Operating Theory

Magnum+ and CFF Operating Mode Function Chart

Chill Loads Setpoints at -9.9 C (14.4 F) and Above Frozen Loads Setpoints at -10 C (14 F) and Below  
Cool w/Mod Heat Defrost Cool Null Defrost Unit Function
1         Evaporator Fans High Speed1
1     1   Evaporator Fans Low Speed1
      1 Evaporator Fans Off1
        Proportional-integral Derivative (Supply Air) Control
        Return Air Sensor Control
        Evaporator Coil Sensor Control
        Compressor On
        Compressor Vapor Injection On (valve energized)2
        Condenser Fan On3
    4     Digital Control Valve Modulating (energized)4
5     Electric Heaters Pulsing or On (energized)5

SF Operating Mode Function Chart

Super Freezer Setpoints at -10 C (14 F) and Below  
Cool Null Defrost Unit Function
      Evaporator Fans High Speed1
  Evaporator Fans Low Speed1
    Evaporator Fans Off1
      Proportional-integral Derivative (Supply Air) Control
  Return Air Sensor Control
    Evaporator Coil Sensor Control
    Compressors On (Compressor High T and Compressor LowT)
      Compressor Vapor Injection On (valve energized)2
    Condenser Fan On3
      Digital Control Valve Modulating (energized)4
    Liquid Injection Valve (energized)
    Electric Heaters Pulsing or On (energized)5

1Setpoint temperature and controlling mode setting determine the evaporator fan speed:

  • Normal Operation: Chill Loads - High or low speed fans; Frozen Loads - Low speed fans or no fans.

2Vapor injection valve:

  • Chill, Frozen, or Power Limit Mode: When the cool capacity is 100 percent.

  • Compressor High Temperature Protection: When the compressor discharge temperature exceeds 138 C (280 F).

3Condenser fan pulses on and off on a 30 second duty cycle to maintain a minimum condenser temperature:

  • Chill Loads: Controller maintains a minimum 30 C (86 F) condenser temperature.

  • Frozen Loads: Controller maintains a minimum 20 C (68 F) condenser temperature.

4Digital Control valve modulates:

  • Chill Loads - whenever the unit is in a Cooling mode; Power Limit - whenever the unit is in Power Limit mode.

  • Dehumidification: When the Dehumidify mode is set to On, the supply air temperature must be In-range to energize the electric heaters.

    • When the humidity is two percent or more above humidity setpoint, the controller (energizes) the heaters.

5Controller energizes electric heaters for heat, defrost and dehumidification:

  • Heat mode (compressor off): If supply air temperature is too low, heaters pulse on and off on a 60 second duty cycle.

  • Defrost mode: Heaters are on until evaporator coil temperature increases to terminate defrost.