Introduction

Thermo King designs and builds temperature-controlled transport equipment.

These types of equipment can be validated for a specific desired temperature range for the transport of pharmaceutical products.

Due to the fact that several test were performed on the different units in time, not all the tests are performed under the same circumstances.

Truck body with T-1000R Spectrum S3+S3

Temperature Range

Extreme Ambient Temperature

Recommended Setpoint

Max Average Deviation from Setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+6°C

+2/-3°C of setpoint

Temperature between 15°C and 25°C

+40°C / -30°C

+20°C

+2/-3°C of setpoint

Truck body with T-1200R Spectrum S3+S3

Temperature Range

Extreme Ambient Temperature

Recommended Setpoint

Max Average Deviation from Setpoint

Temperature below -20°C

+40°C / -30°C

-25°C

+5/-5°C of setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+6°C

+2/-4°C of setpoint

Temperature between 15°C and 25°C

+40°C / -30°C

+20°C

+3/-5°C of setpoint

Truck body with UT-1200 Spectrum S3+S3

Temperature Range

Extreme Ambient Temperature

Recommended Setpoint

Max Average Deviation from Setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+6°C

+3/-3°C of setpoint

Temperature between 15°C and 25°C

+40°C / -30°C

+20°C

+3/-5°C of setpoint

Truck body with Truck body with UT-R Spectrum S3+S3

Temperature Range

Extreme Ambient Temperature

Recommended Setpoint

Max Average Deviation from Setpoint

Temperature above -27°C

+30°C / -30°C

-29 °C

+/- 3°C of setpoint

Temperature below -20°C

+40°C / -30°C

-24 °C

+4/-6°C of setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+5°C

+/-3°C of setpoint

Temperature between 15°C and 25°C

+40°C / -30°C

+20°C

+/-5°C of setpoint

Truck body with Thermo King UT-R Spectrum unit

Temperature Range Extreme Ambient Temperature Recommended Setpoint Max Average Deviation from Setpoint

Temperature above -27°C

+30°C / -30°C

-29 °C

+/-3°C of setpoint

Temperature below -20°C

+40°C / -30°C

-24 °C

+4/-6°C of setpoint

Temperature between 2°C and 8°C

+40°C / -30°C

+5°C

+/- 3°C of setpoint

Temperature between 15°C and 25 °C

+40°C / -30°C

+20 °C

+/- 5°C of setpoint

Note To ensure total flexibility the qualification is to be performed at all stated ranges from above.