- ii Introduction
- Chapter 1: Safety Precautions
- 1.1: Danger Warning Caution and Notice
- 1.2: Auto Start Stop Safety
- 1.3: Battery Installation and Cable Routing Safety
- 1.4: TK Lithium Ion Battery Safety E200
- 1.5: Refrigerant Hazards Safety
- 1.6: Refrigerant Oil Hazards Safety
- 1.7: Electrical Hazards Safety
- 1.8: Microprocessor Service Precautions Safety
- 1.9: Welding Precautions Safety
- 1.10: First Aid
- Chapter 2: Qualification Plan 61296
- Chapter 3: Risk Analysis Thermo King Pharma
- Chapter 4: Design Qualification 61296
- Chapter 5: Installation Qualification 61296,
- Chapter 6: Operational Qualification 61296
- 6.1: Description of the Qualified Operation 61296
- 6.2: Support of the Defined Aspects of Use 61296
- 6.3: Load Space Consideration 61296
- 6.4: Layout of Sample-type Truck Qualification 61296
- 6.5: Technical and User Data 61296
- 6.6: Thermocouple Locations 61296
- 6.7: Operational Qualification on the Field 61296
- Chapter 7: Performance Qualification 61296
- Chapter 8: Appendix Pharma
SP Truck Multi-Temperature
SP Truck MT GDP
ii Introduction
This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.
This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.
This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.
Thermo King’s warranty shall not apply to any equipment which
has been so installed, maintained, repaired or altered as, in the
manufacturer’s judgment, to affect its integrity.
Manufacturer shall have no liability to any person or entity for any personal injury, property damage or any other direct, indirect, special, or consequential damages whatsoever, arising out of the use of this manual or any information, recommendations or descriptions contained herein. The procedures described herein should only be undertaken by suitably qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.
There is nothing complicated about operating and maintaining your Thermo King unit, but a few minutes studying this manual will be time well spent.
Performing pre-trip checks and enroute inspections on a regular basis will minimize operating problems. A regular maintenance program will also help to keep your unit in top operating condition. If factory recommended procedures are followed, you will find that you have purchased the most efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled by a Thermo King dealer for four very important reasons:
-
They are equipped with the factory recommended tools to perform all service functions.
-
They have factory trained and certified technicians.
-
They have genuine Thermo King replacement parts.
-
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.
Copies of the approved Thermo King documentation can be found on the Thermo King iService Portal: http://iservice.thermoking.com/esa.
Emergency Assistance
Thermo Assistance is a multi-lingual communication tool designed to put you in direct contact with an authorized Thermo King dealer.
Thermo Assistance should only be contacted for breakdown and repair assistance.
To use this system, you need the following information before you call: (phone charges will apply)
-
Contact Phone Number
-
Unit Type
-
Thermostat Temperature Setting
-
Ambient temperature
-
Present Load Temperature
-
Probable Cause of Fault
-
Warranty Details of the Unit
-
Payment Details for the Repair
Leave your name and contact number and a Thermo Assistance Operator will call you back. At this point you can give details of the service required and the repair will be organized.
No payment at point of repair for customers with a ThermoKare service contract or with a guaranty of payment from their Thermo King or FRIGOBLOCK home-dealer
Please note that Thermo Assistance cannot guarantee payments and the service is designed for the exclusive use of refrigerated transporters with products manufactured by Thermo King Corporation.
Revision History
Revision A | (04/22) New format |
Revision B | (04/24) Added UT-R |
General Information
The maintenance information in this manual covers unit models: | ||
Multi-temperature Thermo King units for truck | ||
T-1000R Spectrum | ||
T-1200R Spectrum | ||
UT-1200 Spectrum | ||
UT-R Spectrum | ||
Kit Pharma Solutions SP Truck MT | 706828 | |
For further information, refer to: | ||
T-series Operator Manual | ||
Truck T-series Spectrum Installation Manual | ||
UT series Operators Manual | ||
UT Spectrum Installation Manual | ||
UT-R Series Operators Manual | ||
UT-R Spectrum Installation Manual | ||
The information in this manual is provided to assist owners, operators and service people in the proper upkeep and maintenance of Thermo King units. |
-
The term “unit” is referring to temperature controlled units listed above.
-
The term “body” refers to an “insulated equipment” as defined in ATP Annex 1
-
The term “IN” refers to a “Normally insulated equipment” as defined in ATP Annex 1
-
The term “IR” refers to a “Heavily insulated equipment” as defined in ATP Annex 1
Recover Refrigerant
At Thermo King®, we recognize the need to preserve the environment and limit the potential harm to the ozone layer that can result from allowing refrigerant to escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the atmosphere.
When working on transport temperature control systems, a recovery process that prevents or minimizes refrigerant loss to the atmosphere is required by law. In addition, service personnel must be aware of the applicable European Union, National, Federal, State, and/or Local regulations governing the use of refrigerants and certification of technicians. For additional information on regulations and technician programs, contact your local THERMO KING dealer.
Service Tools - Use the proper service tools. Gauge manifold sets should include appropriate shutoff valves or disconnects near the end of each service line.
Recovery Equipment - Recovery equipment must be used. Proper recovering, storing and recycling of refrigerants is an important part of all service work.
Service Procedures - Recommended procedures must be used to minimize refrigerant loss.
Components may be isolated by closing service valves and performing system pump-downs.
Components unable to be isolated for service must be repaired only after refrigerant is properly recovered.
About This Manual
Purpose
The information in this manual is provided to assist owners, operators and service people for GDP qualification of equipment with temperature controlled unit for the transport of pharmaceutical products.
This GDP Qualification Documentation is in line with the EU guideline of Good Distribution Practices of medical products for human usage (GDP) and annex 15 “Qualification and Validation” of the Good Manufacturing Practice for Medicinal products for Human and Veterinary Use (GMP).
Units covered in this manual are Thermo King Truck Multi-Temperature Units: T-1000R Spectrum, T-1200R Spectrum and UT-1200 Spectrum.
Contents
GDP Qualification Documentation
This manual is organized into the following chapters:
Chapter | Purpose |
---|---|
Certificate of the equipment qualified GDP compliant | Validation of the Installation Qualification for specific equipment.
Note (To be inserted in pouch provided at the front of this
Manual.)
|
GDP Approval letter by Independent pharmaceutical company |
Note (To be inserted in pouch provided at the front
of this Manual.)
|
Qualification Plan | Summarizes the minimum information that is included in this qualification report, Purpose, User Requirements Specifications, stages of qualification, qualification method, and responsibilities. |
Risk Assessment | Identifies sensible measures to control the risks during the transport of pharmaceutical products with temperature controlled equipment. |
Design Qualification | Lists equipment specifications and provides a documented verification that the proposed design of the equipment is suitable for the intended purpose. |
Installation Qualification | Confirms that the equipment is installed and conforms to the approved design qualification and the manufacturer's recommendations. |
Operational Qualification | Confirms that the equipment performs as intended throughout the anticipated operating ranges and provides operating guidance. |
Performance Qualification | Provides temperature mapping test results that prove that the equipment can perform effectively and reproducibly, based on the approved process method and product specification. |
Certification | Certificate of Approval of Trane Technologies Quality Management system. |
Contacting Thermo King Service
Before you call Thermo King Service, have the following information on hand (for exact data see serial plate on your unit):
-
Unit Type (commonly typed on serial plate after code DESC)
-
System or Model number (commonly coded on serial plate after code ITEM)
-
System number has usually six digits format (example 901902)
-
Model number is the same as System number but with M letter at the end (example 901902M)
-
-
Serial Number
Who to call: Your Thermo King Dealer Representative or Thermo King Service Center.
Blank Pages
This manual may contain blank pages at the end of chapters. This is normal. There is no information missing from the manual.
Roadside/Curbside Terminology
Roadside/Curbside terminology: These terms can be confusing because of differences between North America and Europe. Please note:
Curbside: | The side of the truck to the driver’s right when the driver is in his seat and facing forward. |
Roadside: | The side of the truck to the driver’s left when the driver is in his seat and facing forward. |
Customer Satisfaction Survey Assistance/Feedback
Let your voice be heard!
Your feedback will help improve our manuals. The survey is accessible through any internet-connected device with a web browser.
Scan the Quick Response (QR) code or click Technical Publications EMEA Feedback to complete the survey.
Need assistance finding technical literature, to report missing content, or to provide feedback on our technical literature? Email Thermo King Americas Publications at thermokingamericaspublications@thermoking.com.
Chapter 1: Safety Precautions
1.1: Danger, Warning, Caution, and Notice
Thermo King®/ FRIGOBLOCK recommends that all service be performed by a Thermo King/FRIGOBLOCK dealer and to be aware of several general safety practices.
Thermo King® recommends that all service be performed by a Thermo King dealer and to be aware of several general safety practices.
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this unit depend upon the strict observance of these precautions. The four types of advisories are defined as follows:
1.2: Auto Start/Stop Auto Start Hazards
1.3: Battery Installation and Cable Routing
1.4: TK Lithium Ion Battery Safety
This product is safe with normal use. Exposure to the ingredients contained within and/or their combustion products could be harmful. Risk of exposure occurs only if the battery is mechanically, thermally, or electrically abused to the point of compromising the enclosure. If this occurs, exposure to the electrolyte solution contained within can occur by inhalation, ingestion, eye contact, and skin contact. The battery should not be opened or burned.
1.5: Refrigerant Hazards
1.6: Refrigerant Oil Hazards
1.7: Electrical Hazards
High Voltage
Important Many modern Thermo King units utilize dangerous AC voltage supplied from the diesel engine driven generator to operate the condenser fans and evaporator blower when the unit is operating in Diesel Mode.
Low Voltage
2prefix are connected directly to battery power. Always disconnect the battery before servicing the unit.
1.8: Controller/Microprocessor Service Precautions
Take precautions to prevent electrostatic discharge when servicing the controller or microprocessor and its related components. Even tiny amounts of current can severely damage or destroy electronic components.
Observe the following precautions when servicing a controller or microprocessor control system to avoid damaging electronic components. Refer to the applicable unit, controller, or microprocessor diagnostic manual for more information.
-
If the unit has a service or microprocessor ON/OFF switch, turn it OFF before connecting or disconnecting the battery.
-
Disconnect power to the unit.
-
Avoid wearing clothing that generates static electricity (wool, nylon, polyester, etc.).
-
Wear a wrist strap (PN 2040622 or equivalent) with the lead end connected to the microprocessor or unit ground terminal (if equipped). These straps are available from most electronic equipment distributors. DO NOT wear these straps with power applied to the unit.
-
Avoid unnecessary contact with the electronic components.
-
Store and ship electronic components in antistatic bags and protective packaging.
-
Leave electronic components in their antistatic packing materials until you’re ready to use them.
-
After servicing any electronic components, check the wiring for possible errors before restoring power to the unit.
-
Never use a battery and a light bulb to test circuits on any controller or microprocessor-based equipment.
1.9: Welding Precautions
Take precautions before electrically welding any portion of the unit or the vehicle to which it is attached. Verify that welding currents are not allowed to flow through the unit’s electronic circuits.
Observe the following precautions when welding to avoid damaging electronic components.
-
If the unit has a service switch, or microprocessor ON/OFF, turn it OFF before connecting or disconnecting the battery.
-
Disconnect power to the unit.
-
Disconnect all wire harnesses from the microprocessor. Disconnect the ECU and the battery charger if so equipped.
-
Disconnect the DCDC converter.
-
If there are any electrical circuit breakers in the control box, switch them OFF.
-
Close the control box.
-
Components that could be damaged by welding sparks should be removed from the unit.
-
Use normal welding procedures, but keep the ground return electrode as close to the area being welded as practical. This will reduce the likelihood of stray welding currents passing through any electronic circuits.
1.10: First Aid
REFRIGERANT
-
Eyes: For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical attention.
-
Skin: Flush area with large amounts of warm water. Do not apply heat. Remove contaminated clothing and shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection. Get prompt medical attention. Wash contaminated clothing before reuse.
-
Inhalation: Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
-
Frost Bite: In the event of frost bite, the objectives of First Aid are to protect the frozen area from further injury, warm the affected area rapidly, and to maintain respiration.
REFRIGERANT OIL
-
Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.
-
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
-
Inhalation: Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
-
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
ENGINE COOLANT
-
Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.
-
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
-
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
BATTERY ACID
Under normal usage, the Ni-MH batteries
are hermetically sealed. In case of accident, perform the following
instructions:
-
Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention. Wash skin with soap and water.
-
Skin: Immediately remove contaminated clothing. Wash skin with large volumes of water, for at least 15 minutes. Wash skin with soap and water. Do not apply fatty compounds. Seek immediate medical assistance.
-
Inhalation: Provide fresh air. Rinse mouth and nose with water. Seek immediate medical assistance.
-
Ingestion: If the injured person is fully conscious: make the person drink extensive amounts of milk. Do not induce vomiting. Take the injured person immediately to a hospital.
ELECTRICAL SHOCK
Take IMMEDIATE action after a person has received an electrical shock. Get quick medical assistance, if possible.
The source of the shock must be quickly stopped, by either shutting off the power or removing the victim. If the power cannot be shut off, the wire should be cut with a non-conductive tool, such as a wood-handle axe or thickly insulated cable cutters. Rescuers should wear insulated gloves and safety glasses and avoid looking at wires being cut. The ensuing flash can cause burns and blindness.
If the victim must be removed from a live circuit, pull the victim away with a non-conductive material. Use wood, rope, a belt or coat to pull or push the victim away from the current. DO NOT TOUCH the victim. You will receive a shock from current flowing through the victim’s body. After separating the victim from power source, immediately check for signs of a pulse and respiration. If no pulse is present, start Cardiopulmonary Resuscitation (CPR). If a pulse is present, respiration might be restored by using mouth-to-mouth resuscitation. Call for emergency medical assistance.
ASPHYXIATION
Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
Chapter 2: Qualification Plan
Prepared for Thermo King, for validation of temperature–controlled equipment Multi-Temperatures units for truck:
T-1000R Spectrum, T-1200R Spectrum, UT-1200 Spectrum and UT-R Spectrum
Thermo King designs and builds temperature-controlled transport equipment.
These types of equipment can be validated for a specific desired temperature range for the transport of pharmaceutical products.
-
Temperature below -20°C
-
Temperature between +2°C and +8°C
-
Temperature between +15°C and +25 °C
Purpose
This qualification plan describes the procedure for qualifying:
-
a refrigeration truck type ATP-FRC certified consisting of an IR body (0.4 W/m2.K or better insulation) and a refrigerated unit type Thermo King multi-temperatures T-1000R Spectrum or T-1200R Spectrum and UT-R Spectrum.
-
a refrigeration truck type ATP-FNA certified consisting of an IN body (0.7 W/m2.K or better insulation) and a refrigerated unit type Thermo King multi-temperatures UT-1200 Spectrum.
The qualification provides the documented proof of the fact that the respective refrigerated equipment (ATP certified body + Thermo King refrigerated unit) fulfils the user requirements (URS), GDP and GMP requirements for the transport of medicines. This document specifies the responsibilities and activities that are to be carried out for the qualification. The specific activities and criteria are described and documented in the various test cases.
User Requirements Specifications (URS)
The equipment is designed to ensure that pre-temperature-controlled goods maintain an adjustable set temperature both for low and high ambient temperatures (winter -30°C and summer +50°C).
It must be possible to operate the equipment within the following temperature ranges:
-
Temperature below -20°C
-
Temperature between +2°C and +8°C
-
Temperature between +15°C and +25°C
Overall Qualification Results
Unit Specifications | Box Specifications | ||||
Unit Model | Refrigerant | Doors |
Installation class (ATP Mark) |
Internal | |
Front/Back/Side | Minimal | Maximal | |||
T-1000R Spectrum 2 S3+S3 | R-404A/ R-452A |
2 Back + 1 Side | IR (FRC) | 41 m3 | 56 m3 |
T-1200R Spectrum 2 S3+S3 | |||||
UT-1200R Spectrum 2 S3+S3 | IN (FNC) | 48 m3 | 54 m3 | ||
UT-R Spectrum 2 S3+S3 | 2 Back | IR (FRC) | 38 m3 | 56 m3 |
Unit Specifications | Pharmaceutical Temperature Ranges | Test Ambient | |||||
Unit Model | Refrigerant | +15/+25 °C | +2/+8 °C | -20 °C | <-20 °C | Extreme | Extreme |
Ambient | Chilled | Frozen | Deep Frozen | HIGH | LOW | ||
T-1000R Spectrum 2 S3+S3 | R-404A/ R-452A |
Qualified | Qualified | N.A | N.A | 40 °C | –30 °C |
T-1200R Spectrum 2 S3+S3 | Qualified | ||||||
UT-1200R Spectrum 2 S3+S3 | N.A | ||||||
UT-R Spectrum 2 S3+S3 | Qualified | Qualified above –27 °C |
Design Qualification (DQ)
Those equipment-types:
-
A 2 zones IR body of 9.12m x 2.47m x 2.54m (L x W x H) internal dimensions equipped of a Thermo King refrigerated unit T-1000R Spectrum S3+S3 or T-1200R Spectrum S3+S3.
-
A 2 zones IR body of 7.36m x 2.46m x 2.59m (L x W x H) internal dimensions equipped of a Thermo King refrigerated unit UT-R Spectrum S3+S3.
-
A 2 zones IN body of 8.93m x 2.47m x 2.44m (L x W x H) internal dimensions equipped of a Thermo King refrigerated unit UT-1200 Spectrum S3+S3.
The above have been designed and qualified to meet the specific desired temperature ranges for the transport of pharmaceutical products..
Installation Qualification (IQ)
The specific equipment has been installed successfully and was proved to comply with the design qualification and installation qualification of the sample-type equipment.
Operational Qualification (OQ)
The specific equipment has been proven to perform according to the sample-type equipment. Operating guidance and planned maintenance schedule have been provided to ensure a correct use of the equipment during its lifetime.
The conditions of the performance test of the sample-type were defined.
Performance Qualification (PQ)
A basic Performance qualification was performed on the sample-type equipment. The tests were performed according to the test cases defined in the Operational Qualification to simulate most common real–life conditions. Tests were performed in accordance with ATP standards and test method FDX 15-140. The tests were successfully completed.
As a result of the test, some recommendations have been provided to ensure an optimal use of the equipment in the different operational modes.
Qualification with a Sample–Type Approach
Thermo King did use a sample-type approach for the qualification of transport equipment. The sample-type approach consists of performing an initial full qualification on one equipment using the worst–case scenario (including thermal mapping in extreme ambient conditions) and all new or existing equipment of the same design specifications are also qualified once IQ and OQ is completed successfully.
-
A basic PQ for one member of each sample-type, selected as the most critical or challenging application in the family. Basic PQs are empty load temperature mapping performed in temperature-controlled chamber to better simulate worst case conditions.
-
For each new and existing unit, an IQ and OQ must to be completed successfully at a Thermo King authorized workshop location. The verification is conducted by a Thermo King trained technician. The verification includes, above all, the equipment's design specifications and set point verification, sensor calibration and equipment performance check.
Responsibility
The qualification activities will be organized by the qualification team:
Organisation | Activity |
---|---|
Thermo King Pharma Team |
|
Trane Technologies Engineering Center |
|
External pharmaceutical consultant company |
|
Thermo King authorized dealers |
|
Qualification Facility
The qualification tests will be performed at the Trane Technologies Equipment Manufacturing Engineering and Technology Centre, Prague, Czech Republic. This organization is an accredited ATP-test-station and has the IATF 16949 and ISO 17025 certifications.
Chapter 3: Risk Analysis Thermo King
The transport process is defined as a closed temperature-controlled storage box in transit. This box can be used in a single temperature mode and set at four different temperature ranges (Deep Frozen, Frozen, Chilled and Ambient).
The risk analysis based on the Failure Mode and Effects Analysis (FMEA) methodology has been conducted to ensure that potential problems during the process of distributing pharmaceutical products have been considered and addressed before the first use of the transport temperature-controlled equipment.
3.1: Risk Reporting Matrix
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment:
-
A 2 zone IR body (0.4 W/m2.K or better insulation) equipped of a Thermo King refrigerated unit V-300 MAX Spectrum ES150+ES150, V-500 MAX Spectrum ES300+ES300 or V-800 MAX Spectrum. ES400+ES400.
-
A 2 zone IN body (0.7 W/m2.K or better insulation) equipped of a Thermo King refrigerated unit V-300 MAX Spectrum ES200+ES100.
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment:
-
a refrigeration body type (van/truck) with similar or better insulation than ATP IN standards (0.7W/m2. K) and equipped with a refrigerated unit type Thermo King Single-Temperature (V-200 MAX 30/50).
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment:
-
a refrigeration trailer body type with similar or better insulation than ATP standards (0.4W/m².K) and equipped with a refrigerated unit type Thermo King A400, A500 or A-500e Single-Temperature.
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment:
-
a refrigeration trailer body type with similar or better insulation than ATP-FRC standards (0.4W/m2.K), and equipped with a refrigerated unit type Thermo King multi-temperatures unit A-500 Spectrum with S3A remote evaporator
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment, a refrigeration trailer type ATP (FRC) certified (0.4 W/m².K or better insulation) with a refrigerated unit type Thermo King multi-temperature (SLXi Spectrum S3, SLXi Spectrum S6, SLXe Spectrum S3 PTC, SLXe Spectrum S6 PTC, SLXe Spectrum S3, SLX Spectrum ETV S3, SLXe Spectrum S6, SLX Spectrum ETV S6) for the transport of medicinal products.
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment, a refrigeration trailer type ATP (FRC) certified (0.4 W/m².K or better insulation) with a refrigerated unit type Thermo King SLX(e) single-temperature (SLXi300, SLXi400; SLXe300, SLXe400; SLX300 and SLX400) for the transport of medicinal products.
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment:
-
a refrigeration body type (truck) with similar or better insulation than ATP standards (0.4W/m2.K), and equipped with a refrigerated unit type Thermo King T-series SingleTemperature (T-1000R, T-1200R and UT-1200).
-
a refrigeration body type (truck) with similar or better insulation than ATP standards (0.49W/m2.K), and equipped with a refrigerated unit type Thermo King T-series SingleTemperature T-800R.
-
a refrigeration body type (container ) with similar or better insulation than ATP standards (0.4W/m2.K), and equipped with a refrigerated unit type Thermo King T-series SingleTemperature (T-1200R Intermodal)
Thermo King used the risk reporting matrix (see below figure) to identify and classify potential problems while using the specific transport equipment:
-
A 2 zones IR body (0.4 W/m2.K or better insulation) equipped of a Thermo King refrigerated unit T-1000R Spectrum S3+S3, T-1200R Spectrum S3+S3 or UT-R Spectrum S3+S3.
-
A 2 zones IN body (0.7 W/m2.K or better insulation) equipped of a Thermo King refrigerated unit UT-1200 Spectrum S3+S3.
3.2: Identified Risks and Preventative Actions
Closed Box
Process | Defining the Possible Process Problem | Likelihood | Consequence | Risk | Preventative Action |
---|---|---|---|---|---|
Poor design of the transport equipment | Equipment not equivalent to sample-type equipment fully GDP qualified Poor quality finishes (example: bad insulation) | 2 | 4 | 8 (Moderate) |
|
The refrigerated unit has been installed incorrectly on the body | Installation Qualification to be conducted and checked by Thermo King authorized and trained technician. | ||||
Temperature excursions | Unexplained temperature excursions | 3 | 4 | 12 (Moderate) | Datalogger and/or a monitoring system should be installed on the transport equipment. |
Installations obstructing the discharge air flow | Correctly check design specifications of the equipment at point of sales. | ||||
Transport equipment not pre-cooled before loading goods | Pre-cool the transport equipment to the set -temperature before loading the products. | ||||
Products not loaded at correct temperature. | Implement correct loading/unloading practices. | ||||
Inadequate split of the compartments of the transport equipment. | When operating the equipment in multi-temperatures mode, the splitting of the compartment zones should be up to 1/2 of the total body length. | ||||
Settings of the refrigerated unit | Incorrect settings of set points for the temperature range to be maintained | 3 | 4 | 12 (Moderate) | To
maintain the best temperature management within the load-space in
winter and summer time, Thermo King recommends operating with the
following set point temperatures:
|
Incorrect settings of the refrigerated unit then the vehicle is being used in multi-temperatures mode. | At IQ, a specific configuration file is loaded to the controller. When operating the equipment in multi-temperatures mode, ZONE PRIORITY function must be DISABLED. | ||||
Incorrect settings of the refrigerated unit when the vehicle is being used in single temperature mode. | At IQ, a specific configuration file is loaded to the controller. In case of single-temperature operation the unit must run in SINGLE ZONE CONTROL (SZC) mode and the dividing wall must be stowed in such a way that it does not interrupt the airflow from each remote evaporator. For ease of use, SZC mode should be added to the Main (driver) menu. |
Environment
Process | Defining the Possible Process Problem | Likelihood | Consequence | Risk | Preventative Action |
---|---|---|---|---|---|
Temperature Europe |
Expected ambient temperature in the regions can go up to extremes. | 3 | 3 | 9 (Moderate) |
Full Qualification of sample-type equipment (temperature mapping) has been successfully performed at extreme temperatures from -30°C to +40°C. |
Risk of temperature excursion due to high delta difference with inside temperature. |
Refrigeration capacity reserve: Thermo King equipment are designed as standard to overcome temperature met in Middle East Africa regions, with temperatures up to 55°C. |
||||
Solar radiation | In summertime, the effect of solar radiation can have a negative impact on the surface temperature of the equipment. The darker the body colour, the higher temperature increase. | 2 | 3 | 6 (Moderate) | In
DQ, recommended body to be white in colour with a max. 20% decal coverage. Refrigeration capacity reserve: Thermo King equipment are designed as standard with reserve capacity of 75% based on ATP standards. |
Door opening at non-temperature-controlled storage location | Depending on:
|
3 | 4 | 12 (Moderate) | Minimize door opening
time. Load and unload the transport equipment at temperature-controlled loading docks of storage location. Driver training on best loading/unloading practices should be conducted. Door opening tests have been performed to enable better risk management. |
Process / Operational Qualification
Process | Defining the Possible Process Problem | Likelihood | Consequence | Risk | Preventative Action |
---|---|---|---|---|---|
Temperature sensor accuracy check |
Invalid temperature registration | 2 | 4 | 8 (Moderate) | At
IQ check Process, all sensors that are used for temperature control
and monitoring are to be checked. A proof of calibration checks of
each sensor as part of IQ Process. Yearly calibration check of all sensors that are used for temperature control and monitoring. Minimum sensor requirements and location should be in accordance with equipment manufacturer's recommendations. The calibration process should be in line with the EN13486. |
Breakdown / Damage of the equipment | No
regular maintenance of the transport equipment Maintenance not done correctly No use of genuine parts |
2 | 4 | 8 (Moderate) | A
maintenance contract with Thermo King or authorized Thermo King dealer
should be in place. If no maintenance contract, the user of the equipment should prove that he has the right schedule maintenance, repair procedures, genuine parts, breakdown risk assessment, and training in place.The user should be open to regular audits. All replacement parts are to be from genuine manufacturer's parts. |
Lack of hygiene | Risk of contamination of pharmaceutical products | 3 | 3 | 9 (Moderate) | A
Cleaning Procedure should be in place. The internal space is easily accessible for cleaning. The internal surfaces of the refrigeration body are corrosion-resistant and comply with hygiene regulations. Pharmaceutical products should not be transported in a mixed load with food products. |
Incorrect operating mode |
Transport
equipment not used appropriately. Lack of knowledge on how to use the refrigerated unit |
3 | 4 | 12 (Moderate) | Thermo
King provides an Operational manual to use efficiently the transport
equipment. Conduct Training of drivers on GDP and how to use the refrigerated unit. |
Transport equipment used with Frozen -Fresh/Ambient or Ambient/Fresh - Frozen Setpoint during Multi-Temp operation. | 3 | 4 | 12 (Moderate) | During multi-temperature use, it is strictly not permitted if one zone is set for Frozen, the other zone cannot be used for chilled / ambient operation. |
Chapter 4: Design Qualification
Prepared for Thermo King, for validation of temperature controlled equipment Multi-Temperatures units for truck:
T-1000R Spectrum, T-1200R Spectrum and UT-1200 Spectrum
Thermo King designs and builds temperature controlled transport equipment.
These types of equipment can be validated for a specific desired temperature range for the transport of pharmaceutical products.
-
Temperature below -20°C
-
Temperature between +2°C and +8°C
-
Temperature between +15°C and +25 °C
To ensure total flexibility the validation is to be performed at all stated ranges from above.
Scope
The scope of the qualification work will be done to the equipment
(a refrigerated unit designed and built by Thermo King with an ATP
certified body) for the transportation, under temperature restrictions,
of medicines.
A standard configuration is defined
for each group.
4.1: Equipment Specifications
Truck body with Thermo King T-1000R Spectrum or T-1200R Spectrum unit
-
A 2 zones multi-temperatures truck body ATP IR standards with internal dimensions (L x W x H) of 9.12m x 2.47m x 2.54m resulting with an internal surface of 103.73 m2. Owing to the many configurations the bodies' sizes are to be calculated in cubic metres therefore it results with a body with maximum total internal volume of 57 m3 . An internal volume that is smaller is permissible as long as the internal surface is not smaller by more than 20%.
-
A K factor of 0.40 W/m2.K. A better K factor is also permissible.
-
Body white in colour. A maximum 20% of the external surface decal coverage is recommended.
-
Body with double rear doors with door switches. A door arrangement that is better than this is also permissible. Unit is to be configured to force ZONE NULL when opening the doors. Thermal curtains are recommended.
-
A transversal movable dividing wall with a K factor as required and laid out in ATP (see table 1 in section “Detail specifications”). A K factor that is better than those from table 1 is also permissible.
-
Thermo King S3 remote evaporators installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode. ZONE PRIORITY function must be DISABLED.
-
A specific configuration file for pharmaceutical applications used for tighter temperature management.
-
A temperature datalogger which complies with EN12830 standard with at least one sensor in each zone. Thermo King DAS or TouchPrint Datalogger are recommended.
Truck with T-1000R/1200R Spectrum S3+S3
Truck body with Thermo King UT-1200 Spectrum unit
-
A 2 zones multi-temperatures truck body ATP IN standards with internal dimensions (L x W x H) of 8.93m x 2.47m x 2.44m resulting with an internal surface of 99.71 m2. Owing to the many configurations the bodies' sizes are to be calculated in cubic meters therefore it results with a body with maximum total internal volume of 54 m3. An internal volume that is smaller is permissible if the internal surface is not smaller by more than 20%.
-
A K factor of 0.70 W/m2.K. A better K factor is also permissible.
-
Body white in colour. A maximum 20% of the external surface decal coverage is recommended.
-
Body with double rear doors and single side door with door switches. A door arrangement that is better than this is also permissible. Unit is to be configured to force ZONE NULL when opening the doors. Thermal curtains are recommended.
-
A transversal movable dividing wall with a K factor as required and laid out in ATP (see table 1 in section “Detail specifications”). A K factor that is better than those from table 1 is also permissible.
-
Thermo King S3 remote evaporators installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode. ZONE PRIORITY function must be DISABLED.
-
A specific configuration file for pharmaceutical applications used for tighter temperature management.
-
A temperature datalogger which complies with EN12830 standard with at least one sensor in each zone. Thermo King DAS or TouchPrint Datalogger are recommended.
Truck with UT-1200 Spectrum S3+S3
Truck body with Thermo King UT-R Spectrum S3+S3 unit
-
2 zone multi-temperatures truck body ATP IR standards with internal dimensions (L x W x H) of 7.50m x 2.59m x 2.81m resulting with an internal surface of 95.56 m2. Owing to the many configurations the bodies’ sizes are to be calculated in cubic meters therefore it results with a body with maximum total internal volume of 46.96 m3 . An internal volume that is smaller is permissible if the internal surface is not smaller by more than 20%.
-
A K factor of 0.40 W/m².K. A better K factor is also permissible.
-
Body white in colour. A maximum 20% of the external surface decal coverage is recommended.
-
Body with double rear doors with door switches. A door arrangement that is better than this is also permissible. Unit is to be configured to force ZONE NULL when opening the doors. Thermal curtains are recommended.
-
A transversal movable dividing wall with a K factor as required and laid out in ATP (see table in section “Detail specifications”). A K factor that is better than those from table 1 is also permissible.
-
Thermo King S3 remote evaporators installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode. ZONE PRIORITY function must be DISABLED.
-
A specific configuration file for pharmaceutical applications used for tighter temperature management.
-
A temperature datalogger which complies with EN12830 standard with at least one sensor in each zone. Thermo King DAS, TouchPrint Datalogger or TouchLog are recommended.
Temperature Range Table
Truck body with Thermo King T-1200R Spectrum unit
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Average Deviation from Setpoint |
Temperature below ‐20°C | +40°C / -30°C | -25°C | +5/-6°C of setpoint |
Temperature between 2°C and 8°C | +40°C / -30°C | +6°C | +2/-4°C of setpoint |
Temperature between 15°C and 25°C | +40°C / -30°C | +20°C | +3/-5 °C of setpoint |
Truck body with Thermo King T-1000R Spectrum unit
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Average Deviation from Setpoint |
Temperature between 2°C and 8°C | +40°C / -30°C | +6°C | +2/-3°C of setpoint |
Temperature between 15°C and 25°C | +40°C / -30°C | +20°C | +2/-4°C of setpoint |
Truck body with Thermo King UT-1200 Spectrum unit
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Average Deviation from Setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+5°C |
+/-3°C of setpoint |
Temperature between 15°C and 25°C |
+40°C / -30°C |
+20°C |
+2/-3°C of setpoint |
Truck body with Thermo King UT-R Spectrum unit
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Average Deviation from Setpoint |
Temperature above -27°C |
+30°C / -30°C |
-29 °C |
+/-3°C of setpoint |
Temperature below -20°C |
+40°C / -30°C |
-24 °C |
+4/-6°C of setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+5°C |
+/- 3°C of setpoint |
Temperature between 15°C and 25 °C |
+40°C / -30°C |
+20 °C |
+/- 5°C of setpoint |
4.2: Additional Validations and Variations
Addition of truck body ATP IR standards with UT-1200 Spectrum S3+S3
2 zones multi-temperatures truck body ATP IR standard with a 0.40 W/m2 K insulation or better with UT-1200 Spectrum S3+S3 is approved in parallel because it offers better insulation and ensure equivalent temperature management.
Addition of Whisper Option for T-1000R Spectrum and T-1200R Spectrum
T-1000R Spectrum S3+S3 Whisper and T-1200R Spectrum S3+S3 Whisper are approved in parallel.
Addition of rear rolling doors in lieu et place of double rear doors
If K factor co-efficient remains below 0.40 W/m2 K and therefore the vehicle is FRC declared, body equipped with rear rolling doors instead of double rear doors are approved in parallel.
Variations on body sizes
Smaller body sizes appropriate to the unit design are also included because the performance will be improved as body size reduces:
-
T-1000R Spectrum S3+S3 and T-1200R Spectrum S3+S3 should not be used on a body volume that is less than 45m3 and not more than 57m3; this would require a different specification unit.
-
UT-1200 Spectrum S3+S3 should not be used on a body volume that is less than 43m3 and not more than 54m3; this would require a different specification unit.
4.3: Detailed Specifications
Diving Wall ATP Specification
Diving wall ATP Specification
K factor coefficient | Minimum thickness of diving wall | ||
Removable | Fixed | ||
GRP floor Longitudinal |
2.0 W/m2.K |
1.5 W/m2.K |
25 mm |
GRP floor Transversal |
2.6 W/m2.K |
1.5 W/m2.K |
40 mm |
Aluminium floor Longitudinal |
3.0 W/m2.K |
2.0 W/m2.K |
25 mm |
Aluminium floor Transversal |
3.2 W/m2.K |
2.0 W/m2.K |
40 mm |
Diving wall coefficients include a safety margin to allow for degradation and thermal leakages.
Refrigerated Unit capacity:
Refrigeration capacities 1 | |||
Refrigerant | R-404A/R-452A | ||
Unit Model | T-1200R Spectrum S3+S3 | ||
Total Nominal | Remote Evaporator S3 | ||
Capacity on engine power | 0 °C | 12 080 W | 8 120 W |
-20 °C | 7 620 W | 4 640 W | |
Capacity on electric standby | 0 °C | 7 560 W | 7 163 W |
-20 °C | 4 720 W | 4 010 W | |
Unit Model | T-1000R Spectrum S3+S3 | ||
Total Nominal | Remote Evaporator S3 | ||
Capacity on engine power | 0 °C | 9 990 W | 7 540 W |
-20 °C | 5 790 W | 4 230 W | |
Capacity on electric standby | 0 °C | 6 280 W | 6 190 W |
-20 °C | 3 860 W | 3 490 W | |
Unit Model | T-1200R Spectrum S3+S3 | ||
Total Nominal | Remote Evaporator S3 | ||
Capacity on engine power | 0 °C | 10 560 W | 7 720 W |
-20 °C | 6 030 W | 4 410 W | |
Capacity on electric standby | 0 °C | 7 560 W | 6 840 W |
-20 °C | 4 720 W | 3 820 W | |
Airflow volume at 0 Pa static pressure |
2 000 m3/hr |
||
Discharge velocity (Air throw) | 9.50 m/sec | ||
Refrigerant | R-452A | ||
Unit Model | UT-R Spectrum S3+S3 | ||
Total Nominal | Remote Evaporator S3 | ||
Capacity on engine power | 0 °C | 11 302 W | 7 780W |
-20 °C | 6 374 W | 4 463 W | |
Capacity on electric standby |
0 °C | 10 249W | 6 861 W |
-20 °C | 4 497 W | 3 652 W | |
Airflow volume at 0 Pa static pressure |
2 350 m3/hr |
||
Discharge velocity (Air throw) |
9.50 m/sec |
||
Maximum zone length (2) | 5.50 m | ||
1 At +30°C ambient temperature under ATP conditions |
|||
2 Maximum recommended dimensions: these are guidelines based on airflow and air velocity requirements based upon the following assumptions: K factor = 0.4W/m2.K, internal height up to 2.5 m, width up to 2.5 m, zero heat load from produce carried. For each application, a heat load calculation must be performed (applies to all listed unit models). |
4.4: Truck Multi-temperatures and GDP Qualified Configurations
Units and Evaporator Dimensions - T1000R Spectrum and T-1200R Spectrum
Units and Evaporator Dimensions - UT Spectrum
Units and Evaporator Dimensions - UT-R Spectrum
Chapter 5: Installation Qualification
Prepared for Thermo King, for validation of temperature-controlled equipment Multi-Temperatures units for truck:
T-1000R Spectrum, T-1200R Spectrum, UT-1200 Spectrum and UT-R Spectrum
For each individual equipment (truck + body + refrigerated unit) a specific TK PharmaSolutions - IQOQ Check-MUL document must be completed by the Thermo King official dealer to confirm that Installation Qualification conforms to the requirements of the Design Qualification: GDP-TK-DQ-SP-MT. The latest valid revision of this document must be used and is available from Thermo King EMEA InfoCentral intranet.
The vehicle has been inspected and conforms to the design qualification document GDP-TK-DQ-SP-MT. Photographic evidence is available on request.
-
Door switches are installed, and the unit is configured to force ZONE NULL when opening the doors. Thermal curtains are recommended as described in GDP-TK-DQ-SP-MT.
-
The transversal movable dividing wall as defined in GDP-TK-DQ-SP-MT is installed and displacement is in accordance with Load Space Considerations described in GDP-TK-OQ-SP-MT.
-
Thermo King S3 remote evaporators are installed in each of the 2 zones. Evaporator fans are to be configured to run in NULL mode as described in GDP-TK-DQ-SP-MT.
-
The specific configuration file as described in GDP-TK-DQ-SP-MT is loaded to the unit controller.
-
A temperature datalogger as described in GDP-TK-DQ-SP-MT with at least one sensor in each zone is installed and configured as per customer settings. Thermo King DAS or TouchPrint Datalogger are recommended.
Chapter 6: Operational Qualification
Prepared for Thermo King, for validation of temperature-controlled equipment Multi-Temperatures units for truck:
T-1000R Spectrum, T-1200R Spectrum, UT-1200 Spectrum and UT-R Spectrum
6.1: Description of the Qualified Operation
The truck shall be used:
-
For transport of pharmaceuticals (in combination with medical devices)
-
To maintain and control air temperature at a set temperature.
-
In multi-temperature operation (< -20°C, +2°C to +8 °C or +15°C to +25°C) in two compartments.
-
At ambient temperature between -30°C and +40°C.
-
The vehicle will be used for transportation between temperature-controlled loading docks of storage locations.
-
According to the drivers instructions supplied by Thermo King on use of Thermo King equipment.
The objective of this qualification is to successfully qualify the designed use of this equipment.
The Operational Qualification conforms to the requirements of the Design Qualification: GDP-TK-DQ-SP-MT.
6.2: Support of the Defined Aspects of Use
-
For transport of pharmaceuticals (in combination with medical devices).
-
Combination of pharmaceuticals and medical devices in one load is approved. Mixing loads of food and chemical substances is not permitted even when the compartments are separated as a multi-temperatures load.
-
-
The load space should be always kept clean at all times and only cleaning agents that will not affect the products should be used.
-
To maintain and control air temperature at a set temperature
-
The products (pharmaceuticals) will be loaded at the correct temperature because they are leaving a temperature-controlled storage location. It is stated that the refrigeration unit and box is used to maintain and not change the temperature of the products. The trailer is not designed for cooling down or warming up pharmaceuticals, and therefore it should not be used for this purpose. However, there is reserve capacity to overcome unscheduled temperature changes within the air pocket surrounding the load.
-
-
This unit+body is qualified in multi-temperatures and single-temperature modes based on the details below:
-
In multi-temperature mode:
In case of multi-temperatures operation, the dividing wall must be locked in vertical position and setpoint must be set according to the requested range in each zone. ZONE PRIORITY function must be DISABLED.
-
-
For T-1200R Spectrum S3+S3:
-
Ranges < -20°C, +2°C to +8 °C or +15°C to +25°C can be operated in any of the 2 zones.
-
-
For T-1000R Spectrum S3+S3 and UT-1200 S3+S3:
-
Ranges +2°C to +8 °C or +15°C to +25°C can be operated in any of the 2 zones.
-
The range < -20°C cannot be operated.
-
In single-temperature mode:
In case of single-temperature operation the unit must run in SINGLE ZONE CONTROL (SZC)mode and the dividing wall must be stowed in such a way that it does not interrupt the airflow from each remote evaporator. For ease of use, SZC mode should be added to the Main (driver) menu.
-
-
For T-1200R Spectrum S3+S3:
-
Ranges < -20°C, +2°C to +8 °C or +15°C to +25°C can be operated.
-
-
For T-1000R Spectrum S3+S3 and UT-1200 S3+S3:
-
Ranges +2°C to +8 °C or +15°C to +25°C can be operated.
-
The range < -20°C cannot be operated:
-
-
For UT-R Spectrum S3+S3:
-
Ranges +2°C to +8 °C or +15°C to +25°C can be operated in any of the 2 zones at the same time.
-
Ranges +2°C to +8 °C or +15°C to +25°C cannot be used if one zone is set for frozen.
-
Ranges < -20°C can be operated only with single zone control.
-
In case of single zone use (one zone, both compartments) the unit must run in SINGLE ZONE CONTROL (SZC) mode and the dividing wall must be stowed in such a way that it does not interrupt the airflow from each remote evaporator. For ease of use, SZC mode should be added to the Main (driver) menu.
-
-
When operating the equipment in multi-temperatures mode, the splitting of the compartment zones should be up to 1/2 of the total body length:
-
At ambient temperature between -30°C and +40 °C.
-
This GDP qualification is performed for use in the ambient temperatures as tested. To provide qualification for the expected ambient temperatures in these regions the qualification test temperatures will be performed in the following manner, minimum to be set at -30°C (to simulate average winter temperatures in Northern Europe) and maximum +40 °C (to simulate average high summer temperatures in the South of Europe).
-
-
The vehicle will be used for transportation between temperature-controlled loading docks of storage locations.
-
Door openings can have a major effect on the temperature inside the body, depending on the difference in ambient temperature and temperature inside the box. To minimise this effect, this is recommended to open doors of the truck only at loading and unloading at temperature-controlled warehouse. In these warehouses the product and the environment are temperature controlled.
-
If the vehicle is to be used with multiple door openings in a non-controlled environment, based on the results of a risk analysis a complementary Performance Qualification may have to be performed by the customer.
-
-
The equipment must be used according to the driver's instructions supplied by Thermo King on use of Thermo King Equipment. These driver instructions are to be found in the specific Operator Manual.
-
The equipment must be run and checked to ensure that all elements are functioning correctly.
-
The load space considerations indicated here after must also be considered.
6.3: Load Space Consideration
-
The load space should be kept always clean at all times and only cleaning agents that will not affect the products should be used.
-
A compartment moveable dividing wall is used in multi-temperatures applications to separate the compartments to allow them to operate at different temperatures. This dividing wall must not be positioned any less than 1300mm from the air outlet of the remote zone evaporator.
-
A minimum of 100 mm clearance must be provided between the top of the load and the air intake of the zone remote evaporator.
-
An air gap between the load and the walls should be always maintained :
-
If the dividing wall is positioned tightly against the load, satisfactory air circulation and temperature management will not be achieved.
-
If the load is positioned tightly against the body internal walls, satisfactory air circulation and temperature management will not be achieved.
-
-
If the unit is to be used as a single-temperature mode, the dividing wall should be stowed in such a way that it does not interrupt the airflow from each remote evaporator.
Recommended position of dividing wall in single temperature operation
6.4: Layout of Sample-type Truck Qualification
The objective of this GDP qualification is to successfully qualify the designed configuration of the equipment mentioned in the Design Qualification: GDP-TK-DQ-SP-MT.
For this qualification three issues are important:
-
The flow of temperature-controlled air in the load space must reach all parts of the load space. Therefore, a fixed return air system is essential.
-
The capacity of the unit that is used to manage the temperature within the load space must be sufficient to maintain the products at the set temperature range recommended by the manufacturer of the product (pharmaceutical company). Therefore, the base colour white plus allowable 20% decal coverage is set to the DQ. Other darker colours would decrease the cooling capacity of the truck.
-
The temperature logging equipment used for the calibration process must be calibrated to each temperature range. This will be checked and confirmed during the OQ (Operational Qualification) process.
The equipment must comply with the three requirements as laid out above and should be measured with calibrated temperature dataloggers and must be registered as such. This will be checked and confirmed during the OQ (Operational Qualification) process.
6.5: Technical and User Data
Risk Management for Transport Equipment
Assumptions that are made:
-
The temperature qualification is performed in an empty body, as this is considered as the worst-case scenario to higher temperatures variation.
-
The products (pharmaceuticals) will be loaded at the correct temperature, because they are leaving a temperature-controlled storage. It is stated that the refrigeration unit and box is used to maintain the temperature of the products do not change the temperature, though this is possible over time.
-
The of the physical state (dry, liquid), pharmaceutical forms (tablets, capsules, crèmes) of the medicines, the primary package material (plastic, glass) used to pack these are enormous. The secondary package materials will probably be boxes made from cardboard.
-
The capacity of a transport refrigeration unit as well as the minimum insulation of a body is regulated by ATP testing standards. Because this guideline is the current standard for temperature testing, this test protocol is used as the basis for GDP qualification.
-
At ambient temperature between -30°C and +40 °C
-
Worst-case scenario for multi-temperatures trucks:
The greatest difference in the set-temperatures between zone 1 and zone 2 and in two extreme ambient temperatures.
-
Worst-case scenario of tests for Multi temperature Trucks
Ambient temperature | Zone 1 | Zone 2 | |
1 | +40 °C | ‐25°C | +20 °C |
2 | ‐30 °C | ‐25°C | +20 °C |
Acceptance Criteria
Regarding the acceptance criteria considered in Thermo King Protocol, the air temperature should remain within the required temperature range. For example, if the requirement is for temperature range +2.0°C to +8.0°C, the minimum air temperature recorded should not be below +2.0°C, and the maximum should not exceed +8.0°C.
Qualification Test for Multi-temperature Vehicles
-
Deviation of registered data of thermocouples 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30 should not exceed maximum deviation as mentioned in section “Acceptance Criteria”.
-
The average temperature of all thermocouples should not exceed maximum deviation as mentioned in section “Acceptance Criteria”.
-
Ambient temperature is to be logged. The logged temperature should not exceed +/-2 °C of required temperature.
-
Return air and discharge air temperature of the unit evaporators is to be logged: Temperatures should not exceed the requirement for the specific temperature being tested.
-
Test time is 2.5 hours in steady state.
Multi-temperatures operation for T-1200R Spectrum S3+S3
Zones | Zone 1 | Zone 2 |
Length |
1/2 |
1/2 |
Zone 2 Evaporators | S3 | S3 |
Setpoints | +20°C | ‐25°C |
+20°C | +6°C | |
‐25°C | +6°C | |
Ambient Temperature 1 | +40°C | +40°C |
Ambient Temperature 2 | ‐30°C | ‐30°C |
Multi-temperatures operation for UT-R Spectrum S3+S3
Zones | Zone 1 | Zone 2 |
Length |
1/2 |
1/2 |
Zone 2 Evaporators | S3 | S3 |
Setpoints | +5°C | +20°C |
+ 20°C | + 5°C | |
- 25°C | - 25°C | |
Ambient Temperature 1 | +40°C | +40°C |
Ambient Temperature 2 | ‐30°C | ‐30°C |
Multi-temperatures operation for T-1000R Spectrum S3+S3 and UT-1200 S3+S3
Zones | Zone 1 | Zone 2 |
Length |
1/2 |
1/2 |
Zone 2 Evaporators | S3 | S3 |
Setpoints | +20°C | +6°C |
Ambient Temperature 1 | +40°C | +40°C |
Ambient Temperature 2 | ‐30°C | ‐30°C |
Single temperature operation for T-1200R Spectrum S3+S3
Zones | Unique Zone | |
Length | Total length | |
Evaporator | S3 | S3 |
Setpoints |
+20°C |
|
+6°C |
||
‐25°C |
||
Ambient Temperature 1 | +40°C | |
Ambient Temperature 2 | ‐30°C |
Single temperature operation for T-1000R Spectrum S3+S3 and UT-1200 S3+S3
Zones | Unique Zone | |
Length | Total length | |
Evaporator | S3 | S3 |
Setpoints |
+20°C |
|
+6°C |
||
Ambient Temperature 1 | +40°C | |
Ambient Temperature 2 | ‐30°C |
Single temperature operation UT-R S3+S3
Zones | Unique Zone | |
Length | Total length | |
Evaporator | S3 | S3 |
Setpoints |
+20°C |
|
+5°C |
||
- 25°C |
||
- 29°C |
||
Ambient Temperature 1 | +40°C | |
Ambient Temperature 2 | ‐30°C |
6.6: Thermocouple Locations
There is no information in GDP guideline as to location of or how many thermo couplings for temperature measurement should be inserted into the load space during the qualification test. Therefore, the locations of the thermo couplings are referred to as in the ATP guideline. ATP is using standard NFX 15-140. This means 15 thermocouples per zone are utilised in the box during the multi-temperature’s qualification test and 25 thermocouples for the single temperature qualification test. These loggers are calibrated, and the calibration documents are available under request.
T-1200R S3+S3, T-1000R S3+S3, UT-1200 S3+S3 and UT-R Spectrum S3+S3 thermocouple locations multi-temperatures operation Z1 length = 1/2 / Z2 length = 1/2 of total length

-
EAIT_1 Return air sensor Zone 1
-
EAOT_1 Supply air sensor Zone 1
-
EAIT_2 Return air sensor Zone 2
-
EAOT_2 Supply air sensor Zone 2
-
Thermocouples Ti1_01, Ti1_06, Ti1_11, Ti2_01, Ti2_06 and Ti2_11 are located at Top right corner 150 mm away from any wall/door.
-
Thermocouples Ti1_02, Ti1_07, Ti1_12, Ti2_02, Ti2_07 and Ti2_12 are located at Right bottom corner between boxes and wall.
-
Thermocouples Ti1_03, Ti1_08, Ti1_13, Ti2_03, Ti2_08 and Ti2_13 are located at Left bottom corner between boxes and wall.
-
Thermocouples Ti1_04, Ti1_09, Ti1_14, Ti2_04, Ti2_09 and Ti2_14 are located at Top left corner 150 mm away from any wall/door.
-
Thermocouples Ti1_05, Ti1_10, Ti1_15, Ti2_05, Ti2_10 and Ti2_15 are located in the centre.
T-1200R S3+S3, T-1000R S3+S3, UT-1200 S3+S3 and UT-R Spectrum S3+S3 thermocouple locations, single temperature operation

-
EAIT_1 Return air sensor
-
EAOT_1 Supply air sensor
-
EAIT_2 Return air sensor (SZC)
-
EAOT_2 Supply air sensor (SZC)
-
Thermocouples Ti1_01, Ti1_06, Ti1_11, Ti1_16 are located at Top right .
-
Thermocouples Ti1_02, Ti1_07, Ti1_12, Ti1_17 are located at Right bottom corner 150 mm from any wall.
-
Thermocouples Ti1_03, Ti1_08, Ti1_13, Ti1_18 are located at Left bottom corner between boxes and wall.
-
Thermocouples Ti1_04, Ti1_09, Ti1_14, Ti1_19 are located at Top left corner between boxes and wall.
-
Thermocouples Ti1_05, Ti1_10, Ti1_15, Ti1_20 are located in the centre.
6.7: Operational Qualification on the Field
For each individual equipment (vehicle + refrigerated unit) a specific TK PharmaSolutions - IQOQ Check-MUL document must be completed by the Thermo King official dealer. The latest valid revision of this document must be used and is available from Thermo King EMEA InfoCentral intranet.
This document confirms that:
-
Installation is conducted as per GDP-TK-IQ-SP-MT.
-
A calibration check has been performed in an empty body for each qualified range. This calibration check is performed for the controlling sensors and the datalogger sensors and the results are attached to this document. The results are available on request in electronic format.
-
All required risk management and due diligence protocols are in place and comply with the GDP requirements. This protocol’s minimum requirements should be:
-
Scheduled maintenance
-
Breakdown repairs
-
Annual 3-temperatures calibration check
-
Availability of service history
-
Asset management
-
Chapter 7: Performance Qualification
Prepared for Thermo King, for validation of temperature-controlled equipment Multi-Temperatures units for truck:
T-1000R Spectrum, T-1200R Spectrum, UT-1200 Spectrum and UT-R Spectrum units
7.1: Introduction
Thermo King designs and builds temperature-controlled transport equipment.
These types of equipment can be validated for a specific desired temperature range for the transport of pharmaceutical products.
Due to the fact that several test were performed on the different units in time, not all the tests are performed under the same circumstances.
Overview: tests performed with transversal layout
Unit | Ambient Temperature | Set Temperature | Door Openings | Failure Test | Hot and Cold Spots |
---|---|---|---|---|---|
E-200 Max
Spectrum Zone 1: Zone 2= 50%:50% |
‐30° ‐20° ‐10° +15° +40° |
+4 °C +20°C |
1 and 5 min. ‐‐ 1 and 5 min. ‐‐ 1 and 5 min. |
Done Done Done Done Done |
‐‐ |
V300 Max Spectrum
(IR) Zone 1: Zone 2= 20%:80% |
‐30° +15° +40° |
+6 °C +20°C |
‐‐ ‐‐ 15 min. |
‐‐ ‐‐ Done |
‐‐ |
V500 Max Spectrum
(IR) Zone 1: Zone 2= 60%:40% |
‐30° +15° +40° |
+6 °C +20°C |
2 and 5 min. 2, 5 and 15 min. 2 and 15 min. |
Done Done Done |
‐‐ |
V800 Max Spectrum
(IN) Zone 1: Zone 2= 50%:50% |
‐30° +45° |
+5 °C +20°C |
5 and 10 min. 5 and 10 min. |
Done Done |
Done |
V300 Max Spectrum (IN) Zone 1: Zone 2= 60%:40% |
‐20° +35° |
+5 °C +20°C |
1 and 2 min. 1 and 2 min. |
Done ‐‐ |
‐‐ |
Overview tests performed
Unit | Ambient temp | Set temp | Door openings | Failure test | Hot and Coldspot |
T-800R | +40°C, -30°C | +20°C, +5 °C, -25°C | 5 min and 10 min | + | + |
T-1000R | +45°C , +40°C, -30°C | +20°C, +5 °C, -25°C | 5 min and 10 min | + | -. |
T-1200R Intermodal | +40°C, -30°C | +20°C, +5 °C, -25°C | - | - | - |
UT-1200R | +45°C, +40°C, -30°C | +20°C, +5 °C, -25°C | 2, 5 and 10 min | + | + |
Overview tests performed
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between ‐20°C | +40°C / ‐25°C | ‐25°C | ‐1/+0.5°C of setpoint |
Temperature between +2°C and +8°C | +40°C / ‐25°C | +5°C | ‐/+0.5°C of setpoint |
Temperature between +15°C and +25°C | +40°C / ‐25°C | +20°C | ‐/+1 °C of setpoint |
Overview tests performed
Temperature Range | Extreme Ambient Temperature | ZONE 1 setpoint | Max Setpoint deviation ZONE 1 | ZONE 2 setpoint | Max Setpoint deviation ZONE 2 |
---|---|---|---|---|---|
Temperature below -20°C | +43°C | ‐23°C | +3°C /-3°C of setpoint | off | - |
-30°C | -23°C | +1°C /-1°C of setpoint | off | - | |
Temperature between +2°C and +8°C | +45°C | +5°C | +2°C /-2.5°C of setpoint | off | - |
-30°C | +5°C | +1°C /-2.5°C of setpoint | off | - | |
Temperature between +15°C and +25 °C | +45°C | +20°C | +1°C /-1 °C of setpoint | off | - |
-30°C | +20°C | +1°C /-3 °C of setpoint | off | - |
Temperature below -20°C | -30°C | -23 °C | +2°C /-2 °C of setpoint | +5°C | +2°C /-2°C of setpoint |
+20°C | +3°C /-3°C of setpoint | ||||
+45°C | -23 °C | +3°C /-1 °C of setpoint | +5°C | +3°C /-3°C of setpoint | |
+20°C | +3°C /-2°C of setpoint | ||||
Temperature between +2°C and +8°C | +45°C | +5°C | +2°C /-1 °C of setpoint | +20°C | +1°C /-2°C of setpoint |
+40°C | +5°C | +2°C /-1.5 °C of setpoint | -25°C | +1°C /-3°C of setpoint | |
-30°C | +5°C | +2°C /-2 °C of setpoint | +20°C | +4°C /-4°C of setpoint | |
Temperature between +15°C and +25 °C | +45°C | +20°C | +1°C /-1 °C of setpoint | +5°C | +2°C /-2°C of setpoint |
-30°C | +20°C | +1°C /-2 °C of setpoint | +5°C | +2°C /-2°C of setpoint |
Trailer Body with SLXi Spectrum / SLXe Spectrum PTC
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between ‐20°C | +40°C / ‐30°C | ‐25°C | +4/‐3°C of setpoint |
Temperature between +2°C and +8°C | +40°C / ‐30°C | +6°C | +2/‐3°C of setpoint |
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +3/‐4°C of setpoint |
Trailer Body with SLXe Spectrum / SLX Spectrum ETV
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between ‐20°C | +40°C / ‐30°C | ‐25°C | +5/‐2°C of setpoint |
Temperature between +2°C and +8°C | +40°C / ‐30°C | +6°C | +2/‐3°C of setpoint |
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +/‐4°C of setpoint |
Test Results - Trailer Body of 13.6 m with SLXi 300
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between 15°C and 25°C | +45°C / ‐30°C | +20°C | +/‐1°C of setpoint |
Temperature between +2°C and +8°C | +45°C / ‐30°C | +5°C | +/‐1°C of setpoint |
Temperature below ‐20°C | +40°C / ‐30°C | –25°C | +/‐3°C of setpoint |
Test Results - Trailer Body of 13.6 m with SLXe 300
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between 15°C and 25°C | +45°C / ‐30°C | +20°C | +/‐2°C of setpoint |
Temperature between +2°C and +8°C | +45°C / ‐30°C | +4°C | +/‐2°C of setpoint |
Temperature below ‐20°C | +45°C / ‐30°C | –25°C | +1/‐3°C of setpoint |
Test Results - Truck body of 42m3 with T-800R
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +/-4°C of set point |
Temperature between +2°C and +8°C | +40°C / ‐30°C | +5°C | +/-3°C of set point |
Temperature between ‐20°C | +40°C / ‐30°C | ‐25°C | +2°C/-4°C of set point |
Test Results - Truck body of 48m3 with T-1000R
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between +15°C and +25°C | +45°C / -30°C | +20°C | +/-2°C of set point |
Temperature between +2°C and +8°C | +40°C / ‐30°C | +5°C | +/-2°C of set point |
Temperature between ‐20°C | +40°C / ‐30°C | ‐25°C | +/-4°C of set point |
Test Results - Truck body of 46m3 with UT-1200R
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between +15°C and +25°C | +45°C / -30°C | +20°C | +2/-1°C of set point |
Temperature between +2°C and +8°C | +45°C / -30°C | +5°C | +2/-2°C of set point |
Temperature between ‐20°C | +45°C / -30°C | ‐25°C | +2/-3°C of set point |
Test Results – 45 feet container with T-1200R
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max deviation of Setpoint |
---|---|---|---|
Temperature between +15°C and +25°C | +40°C / ‐30°C | +20°C | +/-2°C of set point |
Temperature between +2°C and +8°C | +40°C / ‐30°C | +5°C | +2/-1°C of set point |
Temperature between ‐20°C | +40°C / ‐30°C | ‐25°C | +/-4°C of set point |
Truck body with T-1000R Spectrum S3+S3
Temperature Range |
Extreme Ambient Temperature |
Recommended Setpoint |
Max Average Deviation from Setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+6°C |
+2/-3°C of setpoint |
Temperature between 15°C and 25°C |
+40°C / -30°C |
+20°C |
+2/-3°C of setpoint |
Truck body with T-1200R Spectrum S3+S3
Temperature Range |
Extreme Ambient Temperature |
Recommended Setpoint |
Max Average Deviation from Setpoint |
Temperature below -20°C |
+40°C / -30°C |
-25°C |
+5/-5°C of setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+6°C |
+2/-4°C of setpoint |
Temperature between 15°C and 25°C |
+40°C / -30°C |
+20°C |
+3/-5°C of setpoint |
Truck body with UT-1200 Spectrum S3+S3
Temperature Range |
Extreme Ambient Temperature |
Recommended Setpoint |
Max Average Deviation from Setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+6°C |
+3/-3°C of setpoint |
Temperature between 15°C and 25°C |
+40°C / -30°C |
+20°C |
+3/-5°C of setpoint |
Truck body with Truck body with UT-R Spectrum S3+S3
Temperature Range |
Extreme Ambient Temperature |
Recommended Setpoint |
Max Average Deviation from Setpoint |
Temperature above -27°C |
+30°C / -30°C |
-29 °C |
+/- 3°C of setpoint |
Temperature below -20°C |
+40°C / -30°C |
-24 °C |
+4/-6°C of setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+5°C |
+/-3°C of setpoint |
Temperature between 15°C and 25°C |
+40°C / -30°C |
+20°C |
+/-5°C of setpoint |
Truck body with Thermo King UT-R Spectrum unit
Temperature Range | Extreme Ambient Temperature | Recommended Setpoint | Max Average Deviation from Setpoint |
Temperature above -27°C |
+30°C / -30°C |
-29 °C |
+/-3°C of setpoint |
Temperature below -20°C |
+40°C / -30°C |
-24 °C |
+4/-6°C of setpoint |
Temperature between 2°C and 8°C |
+40°C / -30°C |
+5°C |
+/- 3°C of setpoint |
Temperature between 15°C and 25 °C |
+40°C / -30°C |
+20 °C |
+/- 5°C of setpoint |
Overview tests performed
Climate Controlled Room (CCR) temperature | Setpoint | Test Type | Test |
7.5 °C | 32.5 °C | A K coefficient equal to or less than 0.40W/m–2k-1 is required. If not, tests with setpoint above 0 °C can only be completed. | K |
-30 °C | 20 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E01 |
-30 °C | 20 °C | Doors Opening 7 min | E02 |
-30 °C | 20 °C | Failure Mode | E03 |
-30 °C | 5 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E04 |
-30 °C | 5 °C | Doors Opening 7 min | E05 |
-30 °C | 5 °C | Failure Mode | E06 |
-30 °C | -22 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E07 |
30 °C | -25 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E08 |
30 °C | -25 °C | Doors Opening 3 min | E09 |
30 °C | -25 °C | Failure Mode | E10 |
45 °C | 5 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E11a |
45 °C | 5 °C | Doors Opening 7 min | E12 |
45 °C | 5 °C | Failure Mode | E13 |
45 °C | 20 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E14a |
45 °C | 20 °C | Doors Opening 7 min | E15 |
45 °C | 20 °C | Failure Mode | E16 |
50 °C | 20 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E14b |
50 °C | 4 °C | Stability Test (2.5 hours) (Electric/ Continuous) | E11b |
Test Results – IN Truck body of 5.21m3 with V-200 MAX
Extreme Ambient | Recommended Setpoint | Permitted Deviation from Setpoint | Temperature Managemant | |
Min | Max | |||
-30 °C | 20 °C | 17.0 °C | 23.0 °C | +15 °C to +25 °C |
-30 °C | 5 °C | 3.0 °C | 7.0 °C | +2 °C to +8 °C |
-30 °C | -22.5 °C | -25.0 °C | -22.0 °C | Above -20 °C |
30 °C | -25 °C | -25.0 °C | -22.0 °C | Above -20 °C |
50 °C | 20 °C | 17.0 °C | 23.0 °C | +15 °C to +25 °C |
50 °C | 4 °C | 2.1 °C | 7.0 °C | +2 °C to +8 °C |
7.2: Purpose
This protocol defines the qualification of the equipment (a refrigerated unit designed and built by Thermo King with an ATP certified body) for the transportation, under temperature restrictions, of medicines.
The qualification is based on the following documents: GDP-TK-VMP, GDP-TK-DQ-SP-MT, GDP-TK-IQ-SP-MT and GDP-TK-OQ-SP-MT.
7.3: Scope
The scope of the qualification work will be done to the equipment: a refrigerated unit designed and built by Thermo King with an ATP certified body.
A standard configuration is defined for each group.
For multi-temperatures truck the specifications are as per the Design Qualification GDP-TK-DQ-SP-MT.
7.4: Evaluation of the Qualification Test
T-1200R Spectrum S3+S3 - Multi-temperatures Tests
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C | +20°C | +17/+22 °C | +19 °C | -2 /+1°C of setpoint |
+20°C | +17/+22 °C | +20 °C | -2 /+1°C of setpoint | |
+6°C | +2/+8 °C | +6 °C | -2 /+1°C of setpoint | |
-30°C | +20°C | +15/+21 °C | +18 °C | -2 /+1°C of setpoint |
+20°C | +15/+23 °C | +17 °C | -5 /+0°C of setpoint | |
+6°C | +2/+8 °C | +5 °C | -3 /+2°C of setpoint |
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+6°C |
+3/+8 °C |
+6°C |
- /+1°C of setpoint |
-25°C |
-27/-21 °C |
-25°C |
-1 /+2°C of setpoint |
|
-25°C |
-27/-20 °C |
-24°C |
0 /+3°C of setpoint |
|
-30°C |
+6°C |
+4/+7 °C |
+6°C |
-1/+2°C of setpoint |
-25°C |
-28/-24 °C |
-26°C |
-2 /+0°C of setpoint |
|
-25°C |
-29/-21 °C |
-26°C |
-2 /+1°C of setpoint |
Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Setpoint | 5 minutes rear door opening | 10 minutes rear doors opening | |||
Zone 1 | Zone 2 | Air temperature peak (Z2) | Recovery time after closing doors | Air temperature peak (Z2) | Recovery time after closing doors | |
+40°C | +20°C | +6°C | +33.9 °C | 11 minutes | +37.3 °C | 22 minutes |
+20°C | -25°C | +29.7 °C | 87 minutes | - | - | |
+6°C | +20°C | +36 °C | 5 minutes | +37.7 °C | 6 minutes | |
-25°C | +6°C | +32.9 °C | 17 minutes | +35.8 °C | 18 minutes | |
-25°C | +20°C | +35.3 °C | 4 minutes | +38.4 °C | 4 minutes | |
-30°C | +20°C | +6°C | -24.4 °C | 16 minutes | -27.3 °C | 23 minutes |
+20°C | +20°C | -20.9 °C | 25 minutes | -25.8 °C | 39 minutes | |
+6°C | +20°C | -21.1 °C | 19 minutes | -26.9 °C | 27 minutes | |
+6°C | +6°C | -23.6 °C | 9 minutes | -26.8 °C | 14 minutes |
Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Zone 1 | Zone 2 | ||||
Setpoint | Time to move out of the range | Rules to apply | Setpoint | Time to move out of the range | Rules to apply | |
+40°C | +6°C | 10minutes | Above +8°C or max 2hrs. | +20°C | 2 hours | Above +25°C or max 2hrs. |
+6°C | 8 minutes | Above +8°C or max 2hrs. | -25°C | 15 minutes | Above -20°C or max 2hrs. | |
-25°C | 11 minutes | Above -20°C or max 2hrs. | +20°C | 2 hours | Above +25°C or max 2hrs. | |
-30°C | -25°C | N.A. | Non Applicable | +6°C | 7 minutes | Below +2°C or max 2hrs. |
-25°C | N.A. | Non Applicable | +20°C | 4 minutes | Below +15°C or max 2hrs. | |
+20°C | 20 minutes | Below +15°C or max 2hrs. | +6°C | 35 minutes | Below +2°C or max 2hrs. |
T-1200R Spectrum S3+S3 - Single-temperature Tests
Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+20°C |
+16/+21 °C |
+19 °C |
-2 / 0°C of setpoint |
+6°C |
+2/+8 °C |
+5 °C |
-2 / 0°C of setpoint |
|
-25°C |
-27/-20°C |
-24 °C |
0 /+2°C of setpoint |
|
-30°C |
+20°C |
+16/+22 °C |
+19 °C |
-3 / 0°C of setpoint |
+6°C |
+2/+8 °C |
+5 °C |
-2 / 0°C of setpoint |
|
-25°C |
-31/-25 °C |
-28 °C |
-4 /-1°C of setpoint |
Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | 5 minutes rear door opening | 10 minutes rear doors opening | ||
Air temperature peak (Z2) | Recovery time after closing doors | Air temperature peak (Z2) | Recovery time after closing doors | ||
+40°C | +20°C | +36.5 °C | 6 minutes | +38 °C | 8 minutes |
+6°C | +34.2 °C | 30 minutes | +36.5 °C | 41 minutes | |
-25°C | +31.7 °C | 117 minutes | - | - | |
-30°C | +20°C | -24.5 °C | 34 minutes | -26 °C | 55 minutes |
+6°C | -26 °C | 24 minutes | -28.2 °C | 34 minutes |
Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient |
Setpoint |
Time to move out of the range |
Rules to apply |
+40°C |
+6°C |
20 minutes |
Above +8°C or max 2hrs. |
-25°C |
15 minutes |
Above -20°C or max 2hrs. |
|
-30°C |
+20°C |
11 minutes |
Below +15°C or max 2hrs. |
+6°C |
20 minutes |
Below +2°C or max 2hrs. |
T-1000R Spectrum S3+S3 - Multi-temperatures tests
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+20°C |
+17/+22 °C |
+20 °C |
-2 / 0°C of setpoint |
-30°C |
+20°C |
+16/+21 °C |
+18 °C |
-3 / 0°C of setpoint |
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+6°C |
+3/+8 °C |
+6 °C |
- / +1°C of setpoint |
-30°C |
+6°C |
+4/+7 °C |
+5 °C |
-2 / 0°C of setpoint |
Door Opening - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Setpoint | 5 minutes rear door opening | 10 minutes rear doors opening | |||
Zone 1 | Zone 2 | Air temperature peak (Z2) | Recovery time after closing doors | Air temperature peak (Z2) | Recovery time after closing doors | |
+40°C |
+20°C |
+6°C |
+34.2 °C |
19 minutes |
+36.7 °C |
24 minutes |
+6°C |
+20°C |
+36.7 °C |
4 minutes |
+37.9 °C |
5 minutes |
|
-30°C |
+6°C |
+20°C |
-20.7 °C |
34 minutes |
-25.5 °C |
59 minutes |
+20°C |
+6°C |
-24.4 °C |
15 minutes |
-27.9 °C |
24 minutes |
Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Zone 1 | Zone 2 | ||||
Setpoint | Time to move out of the range | Rules to apply | Setpoint | Time to move out of the range | Rules to apply | |
+40°C |
+6°C |
8 minutes |
Above +8°C or max 2hrs. |
+20°C |
2 hours |
Above +25°C or max 2hrs. |
+20°C |
2 hours |
Above +25°C or max 2hrs. |
+6°C |
10 minutes |
Above +8°C or max 2hrs. |
|
-30°C |
+6°C |
86 minutes |
Below +2°C or max 2hrs. |
+20°C |
36 minutes |
Below +15°C or max 2hrs. |
+20°C |
35 minutes |
Below +15°C or max 2hrs. |
+6°C |
65 minutes |
Below +2°C or max 2hrs. |
T-1000R Spectrum S3+S3 - Single-temperature Tests
Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+20°C |
+16/+21 °C |
+19 °C |
-2 / 0°C of setpoint |
+6°C |
+2/+8 °C |
+5 °C |
-2 / 0°C of setpoint |
|
-30°C |
+20°C |
+16/+22 °C |
+19 °C |
-3 / 0°C of setpoint |
+6°C |
+2/+8 °C |
+5°C |
-2 / 0°C of setpoint |
Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | 5 minutes rear door opening | 10 minutes rear doors opening | |||
Air temperature peak (Z2) | Recovery time after closing doors | Air temperature peak (Z2) | Recovery time after closing doors | |||
+40°C |
+20°C |
+36.5 °C |
6 minutes |
+38 °C |
8 minutes |
|
+6°C |
+34.2 °C |
30 minutes |
+36.5 °C |
41 minutes |
||
-30°C |
+20°C |
-24.5 °C |
34 minutes |
-26 °C |
55 minutes |
|
+6°C |
-26 °C |
24 minutes |
-28.2 °C |
34 minutes |
Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | Time to move out of the range | Rules to apply |
+40°C | +6°C | 20 minutes | Above +8°C or max 2hrs. |
-30°C | +20°C | 11 minutes | Below +15°C or max 2hrs. |
+6°C | 20 minutes | Below +2°C or max 2hrs. |
UT-1200 Spectrum S3+S3 - Multi-Temperatures Tests
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+20°C |
+17/+22 °C |
+20 °C |
- / +1°C of setpoint |
-30°C |
+20°C |
+15/+22 °C |
+18°C |
-3 / 0°C of setpoint |
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+5°C |
+2/+8 °C |
+6 °C |
-1 / +2°C of setpoint |
-30°C |
+5°C |
+3/+7 °C |
+4°C |
-4 / 0°C of setpoint |
Door opening 5 minutes - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Zone 1 (side door) | Zone 2 (rear doors) | ||||
Setpoint | Air temperature peak | Recovery time after closing doors | Setpoint | Air temperature peak | Recovery time after closing doors | |
+40°C |
+5°C |
+31.8°C |
9 minutes |
+20°C |
+30.9°C |
4 minutes |
+20°C |
+35.6°C |
4 minutes |
+5°C |
+25.7°C |
20 minutes |
|
-30°C |
+5°C |
-27.5°C |
18 minutes |
+20°C |
-13.8°C |
29 minutes |
+20°C |
-25.3°C |
25 minutes |
+5°C |
-17.3°C |
37 minutes |
Door opening 10 minutes - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Zone 1 (side door) | Zone 2 (rear doors) | ||||
Setpoint | Air temperature peak | Recovery time after closing doors | Setpoint | Air temperature peak | Recovery time after closing doors | |
+40°C |
+5°C |
+37.8°C |
13 minutes |
+20°C |
+35.3°C |
8 minutes |
+20°C |
+38.5°C |
6 minutes |
+5°C |
+34°C |
25 minutes |
|
-30°C |
+5°C |
-29.6°C |
35 minutes |
+20°C |
-20.1°C |
55 minutes |
+20°C |
-29.8°C |
45 minutes |
+5°C |
-25°C |
55 minutes |
Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Zone 1 | Zone 2 | ||||
Setpoint | Time to move out of the range | Rules to apply | Setpoint | Time to move out of the range | Rules to apply | |
+40°C |
+5°C |
18 minutes |
Above +8°C or max 2hrs. |
+20°C |
2 hours |
Above +25°C or max 2hrs. |
+20°C |
102 minutes |
Above +25°C or max 2hrs. |
+5°C |
15 minutes |
Above +8°C or max 2hrs. |
|
-30°C |
+5°C |
13 minutes |
Below +2°C or max 2hrs. |
+20°C |
15 minutes |
Below +15°C or max 2hrs. |
+20°C |
15 minutes |
Below +15°C or max 2hrs. |
+5°C |
7 minutes |
Below +2°C or max 2hrs. |
UT-1200 Spectrum S3+S3 - Single-temperature Tests
Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+20°C |
+17/+23 °C |
+20 °C |
-1 / 0°C of setpoint |
+5°C |
+2/+7 °C |
+5°C |
- / +1°C of setpoint |
|
-30°C |
+20°C |
+15/+21 °C |
+19 °C |
-1°C of setpoint |
+5°C |
+2/+6 °C |
+4°C |
-3 / 0°C of setpoint |
Door open - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | 5 minutes rear door opening | 10 minutes rear doors opening | ||
Air temperature peak | Recovery time after closing doors | Air temperature peak | Recovery time after closing doors | ||
+40°C |
+20°C |
+30.4 °C |
3 minutes |
+35.7 °C |
7 minutes |
+5°C |
+25.9 °C |
17 minutes |
+33.2 °C |
25 minutes |
|
-30°C |
+20°C |
-9.4 °C |
16 minutes |
-21.9 °C |
46 minutes |
+5°C |
-15.3 °C |
16 minutes |
-25.6 °C |
28 minutes |
Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and wall stowed
Ambient | Setpoint | Time to move out of the range | Rules to apply |
+40°C |
+5°C |
19 minutes |
Above +8°C or max 2hrs. |
+20°C |
8 minutes |
Above -20°C or max 2hrs. |
|
-30°C |
+20°C |
16 minutes |
Below +15°C or max 2hrs. |
+5°C |
8 minutes |
Below +2°C or max 2hrs. |
UT-R Spectrum S3+S3 - Multi-Temperatures Tests
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 1)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+5 °C |
+2.6 °C / +6.9 °C |
+ 4.9 °C |
-1.2 / +1 °C of setpoint |
+20 °C |
+17.5 °C / +20.9 °C |
+ 20 °C |
-1.5 / +0.3 °C of setpoint |
|
-30°C |
+5 °C |
+3.6 °C / +6 °C |
+5 °C |
-0.8 / +0.6 °C of setpoint |
+21 °C |
+17.1 °C / +21.6 °C |
+19.3 °C |
-3.2 / +0.2 °C of setpoint |
Multi-Temperatures Operation - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length (Zone 2)
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40°C |
+20 °C |
+17.6 °C / +22.9 °C |
+20.6 °C |
-0.6 / +1.7 °C of setpoint |
+5 °C |
+2.7 °C / +6.2 °C |
+5.2 °C |
-0.6 / +1 °C of setpoint |
|
-30°C |
+21 °C |
+16.9 °C / +22.7 °C |
+19.4 °C |
-3 / +0.5 °C of setpoint |
+5 °C |
+4.2 °C / +6 °C |
+5 °C |
-0.2 / +0.3 °C of setpoint |
Door opening - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length.
Ambient | Setpoint | 7minutes rear door opening | ||
Zone 1 | Zone 2 | Air temperature peak (Z2) | Recovery time after closing doors | |
+40°C |
+20 °C |
+6 °C |
+25.5 °C |
23 minutes |
-30°C |
+5 °C |
+21 °C |
-13.9 °C |
28 minutes |
+21 °C |
+5 °C |
-18.6 °C |
16 minutes |
Failure Test - Configuration as in GDP-TK-OQ-SP-MT figure 7, dividing wall in middle position of total length
Ambient | Zone 1 | Zone 2 | ||||
Setpoint | Time to move out of the range | Rules to apply | Setpoint | Time to move out of the range | Rules to apply | |
+40°C |
+20 °C |
> 2 hours |
Above +25 °C or max 2hrs. |
+6 °C |
8.5 minutes |
Above +8°C or max 2 hrs. |
-30°C |
+21 °C |
> 2 hours |
Above +25°C or max 2hrs. |
+5 °C |
16 minutes |
Below +2°C or max 2 hrs. |
UT-R Spectrum S3+S3 – Single Temperature tests
Single Temperature Operation - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | Min/Max sensor temperature | Average temperature | Average temperature deviation |
+40 °C |
+20 °C |
+16.8 °C / +20.3 °C |
+19.1 °C |
-1.3 / +0 °C of setpoint |
+5 °C |
+2.4 °C / +6.8 °C |
+5.1 °C |
-0.5 / +0.5 °C of setpoint |
|
-23 °C |
-27.2 °C / -23.5 °C |
-25.5 °C |
-2.5 °C of setpoint |
|
+30 °C |
-29 °C |
-31.8 °C / +27.7 °C |
-29.8 °C |
-1.2 / -0.3 °C of setpoint |
-30 °C |
+20 °C |
+17.1 °C / +21.8 °C |
+19.7 °C |
-1.3/ +0.4 °C of setpoint |
+5 °C |
+3.4 °C / +6.6 °C |
+4.7 °C |
-1.0/ +0.4 °C of setpoint |
|
-24 °C |
-26.4 °C / -22.6 °C |
-24.7 °C |
-1.6/ +0.2 °C of setpoint |
|
-27°C |
-30.3 °C / -28.7 °C |
-29.6 °C |
-3.3 / -1.7 °C of setpoint |
Door openings - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and dividing wall stowed
Ambient | Setpoint | 7 minutes rear door opening | |
Air temperature peak | Recovery time after closing doors | ||
+40 °C |
+5 °C |
+24.2 °C |
14 minutes |
–23 °C |
+12.9 °C |
> 60 minutes |
|
-30 °C |
+20 °C |
-14.2 °C |
18 minutes |
+6 °C |
-18.2 °C |
15.5 minutes |
Failure test - Configuration as in GDP-TK-OQ-SP-MT figure 8, Single Zone Control and wall stowed
Ambient | Setpoint | Time to move out of the range | Rules to apply |
+40 °C |
+5 °C |
8.5 minutes |
Above +8 °C or max 2hrs. |
–23 °C |
8.5 minutes |
Above -20 °C or max 2hrs. |
|
-30 °C |
+20 °C |
33.5 minutes |
Below +15 °C or max 2hrs. |
+5 °C |
7 minutes |
Below +2 °C or max 2hrs. |
7.5: Hotspot / Coldspot Identification
As an indicator to support Risk Analysis of the customer the following Hot and Cold spots have been identified in an empty body.
Refer to figures 8 and 11 for thermocouples locations.
During COOLING Cycle - Multi-temperature Operation
T-1000R Spectrum S3+S3 and T-1200R Spectrum S3+S3
Unit model | Zone 1 | Zone 2 | |
Hotspot | T-1000R Spectrum S3+S3 | T4 | T29 |
T-1200R Spectrum S3+S3 | |||
Coldspot | T-1000R Spectrum S3+S3 | T9 | T20 |
T-1200R Spectrum S3+S3 | T14 | T17 |
UT-1200 Spectrum S3+S3
Unit model | Zone 1 | Zone 2 | |
Hotspot | UT-1200 Spectrum S3+S3 |
T1 |
T16 |
Coldspot |
T11 |
T19 |
UT-R Spectrum S3+S3
Unit model | Zone 1 | Zone 2 | |
Hotspot | UT-R Spectrum S3+S3 |
Ti1–04 |
Ti2–01 |
Coldspot |
Ti1-12 |
Ti2-05 |
During COOLING Cycle - Single-temperature Operation
T-1000R Spectrum S3+S3 and T-1200R Spectrum S3+S3
Unit model | Unique zone | ||
Hotspot |
T-1000R Spectrum S3+S3 |
T4 | |
T-1200R Spectrum S3+S3 |
|||
Coldspot |
T-1000R Spectrum S3+S3 |
T9 | |
T-1200R Spectrum S3+S3 |
For UT-1200 Spectrum S3+S3
Unit model | Unique zone | ||
Hotspot |
UT-1200 Spectrum S3+S3 |
T1 | |
Coldspot | T10 |
For UT-R Spectrum S3+S3
Unit model | Unique zone | ||
Hotspot |
UT-R Spectrum S3+S3 |
Ti1-04 | |
Coldspot | Ti1-20 |
During HEATING Cycle - Multi-temperature Operation
T-1000R Spectrum S3+S3 and T-1200R Spectrum S3+S3
Unit model | Zone 1 | Zone 2 | |
Hotspot | T-1000R Spectrum S3+S3 | T9 | T19 |
T-1200R Spectrum S3+S3 | T20 | ||
Coldspot | T-1000R Spectrum S3+S3 | T9 | T26 |
T-1200R Spectrum S3+S3 | T2 | T17 |
UT-1200 Spectrum S3+S3
Unit model | Zone 1 | Zone 2 | |
Hotspot | UT-1200 Spectrum S3+S3 |
T11 |
T19 |
Coldspot |
T14 |
T16 |
UT-R Spectrum S3+S3
Unit model | Zone 1 | Zone 2 | |
Hotspot | UT-1200 Spectrum S3+S3 |
Ti1-14 |
Ti2-05 |
Coldspot |
T14 |
Ti2-05 |
During HEATING Cycle - Single-temperature Operation
T-1000R Spectrum S3+S3 and T-1200R Spectrum S3+S3
Unit model | Unique zone | ||
Hotspot |
T-1000R Spectrum S3+S3 |
T9 | |
T-1200R Spectrum S3+S3 |
|||
Coldspot |
T-1000R Spectrum S3+S3 |
T29 | |
T-1200R Spectrum S3+S3 |
For UT-1200 Spectrum S3+S3
Unit model | Unique zone | ||
Hotspot |
UT-1200 Spectrum S3+S3 |
T10 | |
Coldspot | T28 |
For UT-R Spectrum S3+S3
Unit model | Unique zone | ||
Hotspot |
UT-R Spectrum S3+S3 |
Ti1-16 | |
Coldspot | Ti1-03 |
7.6: Recommendations
To maintain the best temperature management within the load-space it is recommended to operate with the following set-point temperatures in the following ranges:
For T-1200R Spectrum S3+S3
-
+20 °C for temperature range +15 °C to +25 °C
-
+6 °C for temperature range +2 °C to +8 °C
-
-25 °C for temperature below -20 °C
For T-1000R Spectrum S3+S3
-
+20 °C for temperature range +15 °C to +25 °C
-
+6 °C for temperature range +2 °C to +8 °C
For UT-1200 Spectrum S3+S3
-
+20 °C for temperature range +15 °C to +25 °C
-
+5 °C for temperature range +2 °C to +8 °C
For UT-R Spectrum S3+S3
-
+20 °C for temperature range +15 °C to +25 °C
-
+5 °C for temperature range +2 °C to +8 °C
-
-24 °C for temperature below -20 °C
-
-29 °C for temperature below -27 °C