i Preface For None
Note
|
Note
|
This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.
This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.
This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.
Thermo King’s warranty shall not apply to any equipment which
has been so installed, maintained, repaired or altered as, in the
manufacturer’s judgment, to affect its integrity.
Manufacturer shall have no liability to any person or entity for any personal injury, property damage or any other direct, indirect, special, or consequential damages whatsoever, arising out of the use of this manual or any information, recommendations or descriptions contained herein. The procedures described herein should only be undertaken by suitably qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.
There is nothing complicated about operating and maintaining your Thermo King unit, but a few minutes studying this manual will be time well spent.
Performing pre-trip checks and enroute inspections on a regular basis will minimize operating problems. A regular maintenance program will also help to keep your unit in top operating condition. If factory recommended procedures are followed, you will find that you have purchased the most efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled by a Thermo King dealer for four very important reasons:
They are equipped with the factory recommended tools to perform all service functions.
They have factory trained and certified technicians.
They have genuine Thermo King replacement parts.
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.
Copies of the approved Thermo King documentation can be found on the Thermo King iService Portal: http://iservice.thermoking.com/esa.
TK Americas: The product includes software that is licensed under a non‐exclusive, non-sublicensable, terminable and limited license to use the software as installed on the product for its intended purpose. Any removal, reproduction, reverse engineering, or other unauthorized use of the software is strictly prohibited. Hacking the product or installing unapproved software may void the warranty. The owner or operator shall not reverse engineer, decompile, or disassemble the software, except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this limitation. The product may include third party software separately licensed as specified in any documentation accompanying the product or in an about screen on a mobile application or website that interfaces with the product.
EMEA: The product includes software that is licensed under a non‐exclusive, non-sublicensable, terminable and limited license to use the software as installed on the product for its intended purpose. Any removal, reproduction, reverse engineering, or other unauthorized use of the software is strictly prohibited. Hacking the product or installing unapproved software may void the warranty. The owner or operator shall not reverse engineer, decompile, or disassemble the software, except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this limitation. The product may include third party software separately licensed as specified in any documentation accompanying the product or in an about screen on a mobile application or website that interfaces with the product. You are obliged to complete the declaration for “THERMO KING EQUIPMENT SOFTWARE LICENSE AGREEMENT” before you put your unit in operation.
This is located in your language at the following location: https://www.emea-user-manuals.thermoking.com “THERMO KING EQUIPMENT SOFTWARE LICENSE AGREEMENT”.
Let your voice be heard!
Your feedback will help improve our manuals. The survey is accessible through any internet-connected device with a web browser.
Scan the Quick Response (QR) code or click Technical Publications EMEA Feedback to complete the survey.
Need assistance finding technical literature, to report missing content, or to provide feedback on our technical literature? Email Thermo King Americas Publications at thermokingamericaspublications@thermoking.com.
Thermo King®/ FRIGOBLOCK recommends that all service be performed by a Thermo King/FRIGOBLOCK dealer and to be aware of several general safety practices.
Thermo King® recommends that all service be performed by a Thermo King dealer and to be aware of several general safety practices.
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this unit depend upon the strict observance of these precautions. The four types of advisories are defined as follows:
2prefix are connected directly to battery power. Always disconnect the battery before servicing the unit.
In the United States all technicians who maintain, service, repair, or dispose of equipment that could release refrigerants into the atmosphere must be EPA 608 certified. Thermo King recommends all service be performed by a Thermo King dealer.
Take precautions before electrically welding any portion of the unit or the vehicle to which it is attached. Verify that welding currents are not allowed to flow through the unit’s electronic circuits.
Observe the following precautions when welding to avoid damaging electronic components.
If the microprocessor has a power switch, turn it OFF before connecting or disconnecting the battery.
Disconnect power to the unit.
Disconnect all wire harnesses from the microprocessor.
If there are any electrical circuit breakers in the control box, switch them OFF.
Close the control box.
Components that could be damaged by welding sparks should be removed from the unit.
Use normal welding procedures, but keep the ground return electrode as close to the area being welded as practical. This will reduce the likelihood of stray welding currents passing through any electronic circuits.
REFRIGERANT
Eyes: For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical attention.
Skin: Flush area with large amounts of warm water. Do not apply heat. Remove contaminated clothing and shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection. Get prompt medical attention. Wash contaminated clothing before reuse.
Inhalation: Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
Frost Bite: In the event of frost bite, the objectives of First Aid are to protect the frozen area from further injury, warm the affected area rapidly, and to maintain respiration.
REFRIGERANT OIL
Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
ENGINE COOLANT
Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
BATTERY ACID
Under normal usage, the Ni-MH batteries
are hermetically sealed. In case of accident, perform the following
instructions:
Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention. Wash skin with soap and water.
Skin: Immediately remove contaminated clothing. Wash skin with large volumes of water, for at least 15 minutes. Wash skin with soap and water. Do not apply fatty compounds. Seek immediate medical assistance.
Inhalation: Provide fresh air. Rinse mouth and nose with water. Seek immediate medical assistance.
Ingestion: If the injured person is fully conscious: make the person drink extensive amounts of milk. Do not induce vomiting. Take the injured person immediately to a hospital.
ELECTRICAL SHOCK
Take IMMEDIATE action after a person has received an electrical shock. Get quick medical assistance, if possible.
The source of the shock must be quickly stopped, by either shutting off the power or removing the victim. If the power cannot be shut off, the wire should be cut with a non-conductive tool, such as a wood-handle axe or thickly insulated cable cutters. Rescuers should wear insulated gloves and safety glasses and avoid looking at wires being cut. The ensuing flash can cause burns and blindness.
If the victim must be removed from a live circuit, pull the victim away with a non-conductive material. Use wood, rope, a belt or coat to pull or push the victim away from the current. DO NOT TOUCH the victim. You will receive a shock from current flowing through the victim’s body. After separating the victim from power source, immediately check for signs of a pulse and respiration. If no pulse is present, start Cardiopulmonary Resuscitation (CPR). If a pulse is present, respiration might be restored by using mouth-to-mouth resuscitation. Call for emergency medical assistance.
ASPHYXIATION
Move victim to fresh air and use Cardiopulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
Units Built Before December 12, 2022 use R-404A Refrigerant
Units Built On or After December 12, 2022 use R-452A Refrigerant
The T-90 Series and UT-1290 units are one-piece, front-mounted, diesel powered cooling and heating systems designed for straight trucks. The condensing portion of the unit is mounted on to the front of a truck cargo box with the evaporator portion protruding into the box. The unit uses Chlorine free R-404A or R-452A refrigerant. The basic models provide the following:
The T-1090 SPECTRUM™ unit is a microprocessor based transport temperature control system that uses the SR-3 Truck HMI microcontroller to manage system functions. The unit is a self-powered multi-temperature unit for straight trucks. The condensing unit mounts on the front of the truck cargo compartment. Remote evaporators are used to control temperatures in up to three individual cargo compartments. The unit uses Chlorine free R-404A or R-452A refrigerant. The basic models provide the following:
Standard Unit (Model 30): Cooling and hot gas heating on engine operation.
SmartPower™ Unit (Model 50): Cooling and hot gas heating on engine operation and electric standby operation. Electric evaporator heaters are optional.
A three cylinder, EPA Tier 4, special clean and quiet diesel engine powers the unit when in the truck is in route. SmartPower (Model 50) units are also equipped with an electric motor for standby power operation while the truck is stationary.
The SR-3 microprocessor based temperature control system and in-cab HMI controller manage unit functions. CYCLE-SENTRY™, an exclusive Thermo King feature, automatically starts and stops the unit according to temperature demands. This continuous monitoring function optimizing the unit’s performance and reduces fuel consumption while maintaining temperature in multiple compartments.
The on-board Pretrip unit self check feature can be run before beginning the daily distribution route to identify any possible unit malfunctions and help prevent down time.
Microprocessor Controlled
Continuous System Monitoring
In-Cab HMI Controller
Alarm Code Display
Battery Voltage Display
Coolant Temperature Display
CYCLE-SENTRY Start/Stop Controls
Engine and Electric SmartPower (Model 50) Hour Meter
OptiSet Plus Temperature Profiles
Smart Defrost
Unit Self Check-pretripping
Aerodynamic Thermo Plastic Injection Molded Skins with In-mold Color
Air Cleaner, Dry Type
Alternator, 12 Volt, 37 Amp
Bypass Oil Filter (if equipped, see SB803)
Bypass Oil Filter (units built after Sept. 2020 do not have an oil bypass filter.)
Coolant Expansion Tank
Economy Mode
Fahrenheit and Celsius Display
Fuel Filter, Spin On
Oil Filter, Full Flow
Serpentine Belt with Manual Tensioner
R-404A or R-452A Chlorine-free Refrigerant
R-404A /R-452A Chlorine-free Refrigerant
Robotic Welded Steel Frame
X214 Compressor (T-590 and T-690)
X430P Compressor (T890, T-1090, T-1090 SPECTRUM, UT-1290)
ETV (Electronic Throttling Valve) (T-690, T-890, T-1090, T-1090 SPECTRUM, UT-1290)
TK374F Tier 4 Diesel Engine (T-590, T-690, and T-890)
TK380F Tier 4 Diesel Engine (T-1090, T-1090 SPECTRUM, UT-1290)
USB Diagnostic Port
TracKing™
Body Mount HMI Enclosure
Door Switch
MAX Cooling System
Electric Evaporator Heaters
SmartPower Electric Standby (Model 50)
SmartPower Automatic Phase Correction (Model 50)
SmartPower Diesel/Electric Autoswitching (Model 50)
Engine Block Heater
Fuel Tank (30 gallon aluminum, 18” and 22”)
Quick Oil Drain Kit
Rear Remote Control (flushmount)
Remote Indicator Light
Snow Cover
Whisper™ Sound Kit
Top Cover System
Precision Temperature Control (except T–590 / 690)
TouchLog
Bluetooth
Solar Panels
Battery Box
Evaporator Side Screens
Engine power is provided by the TK380F, a three cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 16.2 continuous horsepower (12.1 kW) at 2200 RPM. A belt drive system transfers energy to the compressor and alternator.
Engine power for the T-680S and T-880S is provided by the TK374F, a three-cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 11.7 continuous horsepower (8.7 kW) at 2200 RPM. A belt drive system transfers energy to the compressor, unit fans, and alternator.
Engine power for the T-1080S is provided by the TK380F, a three cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 16.2 continuous horsepower (12.1 kW) at 2200 RPM. A belt drive system transfers energy to the compressor, unit fans and alternator.
Engine power for the T-680R and T-880R is provided by the TK374F, a three-cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 11.7 continuous horsepower (8.7 kW) at 2200 RPM. A belt drive system transfers energy to the compressor, unit fans, and alternator.
Engine power for the T-1080R is provided by the TK380F, a three cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 16.2 continuous horsepower (12.1 kW) at 2200 RPM. A belt drive system transfers energy to the compressor, unit fans and alternator.
Engine power for
the T-590, T-690, and T-890 is provided by the TK374F, a three-cylinder,
EPA Tier 4, special clean and quiet diesel engine rated at 13.27 continuous
horsepower (9.9 kW) at 2200 RPM and 14.61 continuous horsepower (10.9
kW) at 2425 RPM. A belt drive system transfers energy to the compressor,
unit fans, and alternator.
Engine power for the T-1090 and UT-1290 is provided by the TK380F, a three cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 19.3 continuous horsepower (14.4 kW) at 2425 RPM. A belt drive system transfers energy to the compressor, unit fans and alternator.
Engine power for the T-1090 SPECTRUM is provided by the TK380F, a three cylinder, EPA Tier 4, special clean and quiet diesel engine rated at 19.3 continuous horsepower (14.4 kW) at 2425 RPM. A belt drive system transfers energy to the compressor and alternator.
The maintenance interval for ELC is eight years or 15,000 hours. A nameplate near the coolant expansion tank identifies units with ELC. This coolant is Red instead of the previous Green or Blue-Green coolants.
Note The use of 50/50% pre-mixed ELC is recommended to ensure that deionized water is being used. If 100% full strength concentrate is used, deionized or distilled water is recommended instead of tap water to ensure the integrity of the cooling system is maintained. The engine must have antifreeze protection to -40°F/ -40°C. Check and add coolant in the expansion tank as needed.
The centrifugal clutch engages fully at 600 ± 100 RPM on engine operation, constantly turning the compressor, alternator, and fans at both high and low speed. The clutch isolates the engine from the belt drive system during electric standby operation on Model 50 units.
The T-1200R unit features the X430P, 4-cylinder reciprocating compressor with 30.0 cu. in. (492 cc) displacement.
The T-1080R T-1000R features the X426, 4-cylinder reciprocating compressor with 25.9 cu in (424 cc) displacement.
The T-680R and T-880R T-600R and T-800R feature the X214, 2 cylinder reciprocating compressor with 13.92 cu in (229 cc) displacement.
The T-590 and T-690 feature the X214, 2 cylinder reciprocating compressor with 13.92 cu in (229 cc) displacement.
The T-890, T-1090, and UT-1290 feature the X430P, 4 cylinder reciprocating compressor with 30.0 cu in (492 cc) displacement.
The T-1090 SPECTRUM features the X430P, 4 cylinder reciprocating compressor with 30.0 cu in (492 cc) displacement.
The UT-800 and UT-1200 features the TK06,scroll compressor with 5.98 cu in (98 cc) displacement
The HMI Controller communicates with the Base Controller (located inside the control box) and is used operate the unit and display unit information. It also provides access to all the controller functions and menus.
The CYCLE-SENTRY Start/Stop fuel saving system provides optimum operating economy.
The CYCLE-SENTRY system automatically starts the unit on microprocessor demand and shuts down the unit when all demands are satisfied.
The system monitors and maintains the compartment temperature, the engine block temperature, and battery charge levels at a point where quick, easy starts are possible.
Frost will gradually build up on the evaporator coils as a result of normal operation. Periodically this frost must be melted to prevent a loss of cooling and airflow.
Defrost is accomplished by passing hot refrigerant gas through the evaporator coil, thus melting the frost (or ice). Melted frost drains out of the unit onto the ground through the drain tubes. The defrost damper closes during defrost to prevent warm air from entering the cargo area. The defrost damper closes during defrost to prevent warm air from entering the cargo area. The optional electric heater strips are also energized in defrost during electric standby operation.
Defrost can be initiated at any time the evaporator coil temperature is below 42 F (5.5 C).
There are two methods of defrost initiation:
SR-2/SR-3 SR-3 Microprocessor Controller: The Microprocessor Controller is programmed to automatically initiate timed and forced defrost cycles. The SR-2/SR-3 SR-3 uses temperature sensors to determine if forced defrost is required.
TSR/TSR-3 Microprocessor Controller: The Microprocessor Controller is programmed to automatically initiate timed and forced defrost cycles. The TSR/TSR-3 uses temperature sensors to determine if forced defrost is required.
Manual Defrost: Manual Defrost allows the operator to initiate a defrost cycle by pressing the Defrost key. See “Initiating a Manual Defrost Cycle.”
This Thermo King unit is equipped with a wireless communication platform that offers fleet owners the ability to monitor their refrigerated units. Cellular, GPS, and Bluetooth® capabilities communicate with Thermo King’s web-based TracKing platform, and Bluetooth with the Thermo King Reefer App. A third party interface offers a gateway for telematics providers to communicate with the Thermo King unit. To learn more about the TracKing features, contact your Thermo King dealer.
This unit is equipped with Thermo King’s ConnectedSuite™ wireless communication platform that offers fleet owners the ability to monitor their refrigerated units. Cellular, GPS, and Bluetooth® capabilities communicate with Thermo King’s web-based TracKing application, and Bluetooth with the Thermo King Reefer App. A third party interface offers a gateway for telematics providers to communicate with the Thermo King unit. The TracKing system can easily be setup and activated if desired. To learn more about the TracKing features, contact your Thermo King dealer.
TracKing Components:
TKV5 Module: Located inside the controls section of the unit. The telematics module with built-in antenna allows for wireless communication with the Thermo King unit. No service is required by the operator.
AGM Battery: Located inside the condenser section under the cooling system expansion tank. This battery is used to power the telematics system when in unit is turned off. The battery is charged when the unit is operating. No service is required by the operator.
110W Solar Panel: Typically located on cargo box roof. The solar panel keeps the AGM battery charged when the unit is not in use. No service is required by the operator other then keeping the panel free of any dirt of debris.
The SmartPower Electric Standby option allows the unit to be operated on either the diesel engine or external electric power.
The Electric Standby option allows the unit to be operated on either the diesel engine or external electric power.
The following features are standard equipment on units equipped with SmartPower Electric Standby.
The following features are standard equipment on units equipped with Electric Standby.
Automatic Diesel/Electric Selection: The unit will automatically switch to electric operation when a power cord is connected and the standby power is switched On.
Overload Relay: The overload relay is self-resetting.
Hot Gas Heat: Hot gas heat is utilized on all units.
Automatic Phase Correction: The control system features two motor contactors. This allows correct motor rotation regardless of phase rotation on the incoming power.
Electric Heater Strips
Water Heat
The following features are available as options on units equipped with Electric Standby.
Auto Switching
Electric Heater Strips
The following features are available as an option on units equipped with Electric Standby.
Electric Heater Strips
Water Heat
High Pressure Cutout Switch (HPCO): This normally closed switch monitors the discharge pressure at the compressor. It opens on high discharge pressure to shut the unit down to prevent damage.
Electronic Throttling Valve (ETV): (T-1200R only) T-1300X only This component is an electromechanical control device used to limit the suction pressure to the compressor. The valve is controlled by the microprocessor controller.
Engine Oil Pressure Switch/Sensor:
Units built before September 30, 2020 -
The engine oil pressure switch/sensor is located on the filter head above the bypass oil filter. Engine oil pressure should rise immediately on starting. If engine oil pressure drops below 11 ± 3psig (76 ± 20kPa), the switch/sensor signals the microprocessor to stop the engine.Units built September 30, 2020 and after -
The engine oil pressure switch/sensor is located on the engine block near the oil filter. Engine oil pressure should rise immediately on starting. If engine oil pressure drops below 11 ± 3psig (76 ± 20kPa), the switch/sensor signals the microprocessor to stop the engine.Suction Pressure Regulator (SPR, T-590 Only):This component is a mechanical control device used to limit the suction pressure to the compressor. The valve controls suction pressure based on the actual system pressure.
Engine Oil Pressure Switch/Sensor: The engine oil pressure switch/sensor is located on the filter head above the bypass oil filter. Engine oil pressure should rise immediately on starting. If engine oil pressure drops below 10 ± 2 psig (69 ± 14 kPa), the switch/sensor signals the microprocessor to stop the engine.
Preheat Buzzer: The preheat buzzer sounds when the CYCLE-SENTRY system energizes the glow plugs. This should warn anyone near the unit that the CYCLE-SENTRY system is about to start the diesel engine.
Coolant Temperature Sensor: This sensor provides an engine coolant temperature input to the microprocessor. If the engine coolant temperature is too high, the controller stops the unit and records an alarm.
Electric Motor Overload Relay (Model 50) (Model 50): The overload relay protects the electric standby motor. The overload relay opens the circuit from the contactor to the electric motor if the motor overloads for any reason and an alarm will occur. The relay resets when the alarm code is cleared.
Fuses: Sizes and functions are described in the Specifications chapter of this manual.
Electric Heat Overlaod (Optional): Units equipped with the electric heat option are protected by an overload circuit to protect the electrical system of the unit.
Coolant Expansion Tank: The coolant level and temperature are monitored by the base controller. If the coolant temperature becomes too high or the level becomes too low, an alarm will occur.
The engine must have antifreeze protection to –30 F (–34 C). Check and add coolant in the expansion tank as needed.
Note The use of 50/50% pre-mixed ELC is recommended to ensure that deionized water is being used. If 100% full strength concentrate is used, deionized or distilled water is recommended instead of tap water to ensure the integrity of the cooling system is maintained. The engine must have antifreeze protection to -40°F/ -40°C. Check and add coolant in the expansion tank as needed.
Engine Oil Dipstick: Use the engine oil dipstick to check the engine oil level.
Receiver Tank Sight Glass: The receiver tank sight glass is used to assist in checking the amount of refrigerant in the system.
Compressor Oil Sight Glass: The compressor oil sight glass is used to check the relative level of compressor oil in the compressor sump.
1. | Engine Oil Dipstick (on side of engine) | 6. | Alternator |
2. | Engine | 7. | Dehydrator (Filter-Drier) |
3. | Coolant Expansion Tank | 8. | Compressor |
4. | Coolant Overflow Bottle | 9. | Base Controller On/Off Switch |
5. | Electric Motor |
1. | Engine Oil Dipstick (on side of engine) | 6. | Alternator |
2. | Engine | 7. | Dehydrator (Filter-Drier) |
3. | Coolant Expansion Tank | 8. | Compressor |
4. | Coolant Overflow Bottle | 9. | Base Controller On/Off Switch |
5. | Electric Motor |
The Truck Standard Display (TSD) HMI Control Panel is used to operate the unit and display some unit information. The Truck Standard Display communicates with the Base Controller via the Controller Area Network (CAN) bus. It is connected to the Base Controller via CAN Connector J14. The TSD is typically located in the vehicle driver’s compartment. It may be located in the truck dashboard using a DIN mounting ring or under the dashboard using an under dash mounting kit.
The Truck Standard Display (TSD) HMI Control Panel is used to operate the unit and display some unit information. The Truck Standard Display communicates with the Base Controller via the Controller Area Network (CAN) bus. It is connected to the Base Controller via CAN Connector J35. The TSD is typically located in the vehicle driver’s compartment. It may be located in the truck dashboard using a DIN mounting ring or under the dashboard using an under dash mounting kit.
Displays Box Temperature and Setpoint in Fahrenheit or Celsius
Displays Engine Running Hourmeter and Motor Running Hourmeter
Indicates the current zone on Multi-Temperature applications
Changes Unit or Zone Setpoints
Selects and indicates Cycle Sentry or Continuous Mode Operation
Selects and indicates High Speed Lock-Out Operation
Initiates and indicates a Unit or Zone Defrost Cycle
Indicates an alarm condition exists, displays and clears alarms
Initiates and indicates a Pretrip Test
Sends a Start of Trip Marker to the ServiceWatch Data Logger
Changes display brightness
Shows Truck Standard Display serial number and software revision
Displays and changes Date and Time
Displays Box Temperature and Setpoint in Fahrenheit or Celsius
Displays Engine Running Hourmeter and Motor Running Hourmeter
Indicates the current zone on Multi-Temperature applications
Changes Setpoint
Selects and indicates Cycle Sentry or Continuous Mode Operation
Selects and indicates High Speed Lock-Out Operation
Initiates and indicates a Defrost Cycle
Indicates an alarm condition exists, displays and clears alarms
Initiates and indicates a Pretrip Test
Sends a Start of Trip to the ServiceWatch Data Logger
Changes display brightness
Shows Truck Standard Display serial number and software revision
The Truck Standard Display consists of a display and nine touch-sensitive keys. The display presents information to the operator and includes setpoint and box temperature, hourmeter readings, alarms, and several icons.
The display is capable of showing numbers and illuminating several icons. It does not display text, making it suitable for use with any language.
The upper row of numbers can display the box temperature, engine run time hourmeter, current zone, or alarm code(s). The lower row of numbers can display the setpoint, electric run time hourmeter, or total number of alarms.
Display symbols or icons are used to present additional unit information.
When this icon is present in the upper display, it is showing the actual box temperature inside the truck box. | |
When this icon is present in the lower display, it is showing the current setpoint. | |
When this icon is present in the upper display, it is showing the diesel engine run time. | |
When this icon is present in the the lower display, it is showing the electric motor run time (if the unit is equipped with optional Electric Standby). | |
When this Alarm Icon is present, one or more alarm conditions have occurred. If the display is not flashing, any alarms are Check Alarms. If the display is flashing on and off, a Shutdown Alarm has occurred and the unit has been shut down. Immediate action must be taken. |
There are nine touch sensitive keys. Some of these keys have more than one function.
There are amber LED indicators located next to each of the four function keys below the display. The LED will glow amber when that function is active. A red LED indicator is located between the ON Key and OFF Key at the left side of the display. This indicator will glow if Alarm Code 91 Check Electric Ready Input occurs. It will also illuminate if a 15 pin Thermo King Data Cable is connected to the serial port on the back of the Base Controller.
Primary Use – Pressing the ON Key will turn the unit on. Secondary Use – When the unit is on, pressing this key and the PRETRIP Key at the same time will display any alarm codes that are present. Secondary Use – When the unit is on, pressing and holding this key allows the UP ARROW Key and DOWN ARROW Key to increase or decrease the display brightness. Secondary Use – When the unit is on and a different display is shown, pressing this key will return to the Standard Display of box temperature and setpoint. Multi-Temp Use – When Manual Zone Selection is active the selected zone can be turned on and off by simultaneously pressing the ON Key and ENTER Key. |
|
Primary Use – Pressing the OFF Key will turn the unit off. | |
Primary Use – When the unit is turned on and the Standard Display is shown, pressing the UP ARROW Key will increase the setpoint. Secondary Use – When alarms are being displayed, pressing this key will scroll through the alarms (if more than one alarm is present). Secondary Use – While holding ON Key down with the unit turned on, pressing this key will increase the display brightness (Low, Medium, High). |
|
Primary Use – When the unit is turned on and the Standard Display is shown, pressing the DOWN ARROW Key will decrease the setpoint. Secondary Use – While holding ON Key down with the unit turned on, pressing this key will decrease the display brightness (High, Medium, Low). |
|
Primary Use – If the setpoint has been changed using the UP ARROW Key and/or DOWN ARROW Key, pressing the ENTER Key enters the setpoint into the base controller’s memory. Secondary Use – When alarms are being displayed, pressing this key will clear the alarm shown on the display. Secondary Use – When the unit is turned on, press and hold this key for five seconds to send a Start of Trip (SOT) to the data logger. Multi-Temp Use – Pressing this key will enable Manual Zone Selection mode and scroll through the installed zones, one zone at a time. When a zone is manually selected the zone can be turned on or off, the setpoint can be changed and a manual defrost cycle can be initiated if zone conditions permit. |
|
Primary Use – If the unit is turned on and is in Continuous Mode, pressing the CYCLE SENTRY/CONTINUOUS Key will switch operation to CYCLE SENTRY Mode and the amber LED indictor will glow. If the unit is running in CYCLE SENTRY Mode, pressing this key will switch operation to Continuous Mode and the amber LED will turn off. | |
Primary Use – If the unit is turned
on, pressing the HIGH SPEED LOCKOUT Key will activate High Speed Lock-Out.
The unit will switch to low speed operation and the amber LED indictor
will glow. No further high speed operation is allowed until this feature
is turned off. If the High Speed Lockout Timer is enabled, the unit
will automatically return to high speed after a programmed time limit.
This feature is typically used in noise sensitive areas to reduce
unit noise.
Note The HIGH SPEED LOCK-OUT Key is only
used when the unit is operating in Diesel Mode. The HIGH SPEED LOCK-OUT
Key does not have any effect in Electric Mode operation.
|
|
Primary Use – If the unit is turned on, pressing the DEFROST Key will initiate a manual defrost cycle if conditions allow. If the evaporator coil temperature less than 45°F (7°C) the unit will enter a defrost cycle. The amber LED will flash while the defrost cycle is initialized and will glow during the defrost cycle. The defrost cycle will terminate automatically and the amber LED will turn off when the evaporator coil temperature is greater than 52°F (11°C). To manually terminate a defrost cycle turn the unit off and back on. Multi-Temp Use – A zone must be selected before initiating a manual defrost cycle. |
|
Primary Use – Pressing and holding the PRETRIP TEST Key for five seconds will initiate either a Full Pretrip Test or Engine Running Pretrip Test so long as no alarm conditions exist. If the Alarm Icon is glowing, record and clear the alarms before starting the Pretrip Test. Press and hold the PRETRIP TEST Key for five seconds. The amber LED may flash while the Pretrip Test is initialized and will glow steady while the Pretrip Test is running. When the Pretrip Test is complete the amber LED will turn off.
Secondary Use – When the unit is turned off press and hold this key for five seconds to show the HMI Control Panel Serial Number (in the upper display) and the HMI Control Panel Software Revision (in the lower display). Secondary Use – When the unit is turned off this key is used to display the Clock/Calendar. |
If the HMI Control Panel is turned on and the Base Controller ON/OFF Switch is turned off, the HMI display screen will flash ON and OFF.
The unit is turned on by pressing the ON Key and off by pressing the OFF Key. When the ON Key is pressed, the display briefly shows dashes as the display initializes.
The unit running time hourmeters are shown for 30 seconds. The diesel engine run time hours and Diesel Icon are shown in the upper display. If the optional Electric Standby Feature is installed, the electric motor run time hours and Electric Icon appear in the lower display as shown below. A Full Pretrip Test is initiated from this display by pressing and holding the Pretrip Key as shown later in this section.
When the unit is ready to run, the Standard Display of box temperature and setpoint appears. The box temperature and Box Temp Icon are shown in the upper display. The setpoint and Setpoint Icon are shown in the lower display. The box temperature shown below is 35.8°F (2.1°C) with a 35°F (1.6°C) setpoint.
When the unit is ready to run, the Standard Display of box temperature and setpoint appears. The box temperature and Box Temp Icon are shown in the upper display. The setpoint and Setpoint Icon are shown in the lower display. On multi-temperature applications, the Zone indicators are shown to the left of the box temperature. In the example below, Zone 2 is being shown on the display. The Zone 2 box temperature shown here is 35.8°F (2.1°C) with a 35°F (1.7°C) setpoint.
Pressing the OFF Key stops unit operation. The unit shuts down immediately and the display goes blank. To start the unit again, press the ON Key.
The Standard Display is the default display that appears if no other display function is selected. The Standard Display shows the box temperature and setpoint. The box temperature is that measured by the return air sensor. The box temperature and Box Temperature Icon are shown in the upper display. The setpoint and Setpoint Icon are shown in the lower display. The box temperature shown ( Standard Display) is 35.8°F (2.1°C) with a 35°F (1.6°C) setpoint.
From the Standard Display, press the UP ARROW Key and/or DOWN ARROW Key until the desired setpoint is shown. In the figure shown ( UP ARROW Key), the setpoint has been increased to 40°F (4.4°C) using the UP ARROW Key.
When the desired setpoint has been selected using the UP ARROW Key or DOWN ARROW Key, the ENTER Key must be pressed to confirm and load the new setpoint.
If the setpoint is changed using the UP ARROW Key and DOWN ARROW Key, the setpoint display will begin to flash 10 seconds after the last press of the UP ARROW or DOWN ARROW key as a reminder to press the ENTER Key.
The setpoint display will flash for 10 additional seconds. If at the end of this time the ENTER Key still has not been pressed to complete the setpoint change, the setpoint will return to the old setpoint and Alarm Code 127 Setpoint Not Entered will be set. The Alarm Icon will appear in the display.
The new setpoint of 40°F (4.4°C) will remain on the display after the ENTER Key has been pressed.
Failure to confirm the new setpoint by pressing the ENTER Key within 20 seconds of changing the setpoint will result in no setpoint change. In addition, Alarm Code 127 Setpoint Not Entered is set, to indicate that the setpoint change was started but was not completed.
Notice that the setpoint has returned to the old setpoint of 35°F (1.6°C) and the Alarm Icon has lighted indicating that Alarm Code 127 Setpoint Not Entered is set.
If the ENTER Key is pressed, the setpoint change made with the UP ARROW Key and/or DOWN ARROW Key is accepted, the setpoint is changed, and the display returns to the Standard Display showing the new setpoint.
If the ENTER Key is not pressed within 20 seconds of making a change with the UP ARROW Key and/or DOWN ARROW Key, the setpoint is not changed and the display returns to the Setpoint Display showing the old setpoint. Alarm Code 127 Setpoint Not Entered is set and the Alarm Icon will appear on the display, to indicate that the setpoint change was started but not completed.
Verify the Base Controller On/Off switch is in the ON position. Diesel engine preheats and starts are automatic in both Continuous Mode and CYCLE-SENTRY Mode. The engine will preheat and start as required when the unit is turned on. The engine pre-heat and start sequence will be delayed in Cycle Sentry mode if there is no current need for the engine to run.
When the engine is preparing to start, the Truck Standard Display HMI Control Panel will continue to display the Standard Display as shown ( Standard Display Standard Display). The preheat buzzer at the unit (located on the unit Interface Board) sounds during the engine pre-heat and crank sequence.
Verify the Base Controller On/Off switch is in the ON position. Electric motor starting is automatic in both Continuous Mode and CYCLE-SENTRY Mode. The motor will start as required when the unit is turned on in Standby Mode and standby power is connected.
When the motor is preparing to start, the Truck Standard Display HMI Control Panel will continue to show the Standard Display as shown ( Standard Display Standard Display). The preheat buzzer at the unit (located on the unit Interface Board) sounds for 20 seconds before the electric motor starts.
Diesel to Electric Auto Switch Enabled set YES (Default)
If this feature is set YES, the unit will switch automatically from Diesel Mode to Electric Mode when standby power is connected and present.
Diesel to Electric Auto Switch Enabled set NO
The Diesel to Electric Auto Switch Enabled feature should not be set NO on units equipped with the Truck Standard Display HMI Control Panel.
Electric to Diesel Auto Switch Enabled feature set YES
If this feature is set YES, the unit will switch automatically from Electric Mode to Diesel Mode when standby power is removed or fails.
Electric to Diesel Auto Switch Enabled feature set NO (Default)
If the unit is operating in Electric Mode and standby power is disconnected or fails, the unit will not automatically switch to Diesel mode. This is primarily designed to prevent unauthorized diesel engine starts when the truck is indoors or on a ferry where engine operation is strictly prohibited.
If the unit is operating in Electric Mode and standby power is disconnected or fails, Alarm Code 91 Check Electric Ready Input will be set. The red LED between the ON key and OFF Key will glow, the Alarm Icon will glow, and the box temperature and setpoint displays will disappear as shown ( Alarm Icon).
If the unit is running in Electric Mode and electric standby power is lost and then restored, Alarm Code 91 Check Electric Ready Input will be automatically cleared and the unit will restart in Electric Mode.
When the display shown ( Alarm Icon) is present, do not press the Truck Standard Display HMI Control Panel OFF Key to turn the unit off. Press the HMI Control Panel ON Key twice to clear Alarm Code 91 Check Electric Ready Input and turn the unit back on in Diesel Mode.
Preferred Method for Manually Switching from Electric Mode to Diesel Mode
Press the HMI Control Panel OFF Key to turn the unit off.
Turn off the standby power and disconnect the cord.
Press the HMI Control Panel ON Key to turn the unit on. The Hourmeters display will briefly appear and then the screen will appear as shown.
Press the HMI Control Panel ON Key again to clear Alarm Code 91 Check Electric Ready Input and turn the unit back on in Diesel Mode.
If the HMI Control Panel OFF Key is pressed when the display shown ( Display) is present, the unit will turn off and the display will be blank. To restart the unit in Diesel Mode, proceed as follows:
Press the HMI Control Panel ON Key. The Hourmeters display and a blinking Alarm Icon will appear.
When the Hourmeters display and a blinking Alarm Icon is shown, press the HMI Control Panel ON Key again. The display will go blank but the blinking Alarm Icon will remain on and blinking.
When the display goes blank and the blinking Alarm Icon is shown, press the HMI Control Panel ON Key again. The box temperature and setpoint will appear, the blinking Alarm Icon will disappear and the unit will start in Diesel Mode.
When CYCLE-SENTRY mode is selected, the unit will start and stop automatically to maintain setpoint, keep the engine warm, and the battery charged. When Continuous Mode is selected, the unit starts automatically and runs continuously to maintain setpoint and to provide constant airflow.
CYCLE-SENTRY Mode or Continuous Mode is selected by pressing the CYCLE-SENTRY/CONTINUOUS Key when the unit is turned on. If the unit is running in Continuous Mode, pressing this key will switch operation to CYCLE-SENTRY Mode and the amber LED indictor will glow. If the unit is running in CYCLE-SENTRY Mode, pressing this key will switch operation to Continuous Mode and the amber LED will turn off.
The unit shown ( CYCLE-SENTRY/Continuous Key CYCLE-SENTRY/Continuous Key) is running in CYCLE-SENTRY Mode.
If the High Speed Lock-Out feature is enabled and turned on, the unit will run only in low speed until the High Speed Lock-Out feature is turned off or the High Speed Lockout Timer is exceeded. This feature is typically used in noise sensitive areas to reduce unit engine noise.
High Speed Lock-Out is turned on or off by pressing the HIGH SPEED LOCKOUT Key when the unit is turned on. Pressing this key will turn High Speed Lock-Out on, pressing it again will turn High Speed Lockout off. If High Speed Lockout is turned on, unit will switch to low speed operation and the amber LED indictor will glow. No further high speed operation is allowed until this feature is turned off or the High Speed Lockout Timer is exceeded.
The unit shown ( HIGH SPEED LOCKOUT Key) has High Speed Lock-Out turned on.
Defrost cycles are usually initiated automatically based on time or demand. Manual defrost may also be available. Defrost is only available if the unit is running and the evaporator coil temperature is less than 45°F (7°C). Other features such as door switch settings may not allow manual defrost under some conditions.
To initiate a manual defrost cycle, press the DEFROST Key as shown ( DEFROST Key). If conditions allow, the unit will enter a defrost cycle and the amber LED next to the DEFROST Key will glow.
The defrost cycle terminates automatically when the coil temperature is greater than or equal to 52°F (11°C) or the maximum defrost timer expires. When the defrost cycle is completed, the amber LED next to the DEFROST Key will turn off. Defrost can also be terminated by turning the unit off and back on.
If an alarm condition occurs, the Alarm Icon will appear on the display. If the alarm is a Check Alarm, the Alarm Icon will turn on but the unit will continue to run. If the alarm is a Shutdown Alarm, the Alarm Icon and the display will flash on and off and the unit will shut down. If the alarm is zone specific, the zone indicator will be present to show which zone has the alarm condition.
Alarms are displayed by simultaneously pressing and holding the ON Key and PRETRIP TEST Key. The upper display shown ( ON and PRETRIP TEST Keys) indicates that Alarm Code 127 Setpoint Not Entered has been set. The lower display indicates that only one alarm code exists. If more than one alarm code has been set, they are displayed with the most recent alarm shown first. Use the UP ARROW Key to scroll through the alarms.
Unit alarms affect the operation of the entire unit. The Alarm Display shown above indicates that Alarm Code 127 exists and that there is only one alarm condition present.
If an alarm condition is specific to a zone, the zone indicator will be present to identify the zone experiencing the alarm condition. The Alarm Display shown ( Zone Specific Alarm Display) indicates that Alarm Code 127 Setpoint Not Entered exists in Zone 2. It also shows that a total of three alarm conditions exist.
If more than one alarm code has been set, they are displayed with the most recent alarm shown first. Use the UP ARROW Key to scroll through the alarms.
After the alarm situation is resolved, press the ENTER Key to clear the alarm code currently being shown. When all alarms have been cleared, the display will show all zeros to indicate that no alarm codes exist.
The display will return to the Standard Display about 30 seconds after all alarms have been cleared.
Important Alarm Notes
All alarms must be viewed before any of the alarms can be cleared.
If an alarm will not clear, it may still exist. If the alarm is not corrected, it will not clear or may be immediately set again.
Some alarms cannot be cleared using the HMI Control Panel. These alarms must be cleared by maintenance personnel from the Maintenance or Guarded Access Menus.
Alarm Code 91 Check Electric Ready Input is cleared by turning the unit off and back on. Refer to Switching From Electric To Diesel in this section.
Refer to the SR-3 Truck Single Temperature Diagnostic Manual TK 55208 for more information about alarm codes and their diagnosis.
Refer to the SR-2 Truck SPECTRUM Multi-Temp Diagnostic Manual TK 56706 or SR-3 Truck SPECTRUM Multi-Temp Diagnostic Manual TK 54293 for more information about alarm codes and their diagnosis.
A Pretrip Test verifies unit operation. The PRETRIP Key allows either a Full Pretrip Test or an Engine Running Pretrip Test to be initiated by the operator.
The current unit settings are saved and restored at the end of the Pretrip Test or if the unit is turned off and back on.
The Pretrip Test can be run in either Diesel or Electric Mode.
The unit will auto switch from Diesel Mode to Electric Mode or from Electric Mode to Diesel Mode during a Pretrip Test if these features are enabled and the auto switch conditions occur.
Pretrip Tests are not allowed if any Shutdown Alarms are present.
Pretrip tests are allowed with some Check and Log Alarms present.
Pretrip tests proceed in the order shown below.
Full Pretrip Tests include all of the tests shown below.
Amp Checks - Each electrical control component is energized and the current drawn is confirmed as within specification.
Engine Start - The Engine will start automatically.
Defrost - If the coil temperature is below 45°F (7°C), a defrost cycle is initiated.
RPM Check - The engine RPM in high and low speed is checked during the Cool Check.
Cool Check - The ability of the unit to cool in low speed is checked.
Heat Check - The ability of the unit to heat in low speed is checked.
After Cool Check - The ability of the unit to return to cool in low speed is checked.
Report Test Results - The test results are reported when the Pretrip Test is completed. If the Pretrip Test fails, alarm codes will exist to direct the technician to the source of the problem.
Engine Running Pretrip Tests include all of the tests shown below. They do not include the Amps Check or the Engine Start tests.
Defrost - If the coil temperature is below 45°F (7°C), a defrost cycle is initiated.
RPM Check - The engine RPM in high and low speed is checked during the Cool Check.
Cool Check - The ability of the unit to cool in low speed is checked.
Heat Check - The ability of the unit to heat in low speed is checked.
After Cool Check - The ability of the unit to return to cool in low speed is checked.
Report Test Results - The test results are reported when the Pretrip Test is completed. If the Pretrip Test fails, alarm codes will exist to direct the technician to the source of the problem.
When performing a Pretrip Test, the following issues should be considered.
Whenever possible, run the Pretrip Test with an empty truck box.
If running a Pretrip Test on a truck loaded with dry cargo, verify that proper airflow can occur around the load. If the load restricts airflow, false test results may occur. Units have high refrigeration capacity which results in rapid temperature change. Sensitive dry cargo may be damaged as a result.
If running a Pretrip Test on a truck that has just been washed down, the extremely high humidity inside the truck box may result in false test results.
If running a Pretrip Test on a truck loaded with sensitive cargo, monitor the load temperature during the test as normal temperature control is suspended during pre-trip operation.
Always perform Pretrip Tests with the cargo doors closed to prevent false test results.
The Full Pretrip Test must be started with the unit not running. Turn the unit on and clear all alarm codes. Turn the unit off.
Turn the unit on and wait for the unit running time hourmeters to be shown on the display. When the unit running time hourmeters are shown on the display, press and hold the PRETRIP Key for five seconds.
A flashing Pretrip LED indicates that the Pretrip Test is being initialized. When the Pretrip Test starts, the Pretrip LED will glow steady amber. The display will show the Standard Display.
The Amps Check Test will be performed and then the unit will start automatically. The balance of the tests will be completed.
The Pretrip Test will take about 20 - 30 minutes, depending on conditions.
When the Pretrip Test is complete or if a Shutdown Alarm occurs, the amber Pretrip LED will turn off.
Stopping a Pretrip Test: To stop a Pretrip Test at any time, press the POWER OFF Key to turn the unit off. This will generate Alarm Code 28 Pretrip Abort. Other alarm codes may also be generated. This is normal when the Pretrip Test is halted before completion.
The Engine Running Pretrip Test must be started with the unit running. Turn the unit on and clear all alarm codes. Allow the unit to start.
With the unit running, press and hold the PRETRIP Key for five seconds.
A flashing Pretrip LED indicates that the Pretrip Test is being initialized. When the Pretrip Test starts, the Pretrip LED will glow steady amber to indicate the test is in progress. The display will show the Standard Display.
The Pretrip Test will take about 20 - 30 minutes, depending on conditions.
When the Pretrip Test is complete or if a Shutdown Alarm occurs, the amber Pretrip LED will turn off.
Stopping a Pretrip Test: To stop a Pretrip Test at any time, press the POWER OFF Key to turn the unit off. This will generate Alarm Code 28 Pretrip Abort. Other alarm codes may also be generated. This is normal when the Pretrip Test is halted before completion.
If the unit passes the Pretrip Test, the amber Pretrip Test LED will turn off at the completion of the test and the unit will continue to run as required. This signifies that the unit passed the Pretrip Test.
If the unit fails the Pretrip Test with Check Alarms, the Alarm Icon will appear when the alarm condition occurs. The Pretrip Test will continue to run unless a Shutdown Alarm occurs.
The amber Pretrip Test LED will turn off at the completion of the test, but the Alarm Icon will remain illuminated. This indicates that one or more Check Alarm conditions occurred during the Pretrip Test. More than one alarm may be present.
View and record the alarm(s), correct as necessary, clear the alarm(s), and repeat the Pretrip Test.
If the unit fails the Pretrip Test with a Shutdown Alarm, the Alarm Icon will appear when the alarm condition occurs, the unit will immediately shut down and the amber Pretrip Test LED will turn off.
The Pretrip Test will be aborted.
Alarm Code 28 Pretrip Abort will be set along with the Shutdown Alarm that was detected. This signifies that a Shutdown Alarm occurred during the Pretrip Test and that the test was aborted. Other alarms may also be present.
View and record the alarm(s), correct as necessary, clear the alarm(s), and repeat the Pretrip Test.
The brightness of the HMI Control Panel display can be adjusted to allow for changing ambient light conditions. The choices available to the operator are HIGH, MEDIUM, and LOW.
To change the display brightness, press and hold the ON key and press the UP ARROW Key to increase display brightness and the DOWN ARROW Key to decrease display brightness.
The Keypad Lockout feature allows the operator to lock the keypad to prevent tampering. If the Keypad Lockout feature is turned on, all keys except the ON Key and OFF Key are prevented from functioning. The unit can still be turned On and Off, but doing so does not clear Keypad Lockout.
To turn Keypad Lockout on, simultaneously press and hold the ON Key, CYCLE SENTRY Key, and HIGH SPEED LOCK-OUT Key for five seconds. The display shown ( ON Key, CYCLE SENTRY Key, and HIGH SPEED LOCK-OUT Key) will appear, with [0 - - - n] replacing the box temperature. When the three keys are released, the display will return to the Standard Display of box temperature and setpoint.
When Keypad Lockout is turned on, only the ON and OFF Keys are functional. All other keys are locked out. Pressing any key other than the ON Key and OFF Key will cause the box temperature to display [0 - - - n]. When the key is released, the display will return to the Standard Display of box temperature and setpoint.
To turn Keypad Lockout off, simultaneously press and hold the ON Key, CYCLE SENTRY Key, and HIGH SPEED LOCK-OUT Key for five seconds. The display shown ( ON Key, CYCLE SENTRY Key, and HIGH SPEED LOCK-OUT Key) will appear, with [0 - - - n] replacing the box temperature. When the three keys are released, the display will return to the Standard Display of box temperature and setpoint. All keys will function normally.
The HMI Control Panel serial number and software revision can be displayed if necessary. To display the serial number and software revision, press and hold the PRETRIP key for five seconds when the unit is turned off.
The serial number is shown at the top of the display and the software revision is shown at the bottom of the display. The HMI Control Panel Serial Number shown ( Software Revision and Serial Number) is 00212. The software revision shown is Revision 2204.
The Date and Time can be viewed and changed using the HMI Control Panel equipped with Software Revision 2204 and later. To display the Date and Time, press and hold the PRETRIP key for five seconds when the unit is turned off.
The HMI Control Panel serial number will be shown at the top of the display and the installed software revision will be shown at the bottom of the display.
Press the PRETRIP key again to display the current date and time as held by the HMI Control Panel. The time shown is 8:33 AM and the date is January 27th.
Time Display
The time displayed by the HMI Control Panel is always shown by means of a 24 hour clock. This time is sometimes referred to as military time or 24 hour time. Refer to the table ( Time Conversion) to convert 24 hour time to 12 hour time.
Morning | Afternoon - Evening | ||
---|---|---|---|
12 Hour | 24 Hour | 12 Hour | 24 Hour |
Midnight | 0000 | Noon | 1200 |
1 AM | 0100 | 1 PM | 1300 |
2 AM | 0200 | 2 PM | 1400 |
3 AM | 0300 | 3 PM | 1500 |
4 AM | 0400 | 4 PM | 1600 |
5 AM | 0500 | 5 PM | 1700 |
6 AM | 0600 | 6 PM | 1800 |
7 AM | 0700 | 7 PM | 1900 |
8 AM | 0800 | 8 PM | 2000 |
9 AM | 0900 | 9 PM | 2100 |
10 AM | 1000 | 10 PM | 2200 |
11 AM | 1100 | 11 PM | 2300 |
12 AM | 1200 | 12 PM | 2400 |
Date Display
Dates can be displayed in one of two ways.
If the US/EU Clock Set Feature is set for US, time is displayed as Month - Day (December 10, 2012).
If the US/EU Clock Set Feature is set for EU, time is displayed as Day - Month (10 December, 2012).
With all SR-3 control systems, the system Date and Time is maintained by the HMI Control Panel. Prior to Software Revision 2204, the Date and Time held by the HMI Control Panel cannot be viewed using the Truck Standard Display.
With all SR-2 control systems, the system Date and Time is maintained by the HMI Control Panel. The Date and Time held by the HMI Control Panel cannot be viewed using the Truck Standard Display.
With all TSR control systems, the system time and date is maintained by the TSD Control Panel. Prior to Software Revision 2204, the time and date held by the TSD Control Panel cannot be viewed using the TSD Control Panel itself.
Date and Time can be checked and changed using WinTrac 5.2 or later. Power must be connected to the Truck Standard Display and the unit must be turned off in order to check or change the Date and Time.
Remove the Truck Standard Display as necessary to gain access to the back of the device.
Turn the unit on to verify that power is available to the Truck Standard Display. Turn the unit back off.
Remove the back cover from the Truck Standard Display.
Connect a Thermo King 9 to 15 pin serial cable from a computer to the 15 pin connector on the back of the Truck Standard Display as shown below.
1. | 15 Pin “D” Connector |
When the cable is connected, verify the red LED indicator located between the Truck Standard Display POWER ON Key and POWER OFF Key is illuminated as shown (). If the red LED indicator is not illuminated, the Date and Time cannot be changed. If the red LED indicator is not illuminated, verify the unit is turned off.
Open WinTrac 5.2 or later. Earlier versions of WinTrac will not work.
Select Seek Device.
Use WinTrac to set the Date and Time. Refer to the WinTrac Help File for additional information.
When the Date and Time is set and checked, disconnected the cable, replace the back cover, and reinstall the Truck Standard Display as required.
Turn the unit on and perform a ServiceWatch Data Logger download using WinTrac to verify the Date and Time are correct.
The Date and Time can be changed using the HMI Control Panel with Software Revision 2204 and later. Display the current Date and Time as shown on the previous pages.
When the current Date and Time is shown on the display, press and hold the Enter key to display US - EU.
Using the Up Arrow Key and/or Down Arrow Key, select the flashing display to either “US” or “EU” as desired.
If the US/EU Clock Set Feature is set for “US”, time is displayed as Month - Day (December 10, 2012).
If the US/EU Clock Set Feature is set for “EU”, time is displayed as Day - Month (10 December, 2012).
Press the Enter key to display the year. The year will flash indicating it can be changed.
Using the Up Arrow Key and/or Down Arrow Key, select the current year.
Press the Enter key to display the Month - Day. The Month will flash indicating it can be changed.
Using the Up Arrow Key and/or Down Arrow Key, select the current month.
Press the Enter key to display the Month - Day. The Day will flash indicating it can be changed.
Using the Up Arrow Key and/or Down Arrow Key, select the current day.
Press the Enter key to display the Time. The Hour setting will flash indicating it can be changed. The hours shown in 24 Hour clock format are “14”, which is the same as 2 PM.
Using the Up Arrow Key and/or Down Arrow Key, select the desired Hour. The hours shown is now 8 AM.
Press the Enter key to display Minutes. The Minute setting will flash indicating it can be changed. The minutes shown are 15 minutes past the hour.
Using the Up Arrow Key and/or Down Arrow Key, select the desired Minutes. The minutes shown are now 33 minutes past the hour.
Press the Enter Key to load the Date and Time. The time shown is 8:33 AM and date is January 27th.
To leave the Date and Time Display press the Off Key. The displays will also time out after one minute.
Verify the Date and Time is correct displaying the current date and time as shown under Displaying Date and Time. Date and time can also be checked using WinTrac 5.3 or later.
1. | Inspect unit condenser grille openings to ensure they are free of debris. |
2. | Inspect unit defrost drain tubes to ensure they are not plugged or kinked. |
3. | Confirm there is sufficient fuel in tank to operate unit for time required for deliveries. |
4. | Inspect the cargo
box compartment inside and out for:
|
5. | Using
the HMI Controller, turn the unit on to pre-cool cargo compartment:
|
Important As product is
being loaded, make sure evaporator air inlets and outlets are not
blocked. Maximum air circulation is necessary to properly maintain
the temperature of the entire load.
|
1. | Inspect unit condenser grille openings to ensure they are free of debris. |
2. | Inspect evaporator defrost drains to ensure they are not plugged or kinked. |
3. | Confirm there is sufficient fuel in tank to operate unit for time required for deliveries. |
4. | Maintain
a minimum of 1219 mm (48 in.) between evaporator air outlets and wall
or bulkhead. |
5. | Inspect cargo box
compartment inside and out for:
|
6. | Using
the HMI Controller, turn the unit on to pre-cool cargo compartment:
|
Important As product is being loaded, make sure evaporator
air inlets and outlets are not blocked. Maximum air circulation is
necessary to properly maintain the temperature of the entire load.
|
Never assume that the product has been loaded properly. Watch for and perform the following tasks. It takes only a few minutes and could save you or your employer considerable time and money later on.
Turn the unit off before opening the cargo box doors to maintain efficient operation. Opening the doors while the unit is running allows warm air to enter the cargo box.
Perform a final check of the load temperature. If the load is too hot or too cold, make a final notation on the manifest.
While inspecting to see that the cargo is loaded properly, make sure the evaporator air inlets and outlets are not blocked.
Close or supervise the closing of the cargo compartment doors. Make sure they are securely locked.
Check to make sure the unit setpoint is set at the desired temperature as listed on the manifest.
If the unit was stopped, restart using the appropriate starting procedure outlined in this manual.
Repeat the after-start inspection.
Defrost the unit 30 minutes after loading by starting a manual defrost cycle.
Note the setpoint to make certain no one has altered the setting since picking up the load.
Note the return air temperature reading. It should be within the desired temperature range. If the return air temperature reading is not within the desired temperature range, it indicates one of the following:
The unit has not had sufficient time to pull down the temperature. Refer to log, if possible, for history of load (for example, above temperature load, properly pre-cooled cargo compartment, length of time on road).
The unit is in defrost or has just completed defrost.
The evaporator is plugged with frost. Initiate a manual defrost cycle. The defrost cycle will be automatically terminated.
Improper air circulation within the cargo compartment. Inspect the cargo compartment (if possible) to determine if the evaporator fans are working and properly circulating the air. Poor air circulation can be due to improper loading of the cargo or shifting of the load, or the fan belt slipping
The unit did not start automatically. If the unit cranked without starting, determine and correct the cause for not starting.
The unit may have a low refrigerant charge. If liquid is not showing in the unit receiver tank sight glass, the refrigerant charge may be low. Adding refrigerant or repairing the refrigeration system requires a competent mechanic. Refer such problems to the nearest Thermo King dealer or authorized Service Center, or call the Thermo King Cold Line telephone number shown on the inside back cover of this manual for referral.
Initiate a Manual Defrost cycle after each Enroute Inspection.
Engine |
T-590, T-690, and T-890: TK374F (Tier 4) T-1090 and UT-1290: TK380F (Tier 4) |
Fuel Type | Ultra low sulfur diesel (ULSD) fuel only [conforming to ASTM
D975] No. 2 diesel fuel under normal conditions No. 1 diesel fuel is acceptable cold weather fuel |
Oil Capacity |
T-590, T-690, and T-890: T-590,
T-690, and T-890: T-1090 and UT-1290: T-1090 and UT-1290: |
Oil Type |
API Classification CJ-4 or CK-4 ACEA Rating E6 FA-4 (10w-30 only) |
Oil Viscosity |
14 F to 122 F (-10 C to 50 C): SAE 15W-40 (Synthetic) 5 to 104 F (-15 to 40 C): SAE 15W-40 5 to 104 F (-15 to 40 C): SAE 10W-30 (Synthetic or Synthetic Blend) -13 to 104 F (-25 to 40 C): SAE 10W-40 -13 to 86 F (-25 to 30 C): SAE 10W-30 -22 to 122 F (-30 to 50 C): SAE 5W-40 (Synthetic) Below -22 F (-30 C): SAE 0W-30 (Synthetic) |
Cooling System Capacity |
T-590, T-690, and T-890: 7.64 quarts (7.23 liters/litres) T-1090 and UT-1290: 8.36 quarts (7.91 liters/litres) |
Engine Coolant Type |
Factory filled with Chevron Delo® XLC extended life coolant (ELC). 55/45 gylcol/water concentration Freeze protection of -40°F/ -40°C Compatible coolants: Chevron Delo® XLC Havoline Delo® XLC (Europe) Caltex Delo® XLC (Asia) OR Meets the performance requirements of both ASTM D6210 and ASTM D3306 OAT extended life coolant, nitrite free |
Important Only OAT extended
life coolants (Chevron Delo® XLC or equivalent) should be added to
Thermo King systems. Conventional coolants should not be used (Typically
identified by green or blue-green color). If a conventional coolant
is combined with the Thermo King factory fill up to 25% by volume,
the coolant must be changed at the next service opportunity. Above
25%, the coolant must be changed immediately. Conventional coolants
dilute/interact with the additive packages of extended life coolant
which significantly reduces the service life of the coolant.
|
|
Engine Thermostat |
160 F (71 C) |
Coolant Expansion Tank Cap Pressure |
10 psig (69 kPa) |
Engine |
T-1090 SPECTRUM: TK380F (Tier 4) |
Fuel Type | Ultra low sulfur diesel (ULSD) fuel only [conforming to ASTM
D975] No. 2 diesel fuel under normal conditions No. 1 diesel fuel is acceptable cold weather fuel |
Oil Capacity |
T-1090 SPECTRUM: T-1090 SPECTRUM: |
Oil Type |
API Classification CJ-4 or CK-4 ACEA Rating E6 FA-4 (10w-30 only) |
Oil Viscosity |
14 F to 122 F (-10 C to 50 C): SAE 15W-40 (Synthetic) 5 to 104 F (-15 to 40 C): SAE 15W-40 5 to 104 F (-15 to 40 C): SAE 10W-30 (Synthetic or Synthetic Blend) -13 to 104 F (-25 to 40 C): SAE 10W-40 -13 to 86 F (-25 to 30 C): SAE 10W-30 -22 to 122 F (-30 to 50 C): SAE 5W-40 (Synthetic) Below -22 F (-30 C): SAE 0W-30 (Synthetic) |
Cooling System Capacity |
T-1090 SPECTRUM: 8.36 quarts (7.91 liters/litres) |
Engine Coolant Type |
Factory filled with Chevron Delo® XLC extended life coolant (ELC). 55/45 gylcol/water concentration Freeze protection of -40°F/ -40°C Compatible coolants: Chevron Delo® XLC Havoline Delo® XLC (Europe) Caltex Delo® XLC (Asia) OR Meets the performance requirements of both ASTM D6210 and ASTM D3306 OAT extended life coolant, nitrite free |
Important Only OAT extended
life coolants (Chevron Delo® XLC or equivalent) should be added to
Thermo King systems. Conventional coolants should not be used (Typically
identified by green or blue-green color). If a conventional coolant
is combined with the Thermo King factory fill up to 25% by volume,
the coolant must be changed at the next service opportunity. Above
25%, the coolant must be changed immediately. Conventional coolants
dilute/interact with the additive packages of extended life coolant
which significantly reduces the service life of the coolant.
|
|
Engine Thermostat |
160 F (71 C) |
Coolant Expansion Tank Cap Pressure |
10 psig (69 kPa) |
Contact your Thermo King dealer for refrigeration service or maintenance.
Control System Voltage | 12.5 Vdc | |
Battery Charging System | 12 volt, 37 amp, brush type, Thermo King Alternator | |
Voltage Regulator Setting | 13.4 to 14.5 volts |
Fuse | Size | Function |
---|---|---|
F2 | 15A | Power to On/Off Switch |
F3 | 40A | Fuel Sol Pull-In/Starter Circuit |
F4 | None | No Fuse |
F5 | 40A | Preheat Circuit |
F6 | 15A | Damper and High Speed Circuits |
F7 | 2A | 8XP Circuit - Controller On Feedback to HMI |
F8 | 5A | 2A Power to CAN Connector J12 |
F9 | 5A | 2A Power to CAN Connector J14 |
F10 | 10A | 8X Power (Install fuse in right position) |
F11 | None | No Fuse |
F12 | 5A | 2A Power to CAN Connector J13 |
F13 | 2A | 8FC Circuit (Remote Status Light/Optional Power) |
F20 | 2A | Alternator Sense |
F21 | 60A | Main Fuse (2 Circuit) |
F25 | 7.5A | HPCO Switch Circuit |
F26 | 5A | Power to CAN Connector J98 |
F10 When fuse F10 is installed in the right position the On/Off keys on the HMI turn the unit on and off. When fuse F10 is installed in the left position the unit will start and run without the HMI controller. |
Voltage/Phase/Frequency | Horsepower | Kilowatts | RPM | Full Load (amps) | Overload Relay Setting (amps) |
---|---|---|---|---|---|
230/3/50 | 6.0 | 4.5 | 1460 | 17.0 | 23 |
200-230/3/60 | 7.2 | 5.4 | 1765 | 19.4 | 23 |
400/3/50 | 6.0 | 4.5 | 1460 | 9.8 | 11.5 |
460/3/60 | 7.2 | 5.4 | 1765 | 9.7 | 11.5 |
Voltage/Phase/Frequency | Horsepower | Kilowatts | RPM | Full Load (amps) | Overload Relay Setting (amps) |
---|---|---|---|---|---|
230/3/60 | 9 | 6.7 | 1768 | 23 | 24 |
200/3/60 | 9 | 6.7 | 1750 | 24 | 24 |
460/3/60 | 9 | 6.7 | 1768 | 11.5 | 12 |
Voltage/Phase/Frequency | Horsepower | Kilowatts | RPM | Full Load (amps) | Overload Relay Setting (amps) |
---|---|---|---|---|---|
230/3/50 | 10.0 | 7.5 | 1460 | 25.3 | 38 |
200-230/3/60 | 12.0 | 8.9 | 1750 | 28.8 | 38 |
400/3/50 | 10.0 | 7.5 | 1460 | 13.90 | 19 |
460/3/60 | 12.0 | 8.9 | 1750 | 14.4 | 19 |
Voltage/Phase/Frequency | Horsepower | Kilowatts | RPM | Full Load (amps) | Overload Relay Setting (amps) |
---|---|---|---|---|---|
230/3/50 | 10.0 | 7.5 | 1460 | 25.3 | 38 |
200-230/3/60 | 12.0 | 8.9 | 1750 | 28.8 | 38 |
400/3/50 | 10.0 | 7.5 | 1460 | 13.90 | 19 |
460/3/60 | 12.0 | 8.9 | 1750 | 14.4 | 19 |
Standby Power cord to remote receptacle | Power plug rating | Power Supply circuit breaker | Plug configuration | Plug type |
12/9HP Motor (T-1090, UT-1290) |
230 V 50A | 50 A | CS8364 | Twistlock |
12/9HP Motor (T-1090, UT-1290) |
460 V, 20A | 20 A | NEMA L16 – 20R | Twistlock |
12/9 HP Motor (T-890) |
230 V 30A | 30 A | NEMA L15 – 30R | Twistlock |
12/9 HP Motor (T-890) |
460V,20A | 20 A | NEMA L16 – 20R | Twistlock |
7.2 HP Motor (T-590, T-690) |
230 V 30A | 30 A | NEMA L15 – 30R | Twistlock |
7.2 HP Motor (T-590, T-690) |
460V,20A | 20 A | NEMA L16 – 20R | Twistlock |
Standby Power cord to remote receptacle | Power plug rating | Power Supply circuit breaker | Plug configuration | Plug type |
12/9HP Motor (T-1090 SPECTRUM) |
230 V 50A | 50 A | CS8364 | Twistlock |
A regular inspection and maintenance program will help to keep your unit in top operating condition. While pre-trip inspections can be performed by the operator (e.g., checking oil and coolant levels), all major and minor service requirements should be handled by a Thermo King dealer for four very important reasons:
They are equipped with the factory recommended tools to perform all service functions
They have factory trained and certified technicians
They have genuine Thermo King replacement parts
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer
After the first week of operation:
Retighten unit mounting bolts
Check belt tension
Check coolant level
Check engine oil level
Check refrigerant level
Check refrigerant oil level
The following general maintenance inspection schedule is provided to assist in monitoring that maintenance.
Pretrip | 2,000 Hours | Annual/ 3,000 Hours | Inspect/Service These Items | Completed |
---|---|---|---|---|
Microprocessor | ||||
• | Run pretrip test (see “Pretrip Test” in Operating Instructions Chapter). | |||
Engine | ||||
• | Check fuel supply. | |||
• | • | Check engine oil level. | ||
• | • | Check condition and tension of belts every 2,000 hrs or 6 months (whichever occurs first). Replace if excessive wear found. | ||
• | Check air cleaner hose for damage. | |||
• | Inspect and clean electric fuel pump filter. | |||
• | Check engine coolant level every 1,000 hours or 6 months (whichever occurs first). | |||
• | Check that engine coolant antifreeze protection is at –40 F (–40 C) every 1,000 hours or 6 months year (whichever occurs first). | |||
• | Dry air cleaner. Replace air cleaner element at 2,000 hours or 1 year (whichever occurs first) | |||
• | Change EMI 2000 (black) fuel filter. | |||
• | Change engine oil and
oil filters (hot). Requires oil with API Classification CJ-4 or CK-4
(ACEA Rating E6 for Europe) and EMI 2000 bypass oil filter.
Note See Service Bulletin SB803 - T-90 Series Oil Bypass Filter
Update. Units built September 30, 2020 and after do not have an oil
bypass filter.
|
|||
• | Check restraining mount (snubber) pre-load adjustment. | |||
• | Drain water from fuel tank and check vent. | |||
• | Check and adjust engine speeds (high and low speed). | |||
• | Check condition of engine mounts. | |||
• | Test fuel injection nozzles at least every 3,000 hours. Based on EPA 40 CFR Part 89. | |||
— | Adjust engine valve clearance every 1,000 hours. | |||
— | Replace fuel return lines between fuel injection nozzles every 10,000 hours or sooner, as required. | |||
— | Change ELC (red) engine coolant every 8 years or 15,000 hours. Units equipped with ELC have an ELC nameplate on the expansion tank. | |||
Electrical | ||||
• | Check controller for alarms. | |||
• | Run pretrip test. | |||
• | Check battery voltage. | |||
• | Inspect battery terminals and electrolyte level. | |||
• | Tighten all electrical connections (where applicable) and inspect all harnesses, wires and terminals for damage or corrosion. If corrosion is present, clean terminals with electrical contact cleaner. | |||
• | Inspect alternator bearings and brushes.* | |||
• | Inspect electric motor bearings (Model 50).* | |||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). | ||||
Refrigeration | ||||
• | • | Check refrigerant level. | ||
• | Check compressor oil level. | |||
• | Check discharge and suction pressures. | |||
• | Check compressor efficiency. | |||
— | Replace dehydrator and compressor oil filter only when the refrigeration system is opened for repair. | |||
Structural | ||||
• | • | Visually inspect unit for fluid leaks. | ||
• | • | Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads). | ||
• | • | Inspect clutch for shoe and anchor bushing wear with a mirror. Check bearings.* | ||
• | Inspect idlers, fanshafts, and jackshaft (if so equipped) for leakage and bearing wear.* | |||
• | Clean entire unit including condenser coils, evaporator coils, and defrost drains. | |||
• | • | Check all unit, fuel tank, engine, and electric motor mounting bolts, brackets, lines, hoses, etc. | ||
• | Inspect drive belt condition and tension | |||
• | Inspect evaporator and condenser fan hardware | |||
• | Inspect fanshaft oil level | |||
— | Replace drive belts every 4,000 hrs. | |||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). |
Pretrip | 1,200 Hours | 2,000 Hours | Annual/ 3,000 Hours | Inspect/Service These Items | Completed |
---|---|---|---|---|---|
Microprocessor | |||||
• | Run pretrip test (see “Pretrip Test” in Operating Instructions Chapter). | ||||
Engine | |||||
• | Check fuel supply. | ||||
• | • | Check engine oil level. | |||
• | • | Check condition and tension (1,200 hrs) of belts. | |||
• | • | Check engine oil pressure hot, on high speed. | |||
• | • | • | • | Listen for unusual noises, vibrations, etc. | |
• | Check air cleaner hose for damage. | ||||
• | Inspect and clean electric fuel pump filter. | ||||
• | Check engine coolant level every 1,000 hours or 6 months (whichever occurs first). | ||||
• | Check that engine coolant antifreeze protection is at –30 F (–34 C) every 1,000 hours or 6 months year (whichever occurs first). | ||||
• | Dry air cleaner. Replace air cleaner element at 2,000 hours or 1 year (whichever occurs first) | ||||
• | Change EMI 2000 (black) fuel filter. | ||||
• | Change engine oil and oil filters (hot). Requires oil with API Classification CJ-4 or CK-4 (ACEA Rating E6 for Europe) and EMI 2000 bypass oil filter. | ||||
• | Check restraining mount (snubber) pre-load adjustment. | ||||
• | Drain water from fuel tank and check vent. | ||||
• | Check and adjust engine speeds (high and low speed). | ||||
• | Check condition of engine mounts. | ||||
• | Test fuel injection nozzles at least every 3,000 hours. Based on EPA 40 CFR Part 89. | ||||
— | Adjust engine valve clearance every 1,000 hours. | ||||
— | Replace fuel return lines between fuel injection nozzles every 10,000 hours or sooner, as required. | ||||
— | Change ELC (red) engine coolant every 5 years or 12,000 hours. Units equipped with ELC have an ELC nameplate on the expansion tank. | ||||
Electrical | |||||
• | Check controller for alarms. | ||||
• | Run pretrip test. | ||||
• | Check battery voltage. | ||||
• | Inspect battery terminals and electrolyte level. | ||||
• | Inspect wire harness for corrosion, damaged wires or connections. | ||||
• | Inspect alternator bearings and brushes.* | ||||
• | Inspect electric motor bearings (Model 50).* | ||||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). | |||||
Refrigeration | |||||
• | • | Check refrigerant level. | |||
• | Check compressor oil level. | ||||
• | Check discharge and suction pressures. | ||||
• | Check compressor efficiency. | ||||
— | Replace dehydrator and compressor oil filter every two (2) years. | ||||
Structural | |||||
• | • | Visually inspect unit for fluid leaks. | |||
• | • | Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads). | |||
• | • | Inspect clutch for shoe and anchor bushing wear with a mirror. Check bearings.* | |||
• | Inspect idlers, fanshafts, and jackshaft (if so equipped) for leakage and bearing wear.* | ||||
• | Clean entire unit including condenser coils, evaporator coils, and defrost drains. | ||||
• | • | • | Check all unit, fuel tank, engine, and electric motor mounting bolts, brackets, lines, hoses, etc. | ||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). |
Pretrip | 750 Hours |
Annual/ 2,000 Hours | Inspect/Service These Items | Completed |
---|---|---|---|---|
Microprocessor | ||||
• | Run pretrip test (see “Pretrip Test” in Operating Instructions Chapter). | |||
Engine | ||||
• | Check fuel supply. | |||
• | Check engine oil level. | |||
• | • | • | Check
engine coolant level.
|
|
• | • | • | Inspect belts for condition and proper tension. | |
• | • | • | Check engine oil pressure hot, on high speed. | |
• | • | • | Listen for unusual noises, vibrations, etc. | |
• | Change engine oil (hot). (2000 hrs with bypass filter or synthetic oil). | |||
• | • | Change oil filters. | ||
• | • | Clean and service crankcase breather. | ||
• | • | Drain water from fuel tank and check vent. | ||
• | • | Replace fuel filter | ||
• | • | Replace dry type air cleaner element. | ||
• | • | Inspect/clean electric fuel pump filter. | ||
• | • | Check air cleaner hose for damage. | ||
— | Check that engine coolant antifreeze protection is at –30 F (–34 C) every 1,000 hours or 6 months year (whichever occurs first). | |||
— | Adjust engine valve clearance every 1,000 hours. | |||
• | Check and adjust engine speeds. | |||
• | Check condition of engine mounts. | |||
• | Check restraining mount (snubber) pre-load adjustment. | |||
— | Clean and test fuel injection nozzles every 3,000 hours. | |||
— | Replace fuel return lines between fuel injection nozzles every 10,000 hours or sooner, as required. | |||
— | Change ELC (red) engine coolant every 5 years or 12,000 hours. | |||
Refrigeration | ||||
• | • | • | Check refrigerant level and compressor oil condition. | |
• | • | • | Check for proper suction pressure. | |
• | Check throttling valve regulating pressure on defrost. | |||
• | Check compressor oil level. | |||
• | Check compressor efficiency and pump down refrigeration system. | |||
• | Replace dehydrator and check discharge and suction pressure. | |||
— | Replace compressor oil filter when refrigeration system work is performed. | |||
Electrical | ||||
• | Check controller for alarms. | |||
• | Run pretrip test. | |||
• | Check battery voltage. | |||
• | • | Inspect/clean battery terminals and check electrolyte level. | ||
• | • | Inspect wire harness for damaged wires or connections. | ||
• | Inspect alternator bearings and brushes.* | |||
• | Inspect electric motor bearings (Model 50).* | |||
Structural | ||||
• | • | • | Check for oil, fuel, coolant and refrigerant leaks. | |
• | • | • | Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads). | |
• | • | Inspect tapered roller bearing idlers for leakage and bearing wear (noise). | ||
• | • | Check and clean evaporator and condenser coils. | ||
• | • | Clean defrost drains. | ||
• | • | Check all unit and fuel tank mounting bolts, brackets, lines, hoses, etc. | ||
• | Inspect clutch.* | |||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). |
Pretrip | 750 Hours |
Annual/ 2,000 Hours | Inspect/Service These Items | Completed |
---|---|---|---|---|
Microprocessor | ||||
• | Run pretrip test (see “Pretrip Test” in Operating Instructions Chapter). | |||
Engine | ||||
• | Check fuel supply. | |||
• | Check engine oil level. | |||
• | • | • | Check
engine coolant level.
|
|
• | • | • | Inspect belts for condition and proper tension. | |
• | • | • | Check engine oil pressure hot, on high speed. | |
• | • | • | Listen for unusual noises, vibrations, etc. | |
• | Change engine oil (hot). (2000 hrs with bypass filter or synthetic oil). | |||
• | • | Change oil filters. | ||
• | • | Clean and service crankcase breather. | ||
• | • | Drain water from fuel tank and check vent. | ||
• | • | Replace fuel filter | ||
• | • | Replace dry type air cleaner element. | ||
• | • | Inspect/clean electric fuel pump filter. | ||
• | • | Check air cleaner hose for damage. | ||
— | Check that engine coolant antifreeze protection is at –30 F (–34 C) every 1,000 hours or 6 months year (whichever occurs first). | |||
— | Adjust engine valve clearance every 1,000 hours. | |||
• | Check and adjust engine speeds. | |||
• | Check condition of engine mounts. | |||
• | Check restraining mount (snubber) pre-load adjustment. | |||
— | Clean and test fuel injection nozzles every 3,000 hours. | |||
— | Replace fuel return lines between fuel injection nozzles every 10,000 hours or sooner, as required. | |||
— | Change ELC (red) engine coolant every 5 years or 12,000 hours. | |||
Refrigeration | ||||
• | • | • | Check refrigerant level and compressor oil condition. | |
• | • | • | Check for proper suction pressure. | |
• | Check throttling valve regulating pressure on defrost. | |||
• | Check compressor oil level. | |||
• | Check compressor efficiency and pump down refrigeration system. | |||
• | Replace dehydrator and check discharge and suction pressure. | |||
— | Replace compressor oil filter when refrigeration system work is performed. | |||
Electrical | ||||
• | Check controller for alarms. | |||
• | Run pretrip test. | |||
• | Check battery voltage. | |||
• | • | Inspect/clean battery terminals and check electrolyte level. | ||
• | • | Inspect wire harness for damaged wires or connections. | ||
• | Inspect alternator bearings and brushes.* | |||
• | Inspect electric motor bearings (Model 50).* | |||
Structural | ||||
• | • | • | Check for oil, fuel, coolant and refrigerant leaks. | |
• | • | • | Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads). | |
• | • | Inspect tapered roller bearing idlers for leakage and bearing wear (noise). | ||
• | • | Check and clean evaporator and condenser coils. | ||
• | • | Clean defrost drains. | ||
• | • | Check all unit and fuel tank mounting bolts, brackets, lines, hoses, etc. | ||
• | Inspect clutch.* | |||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). |
Pretrip | 1,200 Hours |
2,000 Hours |
Annual/ 3,000 Hours | Inspect/Service These Items | Completed |
---|---|---|---|---|---|
Microprocessor | |||||
• | Run pretrip test (see “Pretrip Test” in Operating Instructions Chapter). | ||||
Engine | |||||
• | Check fuel supply. | ||||
• | • | Check engine oil level. | |||
• | • | Check condition and tension (1,200 hrs) of belts. | |||
• | • | Check engine oil pressure hot, on high speed. | |||
• | • | • | • | Listen for unusual noises, vibrations, etc. | |
• | Check air cleaner hose for damage. | ||||
• | Inspect and clean electric fuel pump filter. | ||||
• | Check engine coolant level every 1,000 hours or 6 months (whichever occurs first). | ||||
• | Check that engine coolant antifreeze protection is at –30 F (–34 C) every 1,000 hours or 6 months year (whichever occurs first). | ||||
• | Dry air cleaner. Replace air cleaner element at 2,000 hours or 1 year (whichever occurs first) | ||||
• | Change EMI 2000 (black) fuel filter. | ||||
• | Change engine oil and oil filters (hot). Requires oil with API Classification CJ-4 or CK-4 (ACEA Rating E6 for Europe) and EMI 2000 bypass oil filter. | ||||
• | Check restraining mount (snubber) pre-load adjustment. | ||||
• | Drain water from fuel tank and check vent. | ||||
• | Check and adjust engine speeds (high and low speed). | ||||
• | Check condition of engine mounts. | ||||
• | Test fuel injection nozzles at least every 3,000 hours. Based on EPA 40 CFR Part 89. | ||||
— | Adjust engine valve clearance every 1,000 hours. | ||||
— | Replace fuel return lines between fuel injection nozzles every 10,000 hours or sooner, as required. | ||||
— | Change ELC (red) engine coolant every 5 years or 12,000 hours. Units equipped with ELC have an ELC nameplate on the expansion tank. | ||||
Electrical | |||||
• | Check controller for alarms. | ||||
• | Run pretrip test. | ||||
• | Check battery voltage. | ||||
• | Inspect battery terminals and electrolyte level. | ||||
• | Inspect wire harness for damaged wires or connections. | ||||
• | Inspect alternator bearings and brushes.* | ||||
• | Inspect electric motor bearings (Model 50).* | ||||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). | |||||
Refrigeration | |||||
• | • | Check refrigerant level. | |||
• | Check compressor oil level. | ||||
• | Check discharge and suction pressures. | ||||
• | Check compressor efficiency. | ||||
— | Replace dehydrator and compressor oil filter every two (2) years. | ||||
Structural | |||||
• | • | Visually inspect unit for fluid leaks. | |||
• | • | Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads). | |||
• | • | Inspect clutch for shoe and anchor bushing wear with a mirror. Check bearings.* | |||
• | Inspect idlers and jackshaft (if so equipped) for leakage and bearing wear.* | ||||
• | Clean entire unit including condenser coils, evaporator coils, and defrost drains. | ||||
• | • | • | Check all unit, fuel tank, engine, and electric motor mounting bolts, brackets, lines, hoses, etc. | ||
* With belt removed, spin bearings by hand. Listen for noise (bearings roll freely). |
Pretrip | 1,200 Hours | Annual/ 3,000 Hours | Inspect/Service These Items | Completed |
---|---|---|---|---|
Electrical | ||||
• | • | Inspect wire harness for damaged wires or connections. | ||
• | Inspect/replace DC fan motors. | |||
Structural | ||||
• | • | • | Visually inspect unit for fluid leaks. | |
• | • | Visually inspect unit for damaged, loose or broken parts. | ||
• | • | Clean entire unit including evaporator coils and defrost drains. | ||
• | Check all mounting bolts, brackets, lines, hoses, etc. |
Thermo King Dealership Name and Number | |
Inspector / Technician’s Name | |
Date Inspection Completed | |
Thermo King Unit / Model | |
Unit Serial Number | |
Current Hour Meter Reading | |
Comments: |
The serial number of your unit, the engine, or the compressor may be required when contacting a Thermo Dealer or the Emergency Cold Line service. Record these numbers for quick access when needed.
1. | Serial nameplate on right end of evaporator frame behind cover |
1. | Serial nameplate on right end of evaporator frame behind cover |
1. | Serial nameplate on right end of evaporator frame behind cover |
1. | Serial nameplate on right end of evaporator frame behind cover |
If you can’t get your unit operating and need assistance, you can locate a Thermo King Dealer anywhere in the United States by going to thermoking.com or by using the Thermo King North American Service Directory (available from any Thermo King Dealer). If you are unable to reach a Dealer, call the Toll Free Emergency Cold Line Number (888) 887-2202. The answering service will assist you in reaching a Dealer to get the help you need. The Cold Line is answered 24 hours a day by personnel who will do their best to get you quick service at an authorized Thermo King Dealer.
If you need assistance, and you have tried the Thermo King Container Service Directory (available from any Thermo King Dealer) to reach a Dealer without success, call the Toll Free Emergency Marine Cold Line Number (800) 227-2506 or International number +1 (512) 712 1399. The answering service will assist you in reaching a Dealer to get the help you need. The Cold Line is answered 24 hours a day by personnel who will do their best to get you quick service at an authorized Thermo King Dealer.
Please contact your nearest Thermo King dealer for terms of the Thermo King North American Self Powered Truck Unit Limited Warranty.
Your Thermo King unit is covered by the diesel engine manufacturer’s EPA and ARB Supplemental Emissions Warranty. Complete details of this emission warranty can be found at www.thermoking.com.
Last Updated : 10/27/2023