A-500E Single and Multi-Temperature Units

A-500E Series Single and Multi-Temperature Units

i Introduction

This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.

This manual is published for informational purposes only. Thermo King® makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Service Department should be consulted.

This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.

Thermo King’s warranty shall not apply to any equipment which has been so installed, maintained, repaired or altered as, in the manufacturer’s judgment, to affect its integrity.

Manufacturer shall have no liability to any person or entity for any personal injury, property damage or any other direct, indirect, special, or consequential damages whatsoever, arising out of the use of this manual or any information, recommendations or descriptions contained herein. The procedures described herein should only be undertaken by suitably qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.

There is nothing complicated about operating and maintaining your Thermo King unit, but a few minutes studying this manual will be time well spent.

Performing pre-trip checks and enroute inspections on a regular basis will minimize operating problems. A regular maintenance program will also help to keep your unit in top operating condition. If factory recommended procedures are followed, you will find that you have purchased the most efficient and dependable temperature control system available.

All service requirements, major and minor, should be handled by a Thermo King dealer for four very important reasons:

  • They are equipped with the factory recommended tools to perform all service functions.

  • They have factory trained and certified technicians.

  • They have genuine Thermo King replacement parts.

  • The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.

 

Copies of the approved Thermo King documentation can be found on the Thermo King iService Portal: http://iservice.thermoking.com/esa.

Machine Information Policy

Use of this product serves as acceptance of the Thermo King Machine Information Policy available at: www.europe.thermoking.com. This product includes an optional feature that collects and shares Machine Information with Thermo King. Separate terms may apply when a customer has entered into an agreement with Thermo King. Customers that would like to opt-out of sharing Machine Information with Thermo King should forward such inquiries to the email address Opt-Out@ThermoKing.com.

Use of this product serves as acceptance of the FRIGOBLOCK Machine Information Policy available at: www.europe.thermoking.com. This product includes an optional feature that collects and shares Machine Information with FRIGOBLOCK. Separate terms may apply when a customer has entered into an agreement with FRIGOBLOCK. Customers that would like to opt-out of sharing Machine Information with FRIGOBLOCK should forward such inquiries to the email address Opt-Out@ThermoKing.com.

Software License

TK Americas: The product includes software that is licensed under a non‐exclusive, non-sublicensable, terminable and limited license to use the software as installed on the product for its intended purpose. Any removal, reproduction, reverse engineering, or other unauthorized use of the software is strictly prohibited. Hacking the product or installing unapproved software may void the warranty. The owner or operator shall not reverse engineer, decompile, or disassemble the software, except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this limitation. The product may include third party software separately licensed as specified in any documentation accompanying the product or in an about screen on a mobile application or website that interfaces with the product.

EMEA: The product includes software that is licensed under a non‐exclusive, non-sublicensable, terminable and limited license to use the software as installed on the product for its intended purpose. Any removal, reproduction, reverse engineering, or other unauthorized use of the software is strictly prohibited. Hacking the product or installing unapproved software may void the warranty. The owner or operator shall not reverse engineer, decompile, or disassemble the software, except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this limitation. The product may include third party software separately licensed as specified in any documentation accompanying the product or in an about screen on a mobile application or website that interfaces with the product. You are obliged to complete the declaration for “THERMO KING EQUIPMENT SOFTWARE LICENSE AGREEMENT” before you put your unit in operation.

This is located in your language at the following location: https://www.emea-user-manuals.thermoking.com “THERMO KING EQUIPMENT SOFTWARE LICENSE AGREEMENT”.

Emergency Assistance

Thermo Assistance is a multi-lingual communication tool designed to put you in direct contact with an authorized Thermo King dealer.

Thermo Assistance should only be contacted for breakdown and repair assistance.

To use this system, you need the following information before you call: (phone charges will apply)

  • Contact Phone Number

  • Unit Type

  • Thermostat Temperature Setting

  • Ambient temperature

  • Present Load Temperature

  • Probable Cause of Fault

  • Warranty Details of the Unit

  • Payment Details for the Repair

Leave your name and contact number and a Thermo Assistance Operator will call you back. At this point you can give details of the service required and the repair will be organized.

No payment at point of repair for customers with a ThermoKare service contract or with a guaranty of payment from their Thermo King or FRIGOBLOCK home-dealer

Please note that Thermo Assistance cannot guarantee payments and the service is designed for the exclusive use of refrigerated transporters with products manufactured by Thermo King Corporation.

General Inquires and Unit Maintenance

For general inquiries please contact your local Thermo King and/or FRIGOBLOCK dealer.

Go to www.europe.thermoking.com and select dealer locator for your local Thermo King/FRIGOBLOCK dealer.

Or refer to the Service Directory for contact information.

Or use a Application for mobile devices, download TK Tek-Marine or TK Controller.

Customer Satisfaction Survey Assistance/Feedback

Let your voice be heard!

Your feedback will help improve our manuals. The survey is accessible through any internet-connected device with a web browser.

Scan the Quick Response (QR) code or click Technical Publications EMEA Feedback to complete the survey.

Need assistance finding technical literature, to report missing content, or to provide feedback on our technical literature? Email Thermo King Americas Publications at thermokingamericaspublications@thermoking.com.

Chapter 1: Safety

1.1: Danger, Warning, Caution, and Notice

Thermo King®/ FRIGOBLOCK recommends that all service be performed by a Thermo King/FRIGOBLOCK dealer and to be aware of several general safety practices.

Thermo King® recommends that all service be performed by a Thermo King dealer and to be aware of several general safety practices.

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this unit depend upon the strict observance of these precautions. The four types of advisories are defined as follows:

    Danger
  • Hazard
  • Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
    Warning
  • Hazard
  • Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
    Caution
  • Hazard
  • Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury and unsafe practices.
    Notice
  • Hazard
  • Indicates a situation that could result in equipment or property-damage only accidents.

1.2: General Safety Practices

    Danger
  • Risk of Injury
  • Keep hands and loose clothing clear of fans and belts at all times when the unit is operating with the doors open.
    Warning
  • Personal Protective Equipment (PPE) Required
  • A battery can be dangerous. Lithium-ion batteries are potentially hazardous. The combustion gas from these batteries is toxic and can present a serious FIRE HAZARD if damaged, defective, or improperly used. A battery stores enough electricity to burn you if it discharges quickly. Always wear goggles or safety glasses and personal protective equipment when working with a battery. Do not replace the battery with any type other than the one approved by Thermo King for this unit.
    Warning
  • Risk of Injury
  • Do not apply heat to a closed cooling system. Before applying heat to a cooling system, drain it. Then flush it with water and drain the water. Antifreeze contains water and ethylene glycol. The ethylene glycol is flammable and can ignite if the antifreeze is heated enough to boil off the water.
    Warning
  • Risk of Injury
  • Temperatures above 120 degrees F (50 degrees C) can cause serious burns. Use an infrared thermometer or other temperature measuring device before touching any potentially hot surfaces.

    Warning
  • Risk of Injury
  • This unit operates with 48 volts dc. While this voltage is not considered dangerous, the large amount of amperage available can cause severe burns if shorted or grounded. Do not wear jewelry, watches, or rings when working in on this unit because they increase the risk of shorting out electrical circuits, damaging equipment, or causing severe burns.

    Caution
  • Sharp Edges
  • Exposed coil fins can cause lacerations. Service work on the evaporator or condenser coils should only be accomplished by a certified Thermo King technician.

1.3: Automatic Start/Stop Operation

    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Turn the unit On/Off switch Off before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King unit.

    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Disconnect the Hard Stop/Disable Auto Start switch before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King unit.

    Caution
  • Risk of Injury
  • The unit can start and run automatically any time the unit is turned on. Turn the Microprocessor On/Off switch Off before doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel should attempt to service your Thermo King Frigoblock unit.

1.4: Battery Installation and Cable Routing

       

    Warning
  • Hazard of Explosion
  • An improperly installed battery could result in a fire, explosion, or injury. A Thermo King approved battery must be installed and properly secured to the battery tray.
    Warning
  • Hazard of Explosion
  • Improperly installed battery cables could result in a fire, explosion, or injury. Battery cables must be installed, routed, and secured properly to prevent them from rubbing, chaffing, or making contact with hot, sharp, or rotating components.
    Warning
  • Fire Hazard
  • Do not attach fuel lines to battery cables or electrical harnesses. This has the potential to cause a fire and could cause serious injury or death.
       

  • Conventional Batteries

    Warning
  • Personal Protective Equipment (PPE) Required
  • A battery can be dangerous. A battery contains a flammable gas that can ignite or explode. A battery stores enough electricity to burn you if it discharges quickly. A battery contains battery acid that can burn you. Always wear goggles or safety glasses and personal protective equipment when working with a battery. If you get battery acid on you, immediately flush it with water and get medical attention.

    Warning
  • Personal Protective Equipment (PPE) Required
  • A battery can be dangerous. A battery contains a flammable gas that can ignite or explode. A battery stores enough electricity to burn you if it discharges quickly. A battery contains battery acid that can burn you. Always wear goggles or safety glasses and personal protective equipment when working with a battery. If you get battery acid on you, immediately flush it with water and get medical attention.

  • AGM Batteries

    Warning
  • Personal Protective Equipment (PPE) Required
  • Overcharging or over-discharging of an AGM Battery. There is a very real possibility of inducing enough heat into an AGM battery to initiate thermal runaway if the battery is charged at too high a voltage. This could cause your AGM battery to get very hot. Always wear personal protective equipment when working with a battery.

  • Lithium Ion Batteries

    Warning
  • Personal Protective Equipment (PPE) Required
  • A battery can be dangerous. Lithium-ion batteries are potentially hazardous. The combustion gas from these batteries is toxic and can present a serious FIRE HAZARD if damaged, defective, or improperly used. A battery stores enough electricity to burn you if it discharges quickly. Always wear goggles or safety glasses and personal protective equipment when working with a battery. Do not replace the battery with any type other than the one approved by Thermo King for this unit.

    Warning
  • Hazard of Explosion
  • Always cover battery terminals to prevent them from making contact with metal components during battery installation. Battery terminals grounding against metal could cause the battery to explode.
    Caution
  • Hazardous Service Procedures
  • Set all unit electrical controls to the OFF position before connecting battery cables to the battery to prevent the unit from starting unexpectedly and causing personal injury.
    Notice
  • Equipment Damage
  • Do not connect other manufacturers’ equipment or accessories to the unit or to the Thermo King batteries unless approved by Thermo King. Failure to do so can result in severe damage to equipment and void the warranty.

1.5: Refrigerant

    Danger
  • Hazardous Gases - Personal Protective Equipment (PPE) Required
  • Refrigerant in the presence of an open flame, spark, or electrical short produces toxic gases that are severe respiratory irritants which can cause serious injury or possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

    Danger
  • Hazardous Gases
  • The refrigeration system is regulated by EU regulation known as "F-Gas" and /or local laws. All regulated refrigeration service procedures must be performed by a certified technician, using approved equipment and complying with all EU and local laws.
    Danger
  • Hazardous Gases - Personal Protective Equipment (PPE) Required!
  • Refrigerant in the presence of an open flame, spark, or electrical short produces toxic gases that are severe respiratory irritants which can cause serious injury or possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and F–Gas guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

    Danger
  • Refrigerant Vapor Hazard
  • Do not inhale refrigerant. Use caution when working with refrigerant or a refrigeration system in any confined area with a limited air supply. Refrigerant displaces air and can cause oxygen depletion, resulting in suffocation and possible death. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
    Warning
  • Personal Protective Equipment (PPE) Required
  • Refrigerant in a liquid state evaporates rapidly when exposed to the atmosphere, freezing anything it contacts. Wear butyl lined gloves and other clothing and eye wear when handling refrigerant to help prevent frostbite. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

Although fluorocarbon refrigerants are classified as safe, use caution when working with refrigerants or in areas where they are being used.

Note These hazard statements refer to servicing of the unit.

1.6: Refrigerant Oil

Observe the following precautions when working with or around refrigerant oil and when servicing the unit:

    Warning
  • Personal Protective Equipment (PPE) Required
  • Protect your eyes from contact with refrigerant oil. The oil can cause serious eye injuries. Protect skin and clothing from prolonged or repeated contact with refrigerant oil. To prevent irritation, wash your hands and clothing thoroughly after handling the oil. Rubber gloves are recommended. When working with or around hazardous chemicals, ALWAYS refer to the applicable Material Data Safety Sheets (MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.

Important Please note that it is recommended to evacuate all passengers if a refrigerant leak is suspected. Please use your own specific company evacuation procedure.

1.7: First Aid

REFRIGERANT

  • Eyes: For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical attention.

  • Skin: Flush area with large amounts of warm water. Do not apply heat. Remove contaminated clothing and shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection. Get prompt medical attention. Wash contaminated clothing before reuse.

  • Inhalation: Move victim to fresh air and use Cardio Pulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.

  • Frost Bite: In the event of frost bite , the objectives of First Aid are to protect the frozen area from further injury, warm the affected area rapidly, and to maintain respiration.

REFRIGERANT OIL

  • Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.

  • Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.

  • Inhalation: Move victim to fresh air and use Cardio Pulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.

  • Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.

BATTERY ACID

  • Eyes: Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention. Wash skin with soap and water.

  • Skin: Immediately remove contaminated clothing. Wash skin with large volumes of water, for at least 15 minutes. Wash skin with soap and water. Do not apply fatty compounds. Seek immediate medical assistance.

  • Inhalation: Provide fresh air. Rinse mouth and nose with water. Seek immediate medical assistance.

  • Ingestion: If the injured person is fully conscious: make the person drink extensive amounts of milk. Do not induce vomiting. Take the injured person immediately to a hospital.

ELECTRICAL SHOCK

Take IMMEDIATE action after a person has received an electrical shock. Get quick medical assistance, if possible.

The source of the shock must be quickly stopped, by either shutting off the power or removing the victim. If the power cannot be shut off, the wire should be cut with an non-conductive tool, such as a wood-handle axe or thickly insulated cable cutters. Rescuers should wear insulated gloves and safety glasses, and avoid looking at wires being cut. The ensuing flash can cause burns and blindness.

If the victim must be removed from a live circuit, pull the victim away with a non-conductive material. Use wood, rope, a belt or coat to pull or push the victim away from the current. DO NOT TOUCH the victim. You will receive a shock from current flowing through the victim’s body. After separating the victim from power source, immediately check for signs of a pulse and respiration. If no pulse is present, start Cardio Pulmonary Resuscitation (CPR). If a pulse is present, respiration might be restored by using mouth-to-mouth resuscitation. Call for emergency medical assistance.

ASPHYXIATION

Move victim to fresh air and use Cardio Pulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.

1.8: Safety Decals and Locations

Service

The Service decal is located inside the Engine compressor bay doors. This decal gives you the information to access/download your unit operator manual, but also the safety icons associated with your unit. These safety icons are directly associated with the information within this chapter. You can see the explanations for these icons starting from General Safety Practices.

Note This decal only contains symbols of warning for the operation of the unit.

Service Decal

Operation

The Operation decal is located on your HMI. Navigate to this using the following steps.

  • From the Standard Display, Select the Main Menu. See (HMI Control Panel) for instructions on navigating the Controller Menu’s

  • From the Main Menu, Select “System”

  • From the System Menu, Select “Summary”.

  • Select Soft Key 3 to enter the “Legal” Menu.

This decal gives you the information to access/download your unit operator manual and other supporting documentation and in many supported languages.
Operation QR Code in HMI

Condenser and Evaporator Fans

Be aware of warning nameplates in the following locations:

  • On bulkhead

  • On belt guard

  • On rear of evaporator housing

Fan Warning Nameplate
1. Rotating Fans: Risk of Injury! Caution Rotating Fan blade operating. Keep hands, hair, cloths and all object clear. Prior to completing any inspections or working on any part of the unit
  1. Press the OFF key on the HMI control panel.

  2. Open the Engine compressor bay doors.

  3. Turn the On/Off switch to the “Off” position.

2. Automatic Start/Stop Operation: Risk of Injury! The unit can start and run automatically any time without warning. Prior to completing any inspections or working on any part of the unit
  1. Press the OFF key on the HMI control panel.

  2. Open the Engine compressor bay doors.

  3. Turn the On/Off switch to the “Off” position.

3. Rotating belt: Risk of Injury! Rotating belt. Keep clear. Prior to completing any inspections or working on any part of the unit
  1. Press the OFF key on the HMI control panel.

  2. Open the Engine compressor bay doors.

  3. Turn the On/Off switch to the “Off” position.

Refrigerant and Compressor Oil

Refrigerant nameplate is located on frame inside door.

Refrigerant and Compressor Oil Nameplate

Electrical Warnings

Magnetic Warning Nameplate
High Voltage Warning Nameplate

Chapter 2: Unit Description

2.1: General Information

The Thermo King Advancer A-500e unit is a one piece, self-contained, electric powered cooling/heating trailer unit designed for single temperature multi-temperature trailer applications. The unit mounts on the front of the trailer with the evaporator extending through an opening in the front wall. It features a fully programmable microprocessor controller designed exclusively for transport refrigeration applications. The compressor, electric fans and electric blowers are powered by an AC generator connected to an external electric power source.

Multi-Temperature Units: Spectrum model systems consist of a host unit with a single evaporator and one (or two) remote evaporator units. The host unit contains compressor, system controls and an evaporator. Refrigerant lines and wire harnesses connect the host unit to the remote evaporators. Several compartment configurations are possible. The temperature in each compartment is maintained by a separate controller (except when the unit is set to control at a single temperature). The systems are flexible enough to allow each compartment to be set at any temperature.

Note Remote evaporator fans are powered by separate electric motors.

Thermo King A-500e Unit

2.2: Thermo King Reciprocating Compressor

This trailer unit is equipped with a 4-cylinder 30.0 cu. in. (492 cm3) displacement Thermo King X430 reciprocating compressor.

The SLXi units (except SLXi-100) are equipped with a 4-cylinder 492 cm3 (30.0 cu. in.) displacement Thermo King X430 reciprocating compressor. The SLXi-100 unit is equipped with a 4-cylinder 426 cm3 (25.9 cu. in.) displacement Thermo King X426 reciprocating compressor.

The SLXi-DRC units are equipped with a 4-cylinder 30.0 cu. in. (492 cm3) displacement Thermo King X430 reciprocating compressor.

SLXi Local units are equipped with a 4-cylinder 30.0 cu. in. (492 cm3) displacement Thermo King X430P reciprocating compressor.

Advancer S-DRC units are equipped with a 4-cylinder 30.0 cu. in. (492 cm3) displacement Thermo King X430P reciprocating compressor.

2.3: Electronic Throttling Valve

Note SLXi-100 or SLXi-200 are equipped with a Mechanical Throttling Valve (MTV).
Note T-1200R and T-1200R Spectrum ONLY

The Electronic Throttling Valve (ETV) provides enhanced control of the refrigeration system as follows:

  • Allows the refrigeration system to fully utilize the power capabilities of the engine under varying conditions.

  • Provides an additional measure of protection against high discharge pressures.

  • Protects the engine from high coolant temperature shutdowns.

  • Provides a means of precise temperature control.

2.4: A-Series Controller Control System

Thermo King’s A-Series Controller is a microprocessor control system designed exclusively for a transport refrigeration system. The A-Series Controller’s integrated HMI (Human Machine Interface) control panel allows the operator to perform the following functions:

  • Power Up and Power Down Unit

  • Display and Change Language

  • Display and Change Setpoint

  • Display and Initiate Defrost

  • Display System Status of Engine, Refrigeration, Power and Control

  • Display and Clear Alarms

The unit will operate in either Cycle-Sentry or Continuous Run mode of operation as selected by the operator using the HMI Control Panel.

See “Operating Instructions” for more information about the A-Series Controller.

CYCLE-SENTRY™ Stop-Start Operation

The CYCLE-SENTRY Start-Stop fuel saving system provides optimum operating economy. When CYCLE-SENTRY Mode is selected the unit will start and stop automatically to maintain setpoint and the battery charged.

Continuous Run Operation

When Continuous Mode is selected, the unit starts automatically and runs continuously to maintain setpoint and provide constant airflow.

2.5: Telematics TracKing® ConnectedSuite

TracKing: These units come with TracKing communication device and Bluetooth® as standard.

Note Your unit may not have a standard configuration and therefore may not include this facility. Please contact your Thermo King Dealer for more information.

TracKing: These units come with TracKing communication device and Bluetooth® as option.

Note Your unit may not have a standard configuration and therefore may not include this facility. Please contact your Thermo King Dealer for more information.

TracKing: Whisper™ Pro models equipped with the TracKing communication device and Bluetooth® as standard, while other units offer TracKing (TracKing communication device and Bluetooth®) as an optional feature.

Note Your unit may not have a standard configuration and therefore may not include this facility. Please contact your Thermo King Dealer for more information.

You can also download from your App store the appropriate App to connect, and manage your unit from your mobile device. Please contact your Thermo King Representative for more information. Refer to (Specifications TracKing) for Specifications.

This trailer unit is equipped with TracKing Connected Solutions communication device that when enabled allows remote access to unit data. Downloading the Thermo King Reefer mobile app, will allow you to monitor and manage temperature and reefer settings over the road, in the yard or in-cab via Bluetooth®. Contact your Thermo King representative for more information about all the features and options available with TracKing Connected Solutions.

SLXi-DRC units are equipped with TracKing ConnectedSuite communication device that when enabled allows remote access to unit data. Downloading the Thermo King Reefer mobile app, will allow you to monitor and manage temperature and reefer settings over the road, in the yard or in-cab via Bluetooth®.

Advancer S-DRC units are equipped with TracKing ConnectedSuite communication device that when enabled allows remote access to unit data. Downloading the Thermo King Reefer mobile app, will allow you to monitor and manage temperature and reefer settings over the road, in the yard or in-cab via Bluetooth®.

Contact your Thermo King representative for more information about all the features and options available with TracKing ConnectedSuite.

Note Refer to (TracKing® ConnectedSuite ) for Specifications.

SLXi Local units are equipped with TracKing ConnectedSuite communication device that when enabled allows remote access to unit data. Downloading the Thermo King Reefer mobile app, will allow you to monitor and manage temperature and reefer settings over the road, in the yard or in-cab via Bluetooth®.

Contact your Thermo King Dealer for more information about all the features and options available with TracKing ConnectedSuite.

Further Communication Capabilities

Cable connection: when using a laptop with WinTrac software.

ServiceWatch: ServiceWatch is standard equipment. It records operating events, alarm codes, and compartment temperatures as they occur and at preset intervals. This information is typically used to analyze unit performance. Use a USB port to download the ServiceWatch data.

Important A ServiceWatch download can be helpful when diagnosing a problem. Therefore, it is recommended that a ServiceWatch download be performed to help diagnose a problem. A ServiceWatch download must be preformed before contacting the Thermo King Service Department for assistance in diagnosing a problem.

Plug&Play Log Download: Facilitates direct download of files - CSV, Pdf – on a USB memory stick without having to format it to WinTrac.

Service Log: Service Log is a standard Log on this unit. It records operating events, alarm codes, and compartment temperatures as they occur and at preset intervals. This information is typically used to analyze unit performance. Use a USB port to download the Service Log data.

Important A Service Log download can be helpful when diagnosing a problem. Therefore, it is recommended that a Service Log download be performed to help diagnose a problem. A Service Log download must be preformed before contacting the Thermo King Service Department for assistance in diagnosing a problem.

CargoWatch: CargoWatch data logging requires the installation of optional sensors. Up to six temperature sensor/probes and four door switches can be installed. CargoWatch also logs the setpoint. Use the CargoWatch Port to download the CargoWatch data. If optional temperature sensors are installed, the readings are displayed as Datalogger Sensor (1-6) Temperature in the sensor readings. Refer to (Using the Sensors Key).

Compliance Log: Compliance Log data logging requires the installation of an independent sensor. Three door switches can be installed also. Compliance Log also logs the setpoint. Use the U.S.B. Port to download the Compliance Log data. If optional temperature sensors are installed, the readings are displayed as Datalogger Sensor (1 or 2) Temperature in the sensor readings.

Printer Port: This port is used to print trip records from the CargoWatch datatlogger download. It is located inside the control box.

USB key: via the USB port provided as standard, eliminating the need for laptops and cables.

GPRS connection: via TracKing tool which allows online fleet and temperature management.

Wireless communication: As end customers demand increasing temperature traceability, transporters need a simple and effective means of accessing critical data.

2.6: Defrost

Frost gradually builds-up on evaporator coils as a result of normal operation. The unit uses hot refrigerant to defrost the evaporator coil. Hot refrigerant gas passes through the evaporator coil and melts the frost. The water flows through collection drain tubes onto the ground. The methods of defrost initiation are Automatic and Manual.

Automatic Defrost: The H.M.I. automatically initiates timed or demand defrost cycles. The H.M.I. can be programmed to initiate timed defrost cycles at intervals of 2, 4, 6, 8, or 12 hours. Demand defrost cycles occur if the differences between the return air temperature, discharge air temperature, and coil temperature exceed certain limits. The unit can enter defrost cycles as often as every 30 minutes if required.

Automatic Defrost: The SR-4 automatically initiates timed or demand defrost cycles. The SR-4 microprocessor can be programmed to initiate timed defrost cycles at intervals of 2, 4, 6, 8, or 12 hours. Demand defrost cycles occur if the differences between the return air temperature, discharge air temperature, and coil temperature exceed certain limits. The unit can enter defrost cycles as often as every 30 minutes if required.

Manual Defrost: In Manual Defrost mode, the operator initiates a defrost cycle. Refer to (Initiating a Manual Defrost Cycle).

Note The unit will not perform a Manual Defrost Cycle unless the unit has been turned on with the ON key, the unit is running in Continuous or CYCLE-SENTRY Mode (or shut down in CYCLE-SENTRY Null Mode), and the coil temperature is below 45°F (7°C) 7°C (45°F).

TSR/TSR-3 Microprocessor Controller: The Microprocessor Controller is programmed to automatically initiate timed and forced defrost cycles. The TSR/TSR-3 uses temperature sensors to determine if forced defrost is required.

Manual Defrost: In Manual Defrost mode, the operator initiates a defrost cycle.

Note The unit will not perform a Manual Defrost Cycle unless the unit has been turned on with the ON key, the unit is running in Continuous or CYCLE-SENTRY Mode (or shut down in CYCLE-SENTRY Null Mode), and the coil temperature is below 45°F (7°C) 7°C (45°F).

Manual Defrost: In Manual Defrost mode, the operator initiates a defrost cycle. Refer to (Defrost Mode).

Note The unit will not perform a Manual Defrost Cycle unless the unit has been turned on with the ON key, the unit is running in Continuous or CYCLE-SENTRY Mode (or shut down in CYCLE-SENTRY Null Mode), and the coil temperature is below 45°F (7°C) 7°C (45°F).

2.7: Opening the Front Doors

To open the front doors to access the engine compartment, pull the door handle out. To close the door, push the door shut and latch the handle securely.

2.8: Unit Protection Devices

High Pressure Cutout Switch: The high pressure cutout switch is located on the compressor discharge manifold. If the compressor discharge pressure becomes excessive, the switch opens the circuit to the run relay to stop the unit. The microprocessor will record an alarm code.

High Pressure Relief Valve: This valve is designed to relieve excessive pressure in the refrigeration system. It is located on the receiver tank. If the high pressure relief valve opens, much of the refrigerant will be lost. Take the unit to a Thermo King dealer if this occurs.

Overload Relay - Automatic Reset: An overload relay protects the CMG - Combined Motor Generator. The overload relay opens the circuit to the electric motor if the motor overloads for any reason (e.g., low line voltage or improper power supply) while the unit is on electric standby operation. the A-Series Controller records an alarm code.

Smart FETs: Smart FETs in the microprocessor protect some circuits and components from an overcurrent condition.

Fuses: Fuses are located in harnesses and in the Power Distribution Module (PDM). See below Harness fuses. Please refer to (Power Distribution Module (PDM)) for the PDM fuses, their location and function.

Fuses: Fuses are located in harnesses and in the Power Distribution Module (PDM). All fuses must be serviced only by qualified Thermo King technicians. Contact your nearest Thermo King Dealer for assistance.

48 Volt Fuses in PDM (Single Temperature Units Only)
Fuse Size Function
F8 20A Blowers Condenser Roadside
F10 20A Blowers Condenser Curbside
F12 20A DC Charger
F14 20A Blowers Evaporator Roadside
F16 20A Blowers Evaporator Curbside
48 Volt Fuses in PDM (Multi Temperature Units Only)
Fuse Size Function
F8 20A Blowers Condenser Roadside
F10 20A Blowers Condenser Curbside
F12 20A Blowers Evaporator Curbside
F14 20A Blowers Evaporator Roadside
F100 3A Fan
F200 50A DCDC Converter
12 Volt Fuses in PDM
Fuse Size Function
F1 5A BlueBox 2 Power Out
F2 5A LPM Power Out
F3 3A 3rd Party Power Out
F4 5A PSM Power Out
F5 5A HMI Power Out
F6 5A Printer Power Out
F7 10A ECU Power Out

12 Volt Fuses in Harness
Fuse Size Function
  40A Charge Supply
  20A LPM (Low Power Module)
  20A HPM (High Power Module

Chapter 3: Manual Pretrip Inspection

Pretrip inspections are an important part of a preventative maintenance program designed to minimize operating problems and breakdowns. Perform this pretrip inspection before every trip involving refrigerated cargo.

Note Pretrip inspections are not intended to take the place of regular maintenance inspections.

Fuel: Verify the diesel fuel supply is adequate to guarantee engine operation to the next check point. Allow for maximum fuel consumption of 3.8 Litres (one gallon) per hour of engine operation.

    Caution
  • Service Procedures
  • Turn the unit off before attempting to check the engine oil.

Engine Oil: Check the engine oil level. It should be at the Full mark when the dipstick is threaded all the way into the oil pan. Do not overfill.

    Caution
  • Hazardous Pressures
  • Do not remove expansion tank cap while coolant is hot.

Engine Coolant: The engine coolant must have antifreeze protection to -34 C (-30 F). Add coolant if alarm code s active. Check and add coolant to the expansion tank.

Note Refer to Specifications (Engine) where it is clearly states which coolant types are allowed to be used in this unit.

Battery: Verify the battery terminals are tight and free of corrosion.

Note All truck and trailer units will have a small battery drain when the unit is off. The battery can be drained even quicker if there are aftermarket options or third party devices connected to the unit which consume battery power.

This will cause the battery to become discharged over time.

Apart from the obvious inconvenience of having to charge the battery, it is also liable to damage battery cell material and cause the life of the battery to be shorter than acceptable.

Therefore, to ensure the battery remains in optimum condition during periods when the unit is not being used, Thermo King strongly recommends to switch on the unit at least once each week and run for 30 minutes or longer to keep the battery safe.

If the EnergyONE battery is drained after a long idle period, it will need to be recharged using an automatic programmable battery charger (Thermo King does not recommend the use of manual battery chargers on dry cell batteries).

Failure to do so may result in warranty for the battery being rejected.

Alternatively, Thermo King offers a solar panel option which would negate the requirement to switch off the microprocessor switch during long unit idle periods. For more information, please contact your local Thermo King dealership.

Compressor:

Important To maintain the integrity of the compressor shaft seal and to prevent loss of refrigerant, it is recommended to run the unit at least once each week for 30 minutes or longer.

Belts: Verify belts are in good condition and adjusted to the proper tension. For more information about belt tension, see the Specifications chapter.

Electrical: Check the electrical connections to verify they are securely fastened. Wires and terminals should be free of corrosion, cracks, and moisture.

Structural: Visually inspect the unit for leaks, loose or broken parts, and other damage.

Coils: Verify condenser and evaporator coils are clean and free of debris.

  • Washing with clean water should be sufficient.

  • The use of cleaning agents or detergents is strongly discouraged due to the possibility of degradation of the construction.

  • If using a power washer, the nozzle pressure should not exceed 600 psi (41 bar). For the best results, spray the coil perpendicular to the face of the coil. The spray nozzle should be kept between 1 inch and 3 inches (25 to 75 millimeters) from the coil surface.

  • If necessary to use a chemical cleaner or detergent, use a cleaner that does not contain any hydrofluoric acids and is between 7 and 8 on the pH scale. Verify dilution instructions provided by the detergent supplier are followed. In case of doubt about the compatibility of the detergent with the type of materials listed above, always ask the supplier a written confirmation of the compatibility.

  • Should a chemical cleaner be required, it is MANDATORY that all components are thoroughly rinsed with water even if the instructions of the cleaner specify that it is a “no rinse” cleaner.

    Notice
  • Equipment Damage
  • Failure to comply with above mentioned guidelines will lead to a shortened life of the equipment to an indeterminable degree and also may void your warranty.
Note The repeated transportation of meat and fish waste can cause extensive corrosion to the evaporator coils and evaporator section tubing over time due to ammonia formation and can reduce the lifespan of the coils. Appropriate additional measures should be taken to protect the coils against the aggressive corrosion that can result from transportation of such products.

Cargo Box: Check the interior and exterior of the cargo box for damage. Any damage to the walls or insulation must be repaired.

Note On trailers equipped with units qualified for pharmaceutical applications - under ThermoKing protocol inspect the integrity of the air chute.

Cargo Doors: Verify the cargo doors and weather seals are in good condition. The doors should latch securely and the weather seals should fit tightly.

Defrost Drains: Check the defrost drain hoses to verify they are open and are equipped with one way kazoo valves at the drain exit.

TracKing Module:

  • Check that the module is turned on and communicating.

  • For Whisper Pro Enabled TracKing, it is recommended to check at some stage throughout your journey if the Advanced Controller automatically switches to “High Speed Lock Out” in an area designated for this - i.e., PIEK assigned Zone.

      Note
    1. For more information on how to set up PIEK assigned Zones, please refer to your unit installation manual, please contact your Thermo King Dealer Representative..

    2. For further best practices, please visit www.europe.thermoking.com/best-practices.

Chapter 4: A-Series Controller

Thermo King has applied the latest advances in computer technology to develop a device that controls temperature and unit function, and displays operating information quickly and accurately.

There is nothing complicated about learning to operate the A-Series Controller, but you will find that a few minutes studying the contents of this manual will be time well spent.

A-Series Controller

Highlights of the A-Series Controller

New Software and Controller

  • Software developed by Thermo King.

  • Hardware Developed with a Global Leader in rugged electronics.

Improvements

  • Intuitive interface similar to a mobile face

  • Bigger screen size with higher resolution and colors

  • All in one screen display dashboard

  • Icon based Interface

  • Improved ease of use

  • Superior Controls

  • Fully accessible and visible HMI orientation angle.

4.1: Microprocessor On/Off Switch

The microprocessor On/Off switch is located behind the lower roadside panel inside the Engine compressor bay compartment. This switch supplies or removes all electrical power to the microprocessor control system and all electrical circuits.

The switch must be in the ON position for the unit to operate.

The switch should be placed in the OFF position only when servicing the unit or if the unit is not going to be operated for one week or longer. Placing the switch in the OFF position will help prevent parasitic battery voltage loss and a dead battery.

Microprocessor On/Off Switch

Chapter 5: Operating Instructions

5.1: HMI Control Panel

    Caution
  • Risk of Injury
  • Do not operate the HMI Control Panel until you are completely familiar with its function.

The A-Series Controller HMI (Human Machine Interface) control panel is used to operate the unit. The HMI has a display and twelve touch sensitive keys. The display is capable of showing both text and graphics.

The Human/Machine Interface (HMI) Control Panel is integrated into the Controller and is used to operate the unit and display unit information. The HMI/MAC communicates with the Low Power Module (LPM) and High Power Module (HPM) via a controller area network (CAN) bus. The HMI Control Panel consists of a display and 12 touch-sensitive keys. The display is capable of showing both text and graphics. The HMI Control Panel also contains the Temperature Log data logger.

HMI Control Panel Details
Keypad Details
1. On Key 6. Soft Key 3
2. Off Key 7. Defrost Key
3. Display Screen (5.7 “) 8. Cycle-Sentry Key
4. Soft Key 2 9. Accept/Enter Key
5. Soft Key 1 10. Navigation Keys (x4)

Control Panel Display and Keys      
  1 On Key (Hard Key)
  2 Off Key (Hard Key)
  3 Display
  4 Soft Key 2
  5 Soft Key 1
  6 Soft Key 3
  7 Defrost Key
  8 Cycle-Sentry Key
  9 Accept/Enter Key
  10 Navigation Keys (x4)
     

Hard Keys

There are four hard keys with dedicated functions.


ON Key: Used to turn the unit on.


Off Key: Used to turn the unit off.


Defrost Key: Press this key to initiate a Manual Defrost cycle.


CYCLE SENTRY Key: Used to select Cycle Sentry Mode or Continuous Mode operation if allowed by OptiSet Plus.

There are four hard keys with dedicated functions.

ON Key: Used to turn the unit on.
Off Key: Used to turn the unit off.
Defrost Key: Press this key to initiate a Manual Defrost cycle.
CYCLE SENTRY Key: Used to select Cycle Sentry Mode or Continuous Mode operation.

Soft Keys

There are three soft keys. The function of soft keys change depending on the operation being performed.


SOFT Keys: The three keys directly under the display are soft keys. The function of soft keys change depending on the operation being performed. If a soft key is active, its function will be shown in the display directly above the key.

There are three soft keys. The function of soft keys change depending on the operation being performed.

SOFT Keys: The three keys directly under the display are soft keys. The function of soft keys change depending on the operation being performed. If a soft key is active, its function will be shown in the display directly above the key.

Navigation Keys

There are four navigation keys that allow the operator to scroll up, down, left and right to view or make changes to a selected display.


UP Key: Used to scroll up through the display menu.


DOWN Key: Used to scroll down through the display menu.


LEFT Key: Used to scroll to the left of the display menu.


RIGHT Key: Used to scroll to the right of the display menu.

There are four navigation keys that allow the operator to scroll up, down, left and right to view or make changes to a selected display.

UP Key: Used to scroll up through the display menu.
DOWN Key: Used to scroll down through the display menu.
LEFT Key: Used to scroll to the left of the display menu.
RIGHT Key: Used to scroll to the right of the display menu.

Accept/Enter Key

The center key is used to accept changes. It is also used to enter changes made by the operator.


ACCEPT/ENTER Key: Used to accept or enter changes.

The center key is used to accept changes. It is also used to enter changes made by the operator.

ACCEPT/ENTER Key: Used to accept or enter changes.

5.1.1: Turning Unit On

Note The Main On/Off Switch must be in the “ON” position for the unit to operate.
Note The Service Switch must be in the “ON” position for the unit to operate.

Turn unit on by pressing the ON Key.

Note System startup sequence may take up to 60 seconds.
Diesel engine preheats and starts are automatic in both Continuous Mode and Cycle Sentry Mode. The engine preheat and start will be delayed in Cycle Sentry mode if there is no current need for the engine to run.
Note If Electric Standby is active, there may be some additional prompts before the engine/electric motor will start.
System Startup Sequence Shown
Once the system startup sequence is completed, the Standard Display will appear and unit will start in the Diesel Mode (if no Electric Standby is detected).
Note Operating Mode: The unit retains the last user configured operating mode when power cycled. i.e. If the unit was running in Continuous Mode, and then power is cycled, the unit would still remain in continuous mode.
The temperature setpoint or other system changes can now be made if required.
Standard Display Showing - Unit Running in Diesel and Continuous Mode

Turn the unit on by pressing the ON Key. Diesel engine preheats and starts are automatic in both Continuous Mode and Cycle Sentry Mode. The engine preheat and start will be delayed in Cycle Sentry mode if there is no current need for the engine to run.

    Note
  1. System startup sequence may take up to 60 seconds.

  2. If Electric Standby is active, there may be some additional prompts before the engine/electric motor will start.

System Startup Sequence
Once the system startup sequence is completed, the Standard Display will appear and the unit will start in Diesel Mode (if no Electric Standby is detected). The temperature setpoint or other system changes can now be made if required.
Note Operating Mode: The unit retains the last user configured operating mode when power cycled. i.e., if the unit was running in Continuous Mode, and power is cycled, the unit would still remain in continuous mode.

Turn unit on by pressing the ON Key.

    Note
  1. System startup sequence may take up to 60 seconds.

  2. If Electric Standby is active, there may be some additional prompts before the electric motor will start.

Once the system startup sequence is completed, the Standard Display will appear and the unit will start in Electric Standby Mode.
Note Operating Mode: The unit retains the last user configured operating mode when power cycled. i.e., if the unit was running in Continuous Mode, and power is cycled, the unit would still remain in continuous mode.
The temperature setpoint or other system changes can now be made if required.

Turn the unit on by pressing the ON Key.

    Note
  1. System startup sequence may take up to 60 seconds.

  2. If Electric Standby is active, there may be some additional prompts before the electric motor will start.

System Startup Sequence
Once the system startup sequence is completed, the Standard Display will appear and the unit will start in Electric Standby Mode. The temperature setpoint or other system changes can now be made if required.
Note Operating Mode: The unit retains the last user configured operating mode when power cycled. i.e., if the unit was running in Continuous Mode, and power is cycled, the unit would still remain in continuous mode.

5.1.1.1: Turning Unit Off

Turn the unit off by pressing the OFF Key. When the off key is pressed, the display will briefly show “SYSTEM IS POWERING DOWN”. After the power-down sequence is complete the display will be blank.

Note When the unit is turned off using the HMI Controller, no temperature control is available. If the unit is not going to be operated for one week or longer, placing the Service Switch in the OFF position will help prevent parasitic battery voltage loss and a dead unit battery.
System Powering Down Sequence Shown

Turn Unit Off:

Turn the unit off by pressing the OFF Key. When the off key is pressed, the display will briefly show “SYSTEM IS POWERING DOWN”. After the power down sequence is complete, the display will be blank.

Note When the unit is turned off using the HMI, no temperature control is available. If the unit is not going to be operated for one week or longer, placing the Service Switch in the OFF position will help prevent parasitic battery voltage loss and a dead unit battery.
System Powering Down Sequence – Blank Screen

5.2: Standard Display

The Standard Display is the base from which all other display operations are launched. The Standard Display appears after the unit startup sequence is completed.

Single Temperature Display
1. Status Bar — Displays unit information across top of screen.
2. Model Type/Specification — Displays unit type.
3. TracKing Signal — Displays telematics signal strength.
4. Time w/Time Zone — Displays current time. Time Zone shows that you are now in a region +/- from the time shown.
5. Trailer Temp — Displays actual box temperature and the user-configured controlling sensor. Default controlling sensor is Return Air.
6. Setpoint — Displays temperature defined by user.
7. LOCK — Is customizable in Main Menu Plus (Default screen is LOCK).
8. SETPOINT — Used for critical functions.
9. SYSTEM — Is customizable in Main Menu Plus.
10. DASHBOARD - See Dashboard Section for details. (Dashboard)

Multi–Temperature Display
1. Status Bar — Displays unit information across top of screen.
2. Model Type/Specification — Displays unit type.
3. TracKing Signal — Displays telematics signal strength.
4. Time w/Time Zone — Displays current time. Time Zone shows that you are now in a region +/- from the time shown.
5. Trailer Temp — Displays actual box temperature and the user-configured controlling sensor. Default controlling sensor is Return Air.
6. Setpoint — Displays temperature defined by user.
7. LOCK — Is customizable in Main Menu Plus (Default screen is LOCK).
8. SETPOINT — Used for critical functions.
9. SYSTEM — Is customizable in Main Menu Plus.
10. DASHBOARD - See Dashboard Section for details. (Dashboard)

Standard Display and Icon Descriptions
Single Temperature Display
     
  1 Status Bar - Displays unit information across top of screen.
  2 Model Type/Specification - Displays unit type.
  3 TracKing Signal - Displays telematics signal strength.
  4 Time w/Time Zone - Displays current time. Time Zone shows that the user is now in a region +/- from the time shown.
  5 Trailer Temp - Displays actual box temperature and the user-configured controlling sensor. Default controlling sensor is Return Air.
  6 Setpoint - Displays temperature defined by user.
  7 LOCK - Customizable in Main Menu Plus (Default screen is LOCK).
  8 SETPOINT - Used for critical functions.
  9 SYSTEM - Customizable in Main Menu Plus.
  10 DASHBOARD - Refer to (Dashboard) for details.
     

Standard Display and Icon Descriptions      
  1 Status Bar - Displays unit information across top of screen.
  2 Model Type/Specification - Displays unit type.
  3 TracKing Signal - Displays telematics signal strength.
  4 Time w/Time Zone - Displays current time. Time Zone shows that the user is now in a region +/- from the time shown.
  5 Trailer Temp - Displays actual zone/box temperature and the user-configured controlling sensor. Default controlling sensor is Return Air.
  6 Setpoint - Displays zone temperature setpoint defined by user.
  7 LOCK - Customizable in Main Menu Plus (Default screen is LOCK).
  8 SETPOINT - Used for critical functions (zone setpoint configuration, turn on/off zones).
  9 SYSTEM - Customizable in Main Menu Plus.
  10 DASHBOARD - Refer to (Dashboard) for details.
     

1. Status Bar - Displays unit information across top of screen. 6. Setpoint – Displays temperature defined by user.
2. Model Type/Specification — Displays unit type. 7. LOCK – Customizable in Main Menu Plus (Default screen is LOCK).
3. TracKing Signal – Displays telematics signal strength. 8. SETPOINT – Used for critical functions.
4. Time w/Time Zone – Displays current time. Time Zone shows that you are now in a region +/- from the time shown. 9. SYSTEM – Customizable in Main Menu Plus.
5. Trailer Temp — Displays actual box temperature and the user-configured controlling sensor. Default controlling sensor is Return Air. 10. DASHBOARD - See Dashboard Section for details. (Dashboard)

Single Temperature Unit Display
Multi-Temperature Unit Display
1. Status Bar - Displays unit information across top of screen.
2. Model Type/Specification — Displays unit type.
3. TracKing Signal – Displays telematics signal strength.
4. Time w/Time Zone – Displays current time. Time Zone shows that you are now in a region +/- from the time shown.
5. Trailer Temp — Displays actual box temperature and the user-configured controlling sensor. Default controlling sensor is Return Air.
6. Setpoint – Displays temperature defined by user.
7. LOCK – Customizable in Main Menu Plus (Default screen is LOCK).
8. SETPOINT – Used for critical functions.
9. SYSTEM – Customizable in Main Menu Plus.
10. DASHBOARD - See Dashboard Section for details. (Dashboard)

5.2.1: TemperatureWatch Display

The Standard Display defaults to the TemperatureWatch Display after about three minutes of non-use (when no keys are pressed) and no info, check or shutdown alarms are present. The Lock Symbol in the Display Dashboard signifies that the Display is locked.

TemperatureWatch Display for Single Temperature Units
TemperatureWatch Display for Multi-Temperature Units
  1. Press any key to enter the Unlock System Screen.

  2. Verify by selecting “Unlock” at this screen.

  3. You will then be returned to the Standard Display.

The Standard Display defaults to the TemperatureWatch Display after about three minutes of non-use (when no keys are pressed), unit is running in diesel or electric mode, and no information, check, or shutdown alarms are present. The Lock icon in the Display Dashboard signifies that the display is locked. Press any key to enter the Unlock System Screen.

The Standard Display defaults to the TemperatureWatch Display after about three minutes of non-use (when no keys are pressed), unit is running in diesel or electric mode, and no check, or shutdown alarms are present. Press any key to enter the Unlock System Screen.

The Standard Display defaults to the TemperatureWatch Display after about three minutes of non-use (when no keys are pressed), unit is running in electric mode, and no information, check, or shutdown alarms are present. The Lock icon in the Display Dashboard signifies that the display is locked. Press any key to enter the Unlock System Screen.

5.2.2: Dashboard

The Dashboard is located on the right of the Standard Display and is the hub for overall system operation. Similar to a car dashboard, all icons have a defined position and only become lit when active. This allows the operator to quickly identify the unit’s operating mode e.g., Continuous, Cycle-Sentry, Diesel or Electric.

Standard Display with Dashboard on Right Shown
Dashboard Icons and Descriptions
1. Cycle-Sentry: This icon indicates the unit is operating in Cycle-Sentry mode when illuminated. When not illuminated, the unit is operating in Continuous mode.
2. USB Connection Status: This icon indicates a USB flash drive is connected to the Controller when illuminated. When not illuminated, the USB flash drive is not connected/detected.
3. Fuel Level: This icon indicates the trailer unit’s fuel in percentage (if applicable).
4. Auto- Switch: This icon indicates:
  • When illuminated, Auto-Switch Enabled feature is set to ENABLE, allowing unit to switch automatically from Diesel Mode to Electric Mode when standby power is connected and available.

  • Not illuminated, Auto-Switch Enabled feature is set to DISABLE, keeping unit in Diesel Mode. A prompt screen (Yes/No) will appear when standby power is connected and available.

5. Diesel Operation: This icon indicates the unit is operating in Diesel Mode.
6. Electric Operation: This icon indicates the unit is operating in Electric Mode (if applicable).

The Dashboard is located on the right of the Standard Display and is the hub for overall system operation. Similar to a vehicle dashboard, all icons have a defined position and only become illuminated when active. This allows the user to quickly identify the unit’s operating mode e.g., Continuous, Cycle-Sentry, Diesel, or Electric.

Dashboard Icons and Descriptions      
  1 Cycle-Sentry - This icon indicates the unit is operating in Cycle-Sentry mode when illuminated. When not illuminated, the unit is operating in Continuous mode.
  2 USB Connection Status - This icon indicates a USB flash drive is connected to the Controller when illuminated. When not illuminated, the USB flash drive is not connected/detected.
  3 Fuel Level - This icon indicates the trailer unit’s fuel in percentage (if applicable).
  4

Auto-Switch

Illuminated - Auto-Switch Enabled feature is set to ENABLE, allowing unit to switch automatically from Diesel Mode to Electric Mode when standby power is connected and available.

Not Illuminated - Auto-Switch Enabled feature is set to DISABLE, keeping unit in Diesel Mode. A prompt screen (Yes/No) will appear when standby power is connected and available.

  5 Diesel Operation - This icon indicates the unit is operating in Diesel Mode.
  6 Electric Operation - This icon indicates the unit is operating in Electric Mode (if applicable).
     

The Dashboard is located on the right of the Standard Display and is the hub for overall system operation. Similar to a vehicle dashboard, all icons have a defined position and only become illuminated when active. This allows the user to quickly identify the unit’s operating mode e.g., Continuous, Cycle-Sentry, Diesel, or Electric.

Dashboard Icons and Descriptions      
  1 Cycle-Sentry - This icon indicates the unit is operating in Cycle-Sentry mode when illuminated. When not illuminated, the unit is operating in Continuous mode.
  2 USB Connection Status - This icon indicates a USB flash drive is connected to the Controller when illuminated. When not illuminated, the USB flash drive is not connected/detected.
  3 Fuel Level - This icon indicates the trailer unit’s fuel in percentage (if applicable).
  4 Electric Operation - This icon indicates the unit is operating in Electric Mode (if applicable).
  5 Diesel Operation - This icon indicates the unit is operating in Diesel Mode.
     

The Dashboard is located on the right of the Standard Display and is the hub for overall system operation. Similar to a vehicle dashboard, all icons have a defined position and only become illuminated when active. This allows the user to quickly identify the unit’s operating mode e.g., Continuous, Cycle-Sentry or Electric.

1. Cycle-Sentry - This icon indicates the unit is operating in Cycle-Sentry mode when illuminated. When not illuminated, the unit is operating in Continuous mode. 3. OptiSet PRO
2. USB Connection Status - This icon indicates a USB flash drive is connected to the Controller when illuminated. When not illuminated, the USB flash drive is not connected/detected. 4. Electric Operation - This icon indicates the unit is operating in Electric Mode (if applicable).

The Dashboard is located on the right of the Standard Display and is the hub for overall system operation. Similar to a vehicle dashboard, all icons have a defined position and only become illuminated when active. This allows the user to quickly identify the unit’s operating mode e.g., Continuous, Cycle-Sentry or Electric.

Dashboard Icons and Descriptions for Single Temperature Units
Dashboard Icons and Descriptions for Multi-Temperature Units
Dashboard Icons and Descriptions
1. Cycle-Sentry: This icon indicates the unit is operating in Cycle-Sentry mode when illuminated. When not illuminated, the unit is operating in Continuous mode.
2. USB Connection Status: This icon indicates a USB flash drive is connected to the Controller when illuminated. When not illuminated, the USB flash drive is not connected/detected.
3. OptiSet PRO
4. Electric Operation: This icon indicates the unit is operating in Electric Mode (if applicable).

5.2.3: Two Zone Standard Display

The Standard Display is the default display that appears if no other display function is selected. The Two Zone Standard Display shows the return air temperature and setpoint for two zones. The absence of the Cycle Sentry Icon at the top of the display shows that the unit is operating in Continuous Mode. The return air temperature for Zone 1 is -7.9 °C with a -20 °C setpoint. The down-pointing arrow indicates that Zone 1 is cooling. The return air temperature for Zone 2 is –0.6 °C with a 0 °C setpoint. The down-pointing arrow indicates that Zone 2 is also cooling.

The soft key under LOCK allows the user to lock the screen.

The soft key under SETPOINT allows the user to change the zone setpoints & also allows the user to turn the zones ON/OFF. The soft key under SYSTEM allows the user to view SYSTEM information.

5.2.4: Dual Zone / Single Zone Display

When the unit is configured for two zones:

  • The HMI standard display screen will always display dual zone displays

  • The HMI TemperatureWatch display screen will display dual zone displays when the remote zone (zone 2) is NOT turned OFF

  • The HMI TemperatureWatch display screen will display only a single zone display (host zone) when the remote zone (Zone 2) is turned OFF

Zone 1 (Host) ON/OFF?

Zone 2 ON/OFF?

Standard Display Screen

TemperatureWatch Display Screen

ON

ON

Dual Zone Display (2 zones)

Dual Zone Display (2 zones)

ON

OFF

Dual Zone Display (2 zones)

Single Zone Display (Host Zone)

OFF

ON

Dual Zone Display (2 zones)

Dual Zone Display (2 zones)

5.2.5: Turning a Zone On and Off

If the number of zones configured is greater than 1, then all zones can be turned off and on as desired.

Note There must always be at least 1 zone turned ON. It is not possible to turn OFF all zones at the same time.

The state of each zone is retained when the unit is turned off and on. For example, on a two zone unit if Zone 2 is turned off and Zone 1 is turned on and the unit is turned off, the zone states remain as they were. When the unit is turned back on Zone 2 will still be off and Zone 1 will still be on.

Note Units equipped with a remote control may operate in a slightly different manner. Refer to Rear Remote Control Panel for additional details.

For example, to turn Zone 2 off, press Soft Key 2 under SETPOINT and navigate to the Zone 2 using the RIGHT Key:

Press Soft Key 1under ZONE-2 OFF and then press Soft Key 3 under CONFIRM. The display briefly shows the programing process and the display returns to the Standard Display, showing Zone 2 is off:

5.3: Operating the A-Series Controller

Please refer to “TK My Controller” App (Android or iPhone) or your A-Series Drivers Guide for step by step instructions and training on how to use your A–Series controller.

Also “TK Alarm Codes” to help diagnose any alarms. These can be found at the following link: http://www.europe.thermoking.com/tools/

5.3.1: Main Menu

The Main Menu contains several additional submenus that allow the operator to view information and modify unit operation.

To access the Main Menu press the ACCEPT/ENTER key.

Standard Display and Main Menu Display Shown

Standard Display and Main Menu Display Shown for
Single Temperature Units
Standard Display and Main Menu Display Shown for
Multi-Temperature Units

Use the UP, DOWN, LEFT or RIGHT keys to scroll through the menu choices. When the desired selection is shown, press the ACCEPT/ENTER key.

Once you have made your selection, again use the UP, DOWN keys and the ACCEPT/ENTER key to view information or modify unit operation.

When done, navigate to the BACK icon and press the ACCEPT/ENTER key to return to the Standard Display.

Note Each of the Main Menu choices will be explained in detail later.

5.3.2: Fresh/Frozen Range

The Fresh/Frozen Range is fixed at -5 °C. When the setpoint is selected to -5 °C or above, the setpoint panel will change to a Green color which defines the trailer temperature zone as Fresh. When the setpoint is selected to -6 °C or below, the setpoint panel will change to a Blue color which defines the trailer temperature zone as Frozen.

The Arrow on left side of zone temperature measurement indicates if the zone is heating or cooling. If no arrow is displayed next to the zone temperature measurement, the zone is not heating or cooling.

Cool Fresh Cool Frozen
Heat Fresh Heat Frozen

Cool Fresh Cool Frozen
Heat Fresh Heat Frozen

Cool Fresh Cool Frozen
Heat Fresh Heat Frozen

Cool Fresh Cool Frozen
Heat Fresh Heat Frozen

Single Temperature Units
Cool Fresh Cool Frozen
Heat Fresh Heat Frozen
Multi-Temperature Units
Cool Fresh Cool Frozen
Heat Fresh Heat Frozen

5.3.3: Operating Software

Flash Loading

Important Only Thermo King supplied, specific operating software should be used and uploaded by a Thermo King Service Technician or damage to the operating system may result.

5.3.4: Mode Submenu

Mode changes are made using the Mode submenu. The Mode submenu allows the user to change the unit operating modes if allowed. Not all modes may appear depending on the settings selected from Guarded Access. From the Standard Display, press the ACCEPT/ENTER center key. From the Main Menu screen select Mode and press the ACCEPT/ENTER center key.

The enabled mode change screen will appear. Scroll through the enabled features, choose a function, and then press SELECT to change if required.

5.3.5: Language Selection Submenu

After turning the unit ON and the Configuring System is complete, the Language Selection display will appear (if set to ENABLED).

Note English is the default language.

To change the language:

  1. Use navigation keys to scroll to preferred language.

  2. Press Accept/Change Key or Cancel.

  3. The Standard Display with the chosen language will appear next.

  4. Note If no key is pressed in language prompt for 45 seconds then the current language will be retained and the HMI will transition to the Standard Display.
    Language Selection Displays Shown

If Language Selection does not appear on startup, then Language change is not activated. Once you follow the steps below, this will activate the language changer. To change the language:

  1. Access the MAIN MENU by pressing the Accept/Enter Key.

  2. Use the arrow keys to access LANGUAGE.

  3. Use arrow keys to choose language and press the Accept/Enter Key.

  4. Exit the Main Menu.

The Language submenu allows the user to select a language from a list of up to 23 languages at one time. All subsequent displays are shown in the selected language. From the Standard Display, press the ACCEPT/ENTER center key. From the Main Menu screen, select Language and press the ACCEPT/ENTER center key.

Note English is the default language.

To change the language, use the navigation keys to scroll to the preferred language. Press the ACCEPT/ENTER key. The Standard Display with the chosen language will appear next.

Note If no key is pressed in language prompt for 45 seconds, the current language will be retained and the HMI will transition to the Standard Display.

Language Selection Language Change

Language Selection

If the Language submenu does not appear on startup, Language Change will not be activated. To change the language, access the Main Menu by pressing the ACCEPT/ENTER Key. Use the arrow keys to access LANGUAGE. Use the arrow keys to choose the language and press the ACCEPT/ENTER Key. Exit the Main Menu.

5.3.6: Pretrip Submenu (Single Temperature Unit Only)

A Pretrip Test verifies unit operation. This display allows a Pretrip Test to be selected and initiated by the operator. From the Standard Display, press the ACCEPT/ENTER center key. From the Main Menu screen select Pretrip and press the ACCEPT/ENTER center key.

Pretrip Test Conditions

  • Current unit settings are saved and restored at the end of the Pretrip Test or if the unit is turned off and back on.

  • A Pretrip Test can be run in either Diesel or Electric Mode.

  • The unit will auto switch from Diesel Mode to Electric Mode or from Electric Mode to Diesel Mode during a Pretrip Test if these features are enabled and the auto switch conditions occur.

  • Current unit settings are saved and restored at the end of the Pretrip Test or if the unit is turned off and back on.

Conditions Where Pretrip Tests are Not Allowed

  • If any Shutdown Alarms are present. Pretrip tests are allowed with some Check and Log Alarms.

  • If the unit is in Sleep Mode.

  • If the unit is in Service Test Mode, Output Test Mode, or Evacuation Mode.

Pretrip Test Considerations

When performing a Pretrip Test, the following issues should be considered:

  • If running a Pretrip Test on a trailer loaded with dry cargo, verify that proper airflow can occur around the load. If the load restricts airflow, false test results may occur. Also, these units have high refrigeration capacity which results in rapid temperature changes. Sensitive dry cargo may be damaged as a result.

  • If running a Pretrip Test on a trailer that has just been washed down, the extremely high humidity inside the trailer may result in false test results.

  • If running a Pretrip Test on a trailer loaded with sensitive cargo, monitor the load temperature during the test as normal temperature control is suspended during pre-trip operation.

  • Always perform Pretrip Tests with the trailer cargo doors closed to prevent false test failures.

Pretrip Test Sequence

Pretrip tests proceed in the order shown below. A Full Pretrip Test includes all tests. A Running Pretrip Test is started with the engine or electric motor running.

  • Engine Start - The Engine will start automatically.

  • ETV Test - The ETV functionality is checked by closing and opening the ETV and determining an expected change in suction pressure.

  • Speed Test - The expected RPM for engine speed, condenser fan speed, and evaporator fan speed in a high and low speed is checked.

  • Cool Test - The ability of the unit to cool is checked.

  • Heat Test - The ability of the unit to heat is checked.

  • Defrost Test - If the coil temperature is below 14 °C, a defrost cycle is initiated.

  • Cool Return Test - The ability of the unit to return to cool is checked.

  • Report Test Results - The test results are reported as COMPLETED or FAIL when the Pretrip Test is completed. If test result is FAIL or if the unit did not PASS each test step, alarm codes will exist to direct the technician to the source of the problem.

Pretrip tests proceed in the order shown below. A Full Pretrip Test includes all tests. A Running Pretrip Test is started with the electric motor running.

  • ETV Test - The ETV functionality is checked by closing and opening the ETV and determining an expected change in suction pressure.

  • Cool Test - The ability of the unit to cool is checked.

  • Heat Test - The ability of the unit to heat is checked.

  • Defrost Test - If the coil temperature is below 14 °C, a defrost cycle is initiated.

  • Cool Return Test - The ability of the unit to return to cool is checked.

  • Report Test Results - The test results are reported as COMPLETED or FAIL when the Pretrip Test is completed. If test result is FAIL or if the unit did not PASS each test step, alarm codes will exist to direct the technician to the source of the problem.

5.3.7: Brightness Submenu

The brightness of the HMI screen (LCD) display and HMI keypad can be individually adjusted to allow for changing ambient light conditions. The choices available to the operator are HIGH, MEDIUM, LOW, and OFF. OFF actually results in a very dim screen suitable for low light conditions.

Important Before replacing an HMI with no backlight, check the Backlight feature to verify the backlight is turned on.

From the Standard Display, press the ACCEPT/ENTER center key. From the Main Menu screen select Brightness and press the ACCEPT/ENTER center key.

The Brightness submenu will appear. Select either LCD or Keypad and use the left or right keys to make a selection for brightness. When the desired brightness is shown, select ACCEPT.

5.3.8: GeoFence Constraint Active

For A500 A500e Spectrum Whisper Pro unit models:

The HMI status bar will display a Geofence Constraint Active icon when any of the following conditions are met:

  • the control system / TK telematics device is detecting that the unit is in a Geofence constraint zone

  • no CAN communication between control system and TK telematics device

For whisper pro unit models:

The HMI icon is an indicator for the end user to confirm that the unit is operating in PIEK mode to reduce noise and ensure compliance with PIEK certification.

For non-whisper pro unit models:

The HMI icon is an indicator for the end user to confirm that the unit is operating in engine high speed lockout mode to reduce noise. Compliance with PIEK certification is not assured/guaranteed.

When the unit is detected not in a Geofence constraint zone (and CAN communication is established between control system and TK telematics device), no geofence constraint active icon is displayed on HMI status bar.


5.4: Main Menu+ Display

Details

The Main Menu+ Display includes additional system information available to the operator.

Main Menu+ Display Shown
Main Menu+ Alarm Display Shown
Main Menu+ System Status Display Shown

Main Menu+ Display Shown

5.5: Defrost Mode

Defrost cycles are usually initiated automatically based on time and demand.

The operator can also initiate a manual defrost if necessary. Manual defrost is only available if the unit is running and the evaporator coil temperature is less than or equal to 45F (7C).

Note Other features such as door switch settings may not allow manual defrost under certain conditions.
  • If the defrost parameters are met — HMI will display “PROGRAMMING DEFROST“ followed by UNIT IS DEFROSTING”.

  • In Defrost Mode, the trailer temperature box will be replaced by defrost information and trailer temp box and dashboard will change its color to “purple”.

  • Additionally, the return air temperature (trailer temp) will be replaced by the coil icon and a intermediate spinner on top with a display progress bar for the remaining defrost time across the bottom.

    Defrost Mode Displays Shown for Single Temperature Units

    Defrost Mode Displays Shown for Multi-Temperature Units

When the defrost is complete, the HMI will display “EXITING DEFROST” for 2 seconds and return to the standard display.

Defrost Complete Displays Shown for Single Temperature Units
Defrost Complete Displays Shown for Multi-Temperature Units

HMI will display “DEFROST NOT AVAILABLE” if the defrost parameters are not met.

Failed Defrost Display Shown

Defrost cycles are usually initiated automatically based on time and demand. The operator can also initiate a manual defrost if necessary. Manual defrost is only available if the unit is running and the evaporator coil temperature is less than or equal to 7°C (45°F).

Note Other features such as door switch settings may not allow manual defrost under certain conditions.
  • If the defrost parameters are met, the HMI will display “PROGRAMMING DEFROST“ followed by “UNIT IS DEFROSTING”.

  • In Defrost Mode, the trailer box temperature will be replaced by defrost information.

  • Additionally, the return air temperature (trailer temp) will be replaced by the coil icon and an intermediate spinner on top with a display progress bar for the remaining defrost time across the bottom.

Defrost Mode Displays

When the defrost is complete, the HMI will display “EXITING DEFROST” for two seconds and return to the standard display.

HMI will display “DEFROST NOT AVAILABLE” if the defrost parameters are not met.

5.6: Connecting to a Third Party Device

All A–Series trailer units come equipped with dedicated device connection points for external devices. Only these connection points must be used as they prevent battery discharge/depletion of the EnergyONE battery during unit idle periods. The Location of the Power Connections are shown below. Please refer to your third party device connection third party device connection instructions for more information.

5.7: Printing a Trip Report

The optional Thermo King TouchLog datalogger printer allows you to print a record of such things as the unit microprocessor controller identification numbers, dates and times, the setpoint, and the data from the optional Compliance Log sensors . If no sensors are connected, the printed record shows the same information without the sensor data.

  1. Thermo King TouchPrint Printer shown
  2. Locate the printer connector - located inside the unit door (close to the A-Series Controller) as shown below.

  3. Remove the connector cover.

  4. Connect the Printer Connector (From Printer harness) to this Printer Connector.

  5. Connect the spliced wires on the other end of the Printer Harness into the connection location at the back of the Printer.

  6. Please refer to your TK 61009-11-OP TouchPrint Operator Manual at EMEA Operator Manual Website(or third party printer manual) for instructions for setup and use.

Note For additional information concerning the TouchPrint Printer or TouchLog Datalogger contact your Thermo King dealer.

5.8: Alarms

Info Log

Info Log events serve as a notice to take corrective action before a problem becomes severe. Maintenance items such as maintenance hourmeter time-outs are Info Log events. The TemperatureWatch screen is not disabled if only Info Log event(s) are active.

When the unit is turned on, the display will show the Thermo King Logo and then the Configuring System message. The Info Log event notification will appear on the Standard Display.

An Info Log event is indicated by an "information" notification on the display located next to the setpoint. The Info Log event icon will appear.

Check Alarm

A Check alarm is indicated by a check alarm notification on the display located next to the setpoint. The Check alarm icon will appear. This level of alarm serves as a notice to take corrective action before a problem becomes severe. The unit will run with Check alarms but some features and functions may be inhibited. If a Check alarm condition occurs while the unit is running, the alarm icon will appear in the display.

Prevent Shutdown Alarm

A Prevent Shutdown alarm is indicated by an Alarm Active enlarged red icon in the center of the display. The Alarm Active icon will appear. The unit will be temporarily shut down if a Prevent alarm is active. The unit will remain shut down for a timed restart interval or until the fault conditions are corrected and then restart. In some cases, the unit will restart with reduced performance to determine if continued operation is possible. If the alarm does not reoccur with reduced performance, the unit will return to full performance. In general, if the alarm condition reoccurs a defined number of times, the alarm is set as a Shutdown alarm and no further restarts are possible.

Note If the Restart After Shutdown feature in the Guarded Access Menu is set as DISABLED, the control system will regard all prevent shutdown alarms as standard shutdown alarms.

Shutdown Alarm

A Shutdown alarm is indicated by an Alarm Active enlarged red icon in the center of the display. If a Shutdown alarm occurs while the unit is running, it will be indicated by all of the following:

  • The Alarm Active icon will appear.

  • The optional remote alarm light will flash on and off.

  • The optional remote status light (triple combo) will flash on and off.

Shutdown alarms will force the unit into shutdown. The unit will remain in shutdown until the Shutdown alarm is manually cleared.

Exceptions are some engine and electric Shutdown alarms that become Info Log events when switched to the alternate operating mode (diesel to electric or electric to diesel).

Chapter 6: Loading and Inspection Procedures

This chapter describes pre-loading inspections, loading procedures, post-loading procedures, post-loading inspections, and enroute inspections. Thermo King FRIGOBLOCK refrigeration units are designed to maintain the required product load temperature during transit. Follow these recommended loading and enroute procedures to help minimize temperature related problems.

Note When in doubt as to the correct refrigeration requirements and/or loading procedures, call your company office for instructions.

6.1: Pre-Loading Inspection

  1. Pre-cool products before loading. Note any variances on the manifest.

  2. Inspect door seals and vent doors for condition and a tight seal with no air leakage.

  3. Inspect the trailer inside and out. Look for:

    • Damaged or loose trailer skin and insulation

    • Damaged walls, air ducts, floor channels, or “T” flooring

    • Clogged defrost drain tubes

    • Blocked return air bulkhead

  4. Verify that the setpoint temperature is correct for your cargo. Pre-cool the trailer as required.

  5. Supervise product loading to ensure sufficient air space around and through the load. Airflow around cargo must not be restricted. It must be possible for air to flow around the goods within the refrigerated body. The return flow of air to the evaporator is ensured by means of the correct use of pallets or roll cages (e.g. they should never be film-wrapped down to the ground).

    Note If the warehouse is not refrigerated, operate the unit with the doors closed until cargo is ready to be loaded. Then turn off the unit, open the cargo doors and load cargo. When cargo is loaded, close trailer doors and restart the unit. The unit can be operated with the cargo box doors open if the truck is backed into a refrigerated warehouse and the dock door seals fit tightly around the trailer.

  1. Observe the guidelines for load securing. Pay attention to the load height. Telescopic bars securing the load must not be positioned beneath the flat evaporators.

Loading Considerations
1. Correct load height (trailers without chutes) 6. Clear defrost drains
2. Tight doors and seals 7. Good outside air circulation
3. Good air circulation around load 8. Unit inspection
4. Proper cargo temperature (prior to loading) 9. Tight seals
5. Interior/exterior walls and insulation in good condition 10. Maximum load height followed

Loading Considerations
1. Correct load height (trailers without chutes) 6. Clear defrost drains
2. Tight doors and seals 7. Good outside air circulation
3. Good air circulation around load 8. Unit inspection
4. Proper cargo temperature (prior to loading) 9. Tight seals
5. Interior/exterior walls and insulation in good condition 10. Maximum load height followed

Loading Considerations
1. Unit inspection 5. Tight doors
2. Good outside air circulation 6. Good air circulation around load
3. Seals equally compressed 7. Interior/exterior walls and insulation in good condition
4. Clear defrost drains 8. Cargo proper temperature prior to loading

Loading Considerations
1. Unit inspection 5. Tight doors
2. Good outside air circulation 6. Good air circulation around load
3. Gaskets Equally Compressed 7. Cargo at Proper Temperature Prior to Loading
4. Clear defrost drains 8. Interior/exterior walls and insulation in good condition

6.2: Post-Loading Inspection

Post-loading inspections verify the cargo has been loaded properly. To perform a post-load inspection:

  1. Inspect the evaporator outlets for blockage.

  2. Turn the unit off before opening the cargo box doors to maintain efficient operation.

    Note The unit can be operated with the cargo box doors open if the truck is backed into a refrigerated warehouse and the dock door seals fit tightly around the trailer.

  3. Perform a final check of the load temperature. If the load is above or below temperature, make a final notation on the manifest.

    Important Cargo must be pre-cooled to proper temperature before loading. The unit is designed to maintain temperature, not cool an above-temperature load.
  4. Close or supervise the closing of the cargo box doors. Verify they are securely locked.

  5. Verify the setpoint is at the temperature listed on the manifest.

  6. If the unit was stopped, restart using the correct starting procedure. See the Operating Instruction chapter in this manual.

  7. Start a manual defrost cycle 30 minutes after loading. See the Manual Defrost procedure in the manual.

6.3: Enroute Inspections

Complete the following enroute inspection every four hours. This will help minimize temperature related problems.

Inspection Procedure

  1. Verify setpoint is correct.

  2. Check the return air temperature reading. It should be within the desired temperature range.

  3. Initiate a manual defrost cycle after each enroute inspection.

Inspection Troubleshooting

  1. If a temperature reading is not within the desired temperature range, refer to the troubleshooting table ( Inspection Troubleshooting). Correct problem as required.

  2. Repeat the Enroute Inspection every 30 minutes until the compartment temperature is within the desired temperature range. Stop the unit if the compartment temperature is not within the desired temperature range on two consecutive 30 minute inspections, especially if the compartment temperature appears to be moving away from the setpoint.

  3. Immediately contact the nearest Thermo King Service Center Thermo King or FRIGOBLOCK Dealer or your company office.

  4. Take all necessary steps to protect and maintain proper load temperature.

    • Notice
    • Cargo Loss
    • Stop the unit if the compartment temperature remains higher than the desired temperature range from the setpoint on two consecutive 30 minute inspections. Contact the nearest Thermo King Service Center Thermo King or FRIGOBLOCK Dealer or your company office immediately. Take all necessary steps to protect and maintain proper load temperature.
Inspection Troubleshooting
Problem: A return air temperature reading is not within desired temperature range of the setpoint.
Cause Remedy
The unit has not had time to cool down to correct temperature. Refer to the load log history. Look for above temperature load records, properly pre-cooled cargo compartment, length of time on road, etc. Correct as required. Continue monitoring return air temperature until the reading is within the desired temperature range of the setpoint.
Note Ensure cargo is properly pre-cooled prior to loading onto trailer. If 'warm cargo' is loaded onto trailer and reefer is used to cool to setpoint this will result in longer time required to cool down to correct temperature and possibly plugging of evaporator with frost due to increased humidity in trailer compartment.
The unit may have a low refrigerant charge. Check the receiver tank sight glass for refrigerant level. If fluid is not showing in the receiver tank sight glass, the refrigerant charge may be low. A competent refrigeration technician is required to add refrigerant or repair the system. Contact the nearest dealer, authorized Service Center, or call the Thermo King Cold Line for referral. Consult the Table of Contents for Cold Line information or refer to Emergency Assistance section for contact information..
The unit is in defrost or has just completed a defrost cycle. Monitor the return air temperature after the defrost cycle is completed to see if the temperature returns to the desired temperature range of the setpoint.
The evaporator is plugged with frost. Initiate a manual defrost cycle. The defrost cycle will automatically terminate when complete. Continue monitoring the return air temperature until the reading is within the desired temperature range of the setpoint.
Improper air circulation in the cargo compartment. Inspect the unit and cargo compartment to determine if the evaporator fan (3) are working properly circulation the air. Poor air circulation may be due to improper loading of the cargo, shifting of the load, or depending on unit, fan belt slippage or faulty electrical fans. Correct as required. Continue monitoring return air temperature until problem is corrected.
The unit did not start automatically. Determine the cause for not starting. Correct as required. Continue monitoring return air temperature until reading is within desired temperature range of the setpoint.

Multi-Temp Units Only– The unit is being used to cool/heat a single temperature load and does not have the capacity to cool the entire trailer.

A multi-temperature unit may not have the cooling or heating capacity to maintain a specific temperature range throughout an entire trailer.

Chapter 7: Specifications

Engine

Model:
A-360
A-400, A-500 and A-500 Spectrum

Thermo King TK486VMGS5 (NRMM Stage V compliant)
Thermo King TK486VEGS5 (NRMM Stage V compliant)
Fuel Type Diesel fuel must conform to EN590
Oil Capacity

12.3 liters/litres (13 quarts) crankcase and oil filter

Fill to full mark on dipstick

Oil Type

Petroleum Multi-grade Oil: API Type CI-4, ACEA Class E3

Synthetic Multi-grade Oil: API Type CI-4, ACEA Class E3 (after first oil change)

Recommended Oil Viscosity (based on ambient temperature)

-10 C to 50 C (14 F to 122 F): SAE 15W-40 (Synthetic)

-15 to 40 C (5 to 104 F): SAE 15W-40

-15 to 40 C (5 to 104 F): SAE 10W-30 (Synthetic or Synthetic Blend)

-25 to 40 C (-13 to 104 F): SAE 10W-40

-25 to 30 C (-13 to 86 F): SAE 10W-30

-30 to 50 C (-22 to 122 F): SAE 5W-40 (Synthetic)

Below -30 C (-22 F): SAE 0W-30 (Synthetic)

Nominal Engine RPM

A–360: 1200 and 1450 RPM

A-400: 1050, 1200 and 1450 RPM

A-500 and A-500 Spectrum: 1050, 1200, 1450 and 1900 RPM

A-500 Whisper Pro: 1050, 1200, 1450 and 1900 RPM

Engine Coolant Thermostat 71°C
Engine Coolant Type

Conventional Coolant: Conventional coolant (antifreeze) is green or blue-green. GM 6038M or equivalent, low silicate antifreeze mixture, 50/50 antifreeze/water mixture, not to exceed 60/40.

Important Do not mix conventional coolant and ELC. ELC (Extended Life Coolant): ELC is red. Units containing ELC have an ELC nameplate on the expansion tank. Use a 50/50 concentration of any of the following equivalents: Texaco ELC (7997, 7998, 16445, 16447), Havoline Dex-Cool® (7994, 7995), Havoline XLC for Europe (30379, 33013), Shell Dexcool® (94040), Shell Rotella (94041), Saturn/General Motors Dex-Cool®, Caterpillar ELC, Detroit Diesel POWERCOOL® Plus
    Notice
  • System Contamination
  • Do not add GREEN or BLUE-GREEN conventional coolant to cooling systems using RED Extended Life Coolant, except in an emergency. If conventional coolant is added to Extended Life Coolant, the coolant must be changed after 2 years instead of 5 years.
    Notice
  • Equipment Damage
  • Do not use high silicate automobile antifreeze.
Coolant System Capacity 5.3 liters/litres (5.6 quarts)
Radiator Cap Pressure 0.83 bar (12 psi) (88 kPa)
Drive Direct to compressor clutch and belt from electric motor/generator, and belt to water pump.

Filters

Engine Oil Filter EMI 3000 Hour – P/N 11-9182
Fuel Filter EMI 3000 Hour – P/N 11-9342
Air Filter EMI 3000 Hour – P/N 11-9955

Refrigeration System

Contact your Thermo King dealer for refrigeration system service or maintenance.

Electrical Control System

Low Voltage 12.8 Vdc to 48 Vdc
17–36 Vac
Battery Thermo King EnergyONE (880 CCA) AGM battery as standard.
Fuses See your Thermo King Dealer
Battery Charging

Single Temperature as Standard - 12 volt, 37 amp, brush type, Thermo King Alternator

Single Temperature Option - 12 volt, 120 amp, brush type, Thermo King Alternator

Electric Motor

Size/Type Operating Speed Voltage/Phase/Hertz Full Load Amps
9.3 kW Induction 1450 RPM 400 Volt, 3 phase, 50 hertz 19.7 amps
9.5 kW Induction 1740 RPM 460 Volt, 3 phase, 60 hertz 17.1 amps

Standby Power Requirements

Power Supply Circuit Breaker

400/3/50

460/3/60

32 ampere

32 ampere

Power Cord Size 400/3/50

Up to 15m, 6mm2

Over 15m, 10mm2

460/3/60

Up to 15m, 10mm2

Over 15m, 16mm2

Standby Power Requirements

Supply Circuit Breaker: A-500E and A-500E Spectrum 32 amps
When connecting from MOA box to main grid
Extension Cord Size:
  • Up to 15 meters (50 feet) — 6 mm2 (10 gauge) per conductor
  • 15 to 22 meters (50 to 75 feet) — 8 mm2 (8 gauge) per conductor
When connecting from Energ-e Pack charging system to main grid
Extension Cord Size:
  • 10 meters (32 feet) maximum - 6 mm2 (10 gauge) per conductor
  • 400V/50Hz/3 phases + neutral

TracKing

Platform ARM Cortex-A8, 300MHz, 256MB RAM, 4GB Flash, Linux
GSM/GPRS 3G, Sierra HL8548
GPS u-blox NEO-7M
Bluetooth Version 4.0 Bluetooth Classic /Bluetooth Low Energy (BLE)
Serial Ports 2 External Serial Ports for TracKing extensions or Third-Party Connect
Operating voltage 12 to 24 V DC
Backup Battery Single cell Li-Ion 3.6V Nominal, 2600mAh, 9.36Wh
Environmental Storage Temperature -40 to +85 C

Chapter 8: Warranty

Terms of the Thermo King Trailer Unit warranty are available on request from your local Thermo King dealer.

Please also refer to TK 61508-2-WA Thermo King EMEA Trailer Unit Limited Warranty for Trailer Units.

Chapter 9: Maintenance Inspection Schedule

9.1: Inspection and Service Intervals

Inspection and Service intervals are determined by the number of unit operating hours and by the age of the unit. Examples are shown in the table below. Your Dealer will prepare a schedule to suit your specific needs.

Service Record: Each inspection and service performed should be recorded on your Dealer Service Record.

Interim Inspection Complete PM Full Service

A Service


Every 1500 hours or every 12 months (whichever comes first)

B Service


Every 3000 hours or every 24 months (whichever comes first)

C Service


Every 9000 hours or every 72 months (whichever comes first)

Pretrip Inspect/Service These Items
Run Pretrip Test
Check fuel supply
Check and adjust coolant/engine oil levels
Listen for unusual noises, vibrations, etc
Visually inspect unit for fluid leaks. (fuel, coolant, oil and refrigerant)
Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads if so equipped)
Visually inspect belt(s)
Note For further best practices, please go to www.europe.thermoking.com/best-practices.
Pretrip Inspect/Service These Items
Run Pretrip Test
Listen for unusual noises, vibrations, etc
Visually inspect unit for fluid leaks. (oil and refrigerant)
Visually inspect unit for damaged, loose or broken parts (includes air ducts and bulkheads if so equipped)
Visually inspect belt(s)
Note For further best practices, please go to www.europe.thermoking.com/best-practices.

Chapter 10: Serial Number Locations

Multi-Temperature Units

Serial Number Plate Location (S-3A shown)
1. Serial nameplate on right end of evaporator frame behind cover
A-Series Serial Number Locations (inside unit) Shown

Chapter 11: Recover Refrigerant

At Thermo King®, and FrigoBlock we recognize the need to preserve the environment and limit the potential harm to the ozone layer that can result from allowing refrigerant to escape into the atmosphere.

We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the atmosphere.

In addition, service personnel must be aware of Federal local regulations concerning the use of refrigerants and the certification of technicians. For additional information on regulations and technician certification programs, contact your local THERMO KING dealer.