTION      
Alarm   Description
Manual Start
bAt   Low Battery Voltage - Check vehicle battery.
Auto Start
HP  

High Pressure Alarm - The system has detected excessively high discharge pressure.

If the problem persists when the unit is restarted, contact your Thermo King Dealer.

LP  

Low pressure alarm – The system has detected excessively low suction pressure and has protected the compressor from an abnormal condition. Unit operation will resume automatically once the normal suction pressure is restored, and the alarm can be cleared (see Clearing Alarm Codes).

Among other reasons, this could be due to:

  • Dirty evaporator coil – excessive ice formation.

  • Load stacked in front of the evaporator does not allow proper air recirculation through the box.

If the problem persists when the unit is restarted, contact your Thermo King dealer.

PSE  

High Pressure Sensor Failure - The high pressure sensor has become faulty or disconnected.

Contact your Thermo King Dealer.

dr1, dr2  

Cargo Doors Are Open (Units with door switch option only) - Check if the Doors are open. if not, then the door switches are faulty, or improper door switch configuration.

Contact your Thermo King Dealer.

tCO  

Control Module Overheating

If the problem persists when the unit is restarted, contact your Thermo King Dealer.

SOF  

Software Failure

Contact your Thermo King Dealer.

P1E  

Faulty Cargo Box Return Air Temperature Sensor - Faulty or disconnected return air temperature sensor.

Contact your Thermo King Dealer.

P2E  

Remote Cargo Box Return Air Temperature Reading Error (open circuit or short-circuit)

Contact your Thermo King Dealer.

C  

Communications Failure

Contact your Thermo King Dealer.

H01  

DSR communication lost - Communication lost to the other Electronic Control Module.

Contact your Thermo King Dealer.

H02  

HMI communication lost - Communication lost to the HMI.

Contact your Thermo King Dealer.

H03  

SCM communication lost - Communication lost to Smart Charger Module.

If the problem persists when the unit is restarted, contact your Thermo King Dealer.

H04  

CDM communication lost - Communication lost to Compressor Drive Module.

Contact your Thermo King Dealer.

H0A  

Low Power Mode Activation - ignition key of the vehicle is disconnected, and the unit is not connected to the shore power. Operation of the unit may be inhibited but remains operational.

Report Alarm at the end of the day.

H0B  

Sleep Mode Activation- While the unit OFF, the vehicle battery voltage dropped below a threshold. Normal operation of the controller will resume as soon as the power is restored.

Report Alarm at the end of the day.

H0C  

Power Derating Shutdown - Low Voltage Shutdown alarm - your battery voltage has dropped below a defined level. The shutdown alarm is automatically cleared once the voltage rises over this limit once more.

Contact your Thermo King Dealer.

H10  

Internal flash erase error - Internal, System reset needed

Report Alarm at the end of the day.

H12  

Default parameters in use - This will typically happen after a new firmware version has been loaded.

If the problem persists when the unit is restarted, contact your Thermo King Dealer.

H15  

eMMC erase error - An error occurred while loading parameters to the DSR-IV Controller.

Internal, System reset needed, contact your Thermo King Dealer.

H16  

eMMC write error - An error occurred while loading parameters to the DSR-IV Controller or performing the datalogging process.

Internal, System reset needed, contact your Thermo King Dealer.

H17  

eMMC read error - An error during powering-up when reading configuration paramenters.

Internal, System reset needed, contact your Thermo King Dealer.

H18  

Flash Loading Failed - An error occurred while loading firmware to the DSR-IV Controller.

Internal, System reset needed, contact your Thermo King Dealer.

H1A  

Non-Compatible SW - Indicates that one of the electronic components contain an incorrect or out-of-date Software version.

Contact your Thermo King Dealer.

Compressor Drive Module Alarms

H21  

Phase overcurrent- Shutdown alarm

Contact your Thermo King Dealer.

H2A  

Overcurrent of DC/DC converter- Shutdown alarm

Contact your Thermo King Dealer.

H22  

Input overvoltage - Shutdown alarm

Contact your Thermo King Dealer.

H23  

Input undervoltage - Consider let the engine run to allow the alternator to charge the vehicle battery.

Contact your Thermo King Dealer.

H24  

Motor Endstage temperature too high - Shutdown alarm

Contact your Thermo King Dealer.

H25  

Motor controller communication error - Critical, Motor controller alarm

Contact your Thermo King Dealer.

H26  

Locked Rotor - Critical, Motor controller alarm

Contact your Thermo King Dealer.

H27  

Compressor start-up failure - Critical, Motor controller alarm

Contact your Thermo King Dealer.

H28  

Phase Loss - One of the phases carrying current to the Compressor Drive Module (CDM) is disconnected.

Contact your Thermo King Dealer.

H40  

CFLT activated - Repeating non-critical alarms or a threshold of Active Alarms is reached which forces the unit to shutdown for maintenance.

Contact your Thermo King Dealer.

Battery Management Alarms

H50 to H5D  

Battery internal alarm (Thermal or Voltage problem) - Shutdown alarm

Contact your Thermo King Dealer.

H5E  

Battery communications lost - Shutdown alarm

Contact your Thermo King Dealer.

H5F  

Low Battery warning. - Please connect your unit to shore power to charge the TK Battery.

If problem persists, Contact your Thermo King Dealer.

H60 to H63  

Battery internal alarm (internal sensors) - Shutdown alarm

Contact your Thermo King Dealer.

H6B, H6C  

Battery deeply discharged. - Please connect your unit to shore power to charge the TK Battery

If problem persists, Contact your Thermo King Dealer.

H6D  

BMS communication lost. - Restart the E-200.

If problem persists, Contact your Thermo King Dealer.

H70 to H77  

SCM Charging Condition. - Restart the E-200.

If problem persists, Contact your Thermo King Dealer.

H78, H79  

Over Temperature in the Power Supply Unit (Main Unit) - Let the unit cool down, then restart the unit.

If problem persists, Contact your Thermo King Dealer.

H7A. H7B  

Relay Malfunction - Shutdown alarm

Contact your Thermo King Dealer.

H7C, H7D  

Batteries current imbalance warning (2 Battery Application ONLY) - Connect the unit to shore power to charge the TK battery.

If problem persists, Contact your Thermo King Dealer.